Plan Review Details - Permit 08080489
Plan Review Stops For Permit 08080489
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-26 Cont ID  
Sent By mjacobs Date 2008-09-26 Time 14:20 Rev Time 0.00
Received By mjacobs Date 2008-09-26 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-16 Cont ID  
Sent By mjacobs Date 2008-09-16 Time 09:05 Rev Time 0.00
Received By mjacobs Date 2008-09-15 Time 14:21 Sent To  
Notes
2008-09-16 09:05:04 
 9-16-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **NO RESPONSE NOT ADDRESSED**
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3) 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. OK
 (2) FIRM LICENSE NUMBER. OK
 (3) NAME OR IDENTIFICATION OF PROJECT. OK
 (4) DATE PREPARED. OK
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. OK
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4) OK
  
 **NO RESPONSE NOT ADDRESSED**
 5) THE APPLICATION INDICATES THE PROJECT AS AN INTERIOR
 REMODEL. ARE THERE ANY WALLS, DOORS OR ANY OTHER
 SYSTEMS BEING ADDED OR DEMOED? CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC
 106.1.1.
  
 **NO RESPONSE NOT ADDRESSED**
 6) IF THIS IS TRULY AN INTERIOR REMODEL, STATE THE
 LEVEL OF ALTERATION ON THE PLANS PER FBC (EXISTING)
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By mjacobs Date 2008-09-08 Time 10:19 Rev Time 0.00
Received By mjacobs Date 2008-09-08 Time 07:35 Sent To  
Notes
2008-09-08 10:19:18 
 9-8-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3) 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4) THE ADDRESS OF THE PROJECT SHALL BE INDICATED ON
 EACH SHEET INCLUDING THE SUITE NUMBER. THIS INFORMATION
 IS TO PROVIDE CONFORMITY TO THE DEPARTMENT RECORD
 RETENTION PROGRAM. FBC 106.1.3*
  
 5) THE APPLICATION INDICATES THE PROJECT AS AN INTERIOR
 REMODEL. ARE THERE ANY WALLS, DOORS OR ANY OTHER
 SYSTEMS BEING ADDED OR DEMOED? CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC
 106.1.1.
  
 6) IF THIS IS TRULY AN INTERIOR REMODEL, STATE THE
 LEVEL OF ALTERATION ON THE PLANS PER FBC (EXISTING)
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-09-29 Cont ID  
Sent By btrobaug Date 2008-09-29 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2008-09-29 Time 14:27 Sent To PC
Notes
2008-09-29 14:40:32 
  
  
 IT IS MY UNDERSTANDING FROM THE OWNERS REP THAT THE
 FIXTURES MENTIONED ARE EXISTING./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2008-09-18 Time 15:25 Sent To PC
Notes
2008-09-18 15:25:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENTS AS THE PREVIOUS REVIEW:
  
 1} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR.
 PLEASE EXPOUND ON ADDED ELECTRICAL WORK AND INDICATE
 COMPLIANCE WITH CHAPTER 13 FBC.
  THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING
 OR A SEPARATELY METERED OR PERMITTED PORTION OF A
 BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING
 AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE
 SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1.
 THE INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN
 ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED
 THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN
 ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE.*** NONE OF THESE COMMENTS WERE
 RESPONDED TO, SUBMIT WRITTEN RESPONSE TO THE COMMENTS
 MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By dpalmer Date 2008-09-08 Time 10:28 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2008-09-08 10:30:54REVIEW FAILED BY BILL TROBAUGH. NOTES ARE ATTACHED
 PRINTED FROM WORD DOCUMENT.
 NOTES WILL BE ADDED INTO SYSTEM AT A LATER DATE
  
 COMPLIANCE WITH STATING CODES IS ONE COMMENT.
 COMPLIANCE WITH MINIMUM CODE FOR CHAPTER 13 OF THE
 FLORIDA BUILDING CODE IS ALSO NOTED.
 SECTION
 13-415.2.C.1,13-415.2.B.1,13-415.2.ABC.1.1,.1.2.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 16:34 Sent To  
Notes
2008-09-23 16:37:22TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 11:52 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 11:52 Sent To  
Notes
2008-09-11 11:54:35TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-09-08 Time   Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 09:47 Sent To  
Notes
2008-08-25 09:47:46TO BOB # 8.