2008-08-27 16:19:15 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| *NOTE: SUBMITTED ISOMETRIC IS NOT INDICATING |
| CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE |
| REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS WITH NO |
| CORRESPONDING LENGTHS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| *NOTE: SUBMITTED ISOMETRIC IS NOT INDICATING THE ABOVE |
| GROUND PIPING MATERIAL AND PIPE SIZE. THE ABOVE GROUND |
| PIPE SIZE NEEDS TO BE 1 INCH (1") SCH. 40 METALLIC |
| (REFERENCE THE ATTACHED FBC-2004 FUEL GAS SIZING TABLE |
| 402.4(2) ATTACHED TO THESE COMMENTS INDICATING THIS) |
| PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE AND SIZING |
| TABLE 402.4(2). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |