Plan Review Details - Permit 08080450
Plan Review Stops For Permit 08080450
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-09 Cont ID  
Sent By jwitmer Date 2009-03-09 Time 15:52 Rev Time 0.77
Received By jwitmer Date 2009-03-09 Time 15:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 13:19 Rev Time 0.77
Received By jwitmer Date 2008-10-20 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By jwitmer Date 2008-09-05 Time 10:41 Rev Time 4.40
Received By jwitmer Date 2008-09-05 Time 10:09 Sent To  
Notes
2008-09-05 10:25:23BUILDING PLAN REVIEW
 PERMIT: 08080450
 ADD: 5205 GREENWOOD AVENUE SUITE# ______
 CONT: HEDRICK BROTHERS CONST
 TEL: (561603-7417
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPTEMBER 5TH, 2008
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) SHEET GV-102 PROJECT DATA IS MISSING PLANS
 SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 2) THE PERMIT APPLICATION DESCIPTION OF WORK INDICATES
 PHASE V, THERE SEEMS TO BE SOME DISCREPENCIES OR
 CLARIFICATION NEEDED AS TO WHERE THIS WORK WILL TAKE
 PLACE. THE PERMIT APPLICATION DOES NOT INDICATE AS TO
 FLOOR OR SUITE NUMBER.
 PHASE III AREA UNDER PERMIT # 07040621 WAS FOR THE 1ST
 FLOOR TENANT & COMMON AREAS. SHEET GV-101
 PHASE IV AREA UNDER PERMIT # 08020236 WAS FOR 2ND FLOOR
 PARTIAL DR. JONES OFFICE
 PHASE V SHOULD SHOW UP AS SUITE # 250 AS SHOWN ON SHEET
 AF-102 UNDER PHASE IV PERMIT# 08020236
 PLEASE MAKE CORRECTIONS
 SHEET AF-102 NOTE# 15 MAKES IT UNCLEAR AS TO WHAT WORK
 IS BEING PERMITED UNDER THIS PERMIT AS WELL AS
 ELEVATIONS THAT ARE ALASO NOT REQUIED FOR AN INTERIOR
 BUILD-OUT.
  
  
  
 3) SHEET AF-406 DETAIL# 3 INDICATES WHAT APPEARS TO BE
 A BREAK ROOM WITH MICROWAVE , DISHWASHER & KITHEN SINK.
 IF THIS AREA IS TO BE USED AS A BREAK AREA THEN
 ACCESSIBLITY ISSUES NEED TO BE ADDRESSED.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 19:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-03 Cont ID  
Sent By dpalmer Date 2009-03-03 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2009-03-03 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 09:23 Sent To  
Notes
2008-10-08 09:24:39REDLINED PLANS FOR 2007 REVISIONS TO THE 2004 FBC ON
 ELECTRICAL COVER SHEET.
  
 REDLINED PLANS AS THIS SPACE IS TO BE USED FOR TRAINING
 ONLY. NO MEDICAL PROCEDURES ARE TO DONE. STILL REQUIRES
 GROUNDIGN PER 517 PART II

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By dpalmer Date 2008-09-03 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2008-09-03 Time 09:16 Sent To  
Notes
2008-09-03 09:16:53 
  
  
  
  
 ** DENIED **
  
  
  
 1) NOTE: PLEASE COORDINATE ALL CIRCUITING. PLEASE BE
 SURE TO LABEL PANELS. SOME CIRCUITING ON PLANS ARE NOT
 ON SCHEDULE(S). FOR EXAMPLE PLEASE SEE LIGHTING.
 PLEASE ALSO INDICATE ALL NEW LIGHTING CIRCUITS. SOME
 CIRCUITS ARE NOTED AS *NEW* ON SCHEDULES HOWEVER THE
 OTHERS ARE NOT.
 408.4
 FBC 106.1.1, 106.3.5.1.2
  
 2) NOTE: PLEASE GO OVER LIGHTING PERFORMANCE
 CALCULATIONS. THERE ARE LEVELS SHOWN WHICH EXCEED TABLE
 WATTAGE ALLOWANCES. FOR EXAMPLE: A JANITOR CLOSET MAY
 NOT HAVE AN ALLOWANCE OF 1.5. PLEASE SEE 13-415.2.B
 THIS IS ONE EXAMPLE HOWEVER THERE ARE OTHERS.
  
 ** PLEASE KNOW IF THIS IS A SIMULATED EMERGENCY OR
 TRIAGE AREAS THIS IS NOT HOSPITAL OCCUPANCY WHERE
 ACTUAL TREATMENTS OR SURGERY WILL TAKE PLACE. HOWEVER
 IF SIMULATED USE AND EQUIPMENT IS BEING USED THERE MAY
 BE AN ALLOWANCE. AS THE SCOPE IS NOT CLEAR AT THIS TIME
 PLEASE CALL TO GO OVER.
  
 3) NOTE: PLEASE PROVIDE NOTES ON PLANS FOR AREAS AND
 WIRING PER NEC 517 PART TWO.
  
 PLEASE PROVIDE DETAIL ON WHAT THESE AREAS MAY BE USED
 FOR.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-03-04 Cont ID  
Sent By mwennerg Date 2009-03-04 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2009-03-04 Time 13:11 Sent To  
Notes
2009-03-04 13:11:37REVISION DATED 1/23/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-22 Cont ID  
Sent By mwennerg Date 2008-10-22 Time 13:37 Rev Time 0.00
Received By mwennerg Date 2008-10-22 Time 13:37 Sent To  
Notes
2008-10-22 13:38:35PLANS WERE PASSED WITH PROVISO AT LAST REVIEW WITH
 COMMENTS.PLANS WERE RED LINED AND STAMPED BY THIS
 WRITER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-09-12 Cont ID  
Sent By mwennerg Date 2008-09-12 Time 12:02 Rev Time 0.00
Received By mwennerg Date 2008-09-12 Time 12:02 Sent To  
Notes
2008-09-12 12:05:40***PROVISO***
  
 1) PLEASE ADD NFPA 13, 2003 TO CODE DATA ON SHEET GV
 101.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) EXTERIOR DOORS SHOWN ON SHEET AF 201 ARE NOT
 IDENTIFIED. IF DOORS LEAD TO AN INTERIOR STAIRWELL OR
 SEPARATE SUITE, IDENTIFICATION OF SUCH SHALL BE
 REQUIRED.
  
 4) PLEASE SEE MECHANICAL COMMENT REGARDING DUCT
 PENETRATIONS.
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THESE AND
 OTHER REVIEW CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 10:33 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 10:33 Sent To  
Notes
2008-10-06 10:37:47TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-12 Cont ID  
Sent By mwennerg Date 2008-09-12 Time 12:08 Rev Time  
Received By mwennerg Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 19:19 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 19:19 Sent To PC
Notes
2009-03-24 19:19:23PAGE MH-102 REVISION 2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-10 Cont ID  
Sent By rregueir Date 2009-03-10 Time 10:53 Rev Time 0.00
Received By rregueir Date 2009-03-10 Time 10:51 Sent To PC
Notes
2009-03-10 10:52:59REVISION #1 PAGES MH-102 AND MM-602

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-28 Cont ID  
Sent By tgordon Date 2008-10-28 Time 09:30 Rev Time 1.30
Received By tgordon Date 2008-10-28 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 14:46 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 11:44 Sent To  
Notes
2008-09-02 14:46:32REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED UNDER THE FOLLOWING CODES:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED, CORRECTIONS
 MADE TO THE PLANS AND RESUBMITTED:
  
 MH-102: BASED ON THE LOCATION OF FIRE RATED WALLS SHOWN
 ON PAGE GV-102, THERE ARE AT LEAST 8 DUCT PENETRATIONS
 OF A 1-HOUR RATED WALL WHICH ARE NOT SHOWN ON PLANS TO
 BE PROTECTED AS REQUIRED IN ACCORDANCE WITH FBCM 607.5.
 SHOW TYPE AND LOCATION OF PROTECTION AT EACH DUCT
 PENETRATION OF A FIRE RATED ASSEMBLY IN ACCORDANCE WITH
 THIS SECTION AND FBCM 607.8.
 NOTE: ONE SET OF SUBMITTED PLANS IS MARKED-UP FOR
 REFERENCE TO SHOW THESE LOCATIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 08:50 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 08:50 Sent To  
Notes
2009-03-04 08:51:18REVISIONS OK -- SHTS PL-101, PL-102, PP-801, PP-802 &
 (NEW SHEET PP-803).

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-08-26 Cont ID  
Sent By kstevens Date 2008-08-26 Time 10:16 Rev Time 0.00
Received By kstevens Date 2008-08-26 Time 10:16 Sent To  
Notes
2008-08-26 10:16:59PASSED/PROVISO--WATER HAMMER ARRESTOR SHALL BE
 LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH
 201

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-02 Cont ID  
Sent By lfranco Date 2008-09-02 Time 18:13 Rev Time 0.00
Received By lfranco Date 2008-09-02 Time 18:13 Sent To  
Notes
***NONE***