Plan Review Details - Permit 08080452
Plan Review Stops For Permit 08080452
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-22 Cont ID  
Sent By rmcdouga Date 2008-09-22 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2008-09-22 Time 10:39 Sent To  
Notes
2008-09-22 10:45:37BUILDING PROVISO
  
 SUBMIT A LETTER OR DRAWING FROM THE ARCHITECT/ENGINEER
 THAT SPECIFIES THE ANCHORS THAT WILL BE USED TO ATTACH
 THE GENERATOR TO THE CONCRETE SLAB. SPECIFY THE TYPE,
 SIZE, EMBED DEPTH, AMOUNT AND LOCATION ON THE
 FASTENERS. FBC 1609.1.3
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By rmcdouga Date 2008-09-09 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2008-09-09 Time 11:38 Sent To  
Notes
2008-09-09 11:20:172004 FBC W/2007 REVISIONS
 RESIDENTIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING. GENERATOR SLAB &
 ANCHOR REQUIREMENT PLEASE PROVIDE SIZE OF
 GENERATOR(WXL), PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF FASTENER, AND THE
 MINIMUM EDGE DISTANCE THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION. SPECIFY DIMENSIONS OF CONCETE SLAB,
 REINFORCEMENT, ETC.
  
 2) PLEASE PROVIDE 2 COPIES OF A SITE PLAN. PROVIDE
 PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES
 BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL
 TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
 3. THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 INTO THE BUILDING.
 4. THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5. THE VENT TERMINATION SHALL NOT BE MOUNTED DIRECTLY
 ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY FROM AN
 OIL TANK
 VENT OR GAS METER.
 6. THE BOTTOM OF THE VENT TERMINATION SHALL BE LOCATED
 AT LEAST 12 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
 3. WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4. THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 MM)
 BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 FOR THE BUILDING. 5. A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT SYSTEM.
 6. THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES
 OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE
 CENTERLINE OF THE
 STREET OR PUBLIC WAY. TING THE LOCATION OF THE
 GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE
 NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE
 GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS.
 ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL
 ISSUES.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 4) SPECIFY WIND DESIGN DATA ON THE SLAB AND ANCHORING
 PLANS 1603.1.4 WIND DESIGN DATA. BASIC WIND SPEED
 (3-SECOND GUST), MILES PER HOUR (KM/HR).
  
 5) THE EQUIPMENT IS LOCATED IN AN A5 FLOOD ZONE AN
 ELEVATION OF 7' 6" TO THE TOP OF THE GENERATOR SLAB IS
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By btrobaug Date 2008-10-07 Time 16:53 Rev Time 0.00
Received By btrobaug Date 2008-10-07 Time 16:52 Sent To PC
Notes
2008-10-07 16:53:50 
  
 REVISION TO INCREASE THE GENERATOR SISE TO 48KW FROM
 35KW./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By btrobaug Date 2008-09-17 Time 09:42 Rev Time 0.00
Received By btrobaug Date 2008-09-16 Time 16:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By btrobaug Date 2008-09-05 Time 12:53 Rev Time 0.00
Received By btrobaug Date 2008-09-05 Time 12:21 Sent To G
Notes
2008-09-05 12:53:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2}702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY SYSTEM
 SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE SUPPLY
 OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME.
 THE LOAD CALCULATION SUBMITTED EXCEEDS THE GENERATOR
 OUTPUT IN THE GENERATOR SPECIFICATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-11-03 Cont ID  
Sent By mperson Date 2008-11-03 Time 14:16 Rev Time 0.30
Received By mperson Date 2008-11-03 Time 14:16 Sent To PC
Notes
2008-11-03 14:25:47REVISION: CHANGE GRILL AND WATER HEATER GAS CONNECTIONS
 TO "FUTURE". *MRPERSON.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By mperson Date 2008-09-17 Time 14:22 Rev Time 0.00
Received By mperson Date 2008-09-17 Time 14:22 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By mperson Date 2008-09-05 Time 14:07 Rev Time 0.00
Received By mperson Date 2008-09-05 Time 14:07 Sent To B
Notes
2008-09-05 14:24:32GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. THE GAS PERMIT CAN NOT BE APPROVED UNTIL THE GEN/RES
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION. GAS RISER MAY NEED TO BE REVISED
 PER ZONING COMMENTS. PER FBC-2004 FUEL GAS SECTION
 401.1 SCOPE.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 15:57 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 15:57 Sent To G
Notes
2008-10-31 15:58:06TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 17:01 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 17:01 Sent To E
Notes
2008-09-30 17:01:37TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 12:28 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 12:28 Sent To Z
Notes
2008-09-11 12:29:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 09:19 Sent To E
Notes
2008-09-02 09:20:13TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-09 Cont ID  
Sent By rmcdouga Date 2008-09-09 Time 11:39 Rev Time 0.00
Received By rmcdouga Date 2008-08-21 Time 17:01 Sent To  
Notes
2008-08-21 17:01:50TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By tgordon Date 2008-09-17 Time 16:11 Rev Time 0.45
Received By tgordon Date 2008-09-17 Time 16:11 Sent To B
Notes
2008-09-17 16:16:21*** PROVISO ***
 1) FLOOD ZONE A-5. THE INSTALLED ELEVATION OF THE
 EQUIPMENT IS REQUIRED TO BE DETERMINED AND CERTIFIED BY
 A QUALIFIED SURVEYOR, ENGINEER, OR ARCHITECT TO MEET AT
 LEAST THE MINIMUM REQUIRED HEIGHT, (BASE FLOOD
 ELEVATION 7 FEET PLUS SIX INCHES), FOR THE SPECIAL
 FLOOD HAZARD AREA IN WHICH IT IS INSTALLED. PER CITY
 ORDINANCE 94-543.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By tgordon Date 2008-09-05 Time 09:18 Rev Time 0.30
Received By tgordon Date 2008-09-05 Time 09:18 Sent To E
Notes
2008-09-05 09:26:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SUBMIT A LARGER SITE PLAN SHOWING THE
 GENERATOR LOCATION AS A BOX WITH AN X IN IT, SHOW
 DISTANCES TO THE BUILDING, BUILDING OPENINGS AND
 COMBUSTIBLE MATERIALS.
  
 NOTICE: PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4 ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS. A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED
 BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT
 TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES
 TO THE ADJACENT PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND
 EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD
 INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-12 Cont ID  
Sent By mcruz Date 2008-09-12 Time 15:33 Rev Time 0.00
Received By mcruz Date 2008-09-12 Time 15:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By mcruz Date 2008-08-29 Time 15:39 Rev Time 0.00
Received By mcruz Date 2008-08-29 Time 15:39 Sent To I
Notes
2008-08-29 15:39:17**ZONING FAILED **
  
 1. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES. AS PER
 SECTION94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO AN REQUIRED
 SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  