Plan Review Details - Permit 08080403
Plan Review Stops For Permit 08080403 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-06-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-06-18 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-06-18 |
Time |
14:23 |
Sent To |
|
|
Notes |
2009-06-18 14:51:10 | *****REVISIONS #2 AND #3, APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED; REVISED PLAN SHEETS FA0.1, FA1.0, AND | | FA2.0 WERE STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-12-30 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-12-30 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-12-30 |
Time |
13:37 |
Sent To |
E |
|
Notes |
2008-12-30 15:16:22 | *****UNSAT***** | | | | | | 1. THE TITLE BLOCK INFORMATION LISTED ON THE SUBMITTED | | REVISED SHEETS DOES NOT CORRESPONDS WITH THAT OF THE | | ORIGINALLY APPROVED PLAN SHEETS. FOR EXAMPLE: A) | | REVISED SHEET FA 0.1 WHICH IS THE FIRE ALARM DETAIL | | PLAN READS FIRE ALARM 2ND FLOOR PLAN, B) THE FIRE ALARM | | 2ND FLOOR PLAN SHOULD BE LISTED AS FA 2.0 NOT AS THE | | SECOND (OF 2) FA 1.0 SHEET. | | | | 2. AS PER THIS LOCAL JURISDICTION, DUCT SMOKE DETECTORS | | SHALL INITIATE A GENERAL FIRE ALARM. ON SHEET FA 0.1, | | AMEND FIRE ALARM SYSTEM INPUT #10 TO REFLECT THIS | | REQUIREMENT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-05 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-05 |
Time |
15:05 |
Sent To |
|
|
Notes |
2008-09-05 15:07:52 | PLANS STAMPED UL CERTIFICATED FOR CENTRAL STATION | | SERVICE AND FIRE ALARM TO BE CLASS A OR FULLY | | ADDRESSABLE. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-06-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-06-16 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-06-12 |
Time |
15:19 |
Sent To |
|
|
Notes |
2009-06-16 15:19:56 | PUT IN FIRE BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-12-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-22 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-22 |
Time |
16:37 |
Sent To |
FIRE |
|
Notes |
2008-12-22 16:37:34 | TO "F" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-09-05 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-05 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-08-21 |
Time |
09:53 |
Sent To |
|
|
Notes |
2008-08-21 09:53:17 | TO "F" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy