Plan Review Details - Permit 08080373
Plan Review Stops For Permit 08080373
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By mjacobs Date 2008-10-21 Time 06:21 Rev Time 0.00
Received By mjacobs Date 2008-10-21 Time 06:21 Sent To P
Notes
2008-10-21 06:21:54ONE BATHROOM TO REMAIN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-22 Cont ID  
Sent By mjacobs Date 2008-09-22 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2008-09-22 Time 14:48 Sent To  
Notes
2008-09-22 15:46:01PROVISOR:ASBESTOS
 FBC 105.9 EACH BUILDING PERMIT FOR DEMOLITION OR
 RENOVATION SHALL CONTAIN AN ASBESTOS NOTIFICATION
 STATEMENT HOLDING THE OWNER OR OPERATOR RESPONSIBLE TO
 COMPLY WITH FLORIDA STATUTES 469.003. THE OWNER OR
 OPERATOR SHALL NOTIFY THE DEPT. OF ENVIRONMENTAL
 PROTECTION WHEN REMOVING ASBESTOS WHEN APPLICABLE, IN
 ACCORDANCE WITH STATE AND FEDERAL LAW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-25 Cont ID  
Sent By mjacobs Date 2008-08-25 Time 13:50 Rev Time 0.00
Received By mjacobs Date 2008-08-25 Time 11:16 Sent To  
Notes
2008-08-25 13:50:30 
 BUILDING PLAN REVIEW
 PERMIT: 08080373
 ADD: 101 N. CLEMATIS ST. #150
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) THE TITLE BLOCK FOR MLA DESIGNS, INC. ON THE
 SUBMITTED SHEET SHALL CONTAIN THE INFORMATION STATED.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS. PLEAS SEE FLORIDA STATUTES 481.219 FOR
 INFORMATION REGARDING ARCHITECTURE AND INTERIOR DESIGN.
 A GENERAL CONTRACTOR CANNOT SIGN HIS NAME ON PLANS
 WHICH CONTAIN A TITLE BLOCK OF A DESIGN FIRM,
  
 2) THE GENERAL NOTES ON THE DRAWING SHEET NEEDS TO BE
 IDENTIFY BY A LETTER OR NUMBER OR SOME KIND OF SYMBOL
 TO IDENTIFY CLEARLY WHAT STATEMENT REFER TO THE DEMOED
 AREA. PROVIDE A WALL LEGEND TO SHOW THE SYMBOL FOR THE
 DEMOED WALLS AND WHICH WALL WILL REMAIN. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-02 Cont ID  
Sent By btrobaug Date 2008-10-02 Time 15:39 Rev Time 0.00
Received By btrobaug Date 2008-10-02 Time 15:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-26 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 07:39 Rev Time 0.00
Received By btrobaug Date 2008-08-26 Time 07:26 Sent To  
Notes
2008-08-26 07:39:18 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION. IF THERE IS NONE IN DEMO AREA
 STATE SAME ON THE APPLICATION AND PLAN.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY. THE DESIGNERS TITLE BLOCK MUST BE
 REMOVED IF THE CONTRACTOR CLAIMS THE EXEMPTION.
  
 3} THE SCOPE OF WORK IS UNCLEAR AS TO THE AREA
 INVOLVED. PROVIDE A LEGEND FOR CLARIFICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By mwennerg Date 2008-10-24 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2008-10-24 Time 15:04 Sent To E
Notes
2008-10-24 15:04:54REVISION DATED 10/1/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-01 Cont ID  
Sent By mwennerg Date 2008-10-01 Time 10:40 Rev Time 0.00
Received By mwennerg Date 2008-10-01 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 09:41 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 09:41 Sent To  
Notes
2008-08-29 09:44:56***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR TITLE BLOCK INFORMATION ON PLANS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) BUILDING FIRE PROTECTION SYSTEMS SHALL NOT BE
 INTERUPTED WITHOUT NOTIFICATION AND APPROVAL OF THIS
 OFFICE.
  
 4) SITE SHALL BE CLEANED DAILY OR MORE FREQUENT IF
 NECESSARY TO PREVENT EXCESSIVE BUILD UP OF DEBRIS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 11:31 Sent To B
Notes
2008-10-17 11:32:31TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 11:00 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 11:00 Sent To  
Notes
2008-09-18 11:00:15TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-03 Cont ID  
Sent By lmartine Date 2008-08-29 Time 14:26 Rev Time 0.00
Received By lmartine Date 2008-08-15 Time 16:06 Sent To  
Notes
2008-08-20 17:05:46TO "BOB"#14
2008-08-15 16:10:12WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-09-19 Cont ID  
Sent By tgordon Date 2008-09-19 Time 08:43 Rev Time 0.20
Received By tgordon Date 2008-09-19 Time 08:43 Sent To  
Notes
2008-09-19 08:43:57DEMO.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-09-19 Cont ID  
Sent By tgordon Date 2008-08-21 Time 11:36 Rev Time 0.20
Received By tgordon Date 2008-08-21 Time 11:36 Sent To  
Notes
2008-08-21 11:36:38DEMO.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By mperson Date 2008-10-24 Time 14:19 Rev Time 0.30
Received By mperson Date 2008-10-24 Time 14:19 Sent To E
Notes
2008-10-24 14:20:40REVISION #1: ONE BATHROOM TO REMAIN.
  
 ******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF THE PLUMBING DEMO WORK
 PRIOR TO COVERING DEMO WORK WITH FINNISH WALLS,
 CIELINGS, OR POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-19 Cont ID  
Sent By mperson Date 2008-09-19 Time 07:01 Rev Time 0.00
Received By mperson Date 2008-09-19 Time 07:00 Sent To  
Notes
2008-09-19 07:06:55******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF THE PLUMBING DEMO WORK
 PRIOR TO COVERING DEMO WORK WITH FINNISH WALLS,
 CIELINGS, OR POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By mperson Date 2008-08-21 Time 09:33 Rev Time 0.00
Received By mperson Date 2008-08-21 Time 09:33 Sent To  
Notes
2008-08-21 09:52:14PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMITTED PLAN SHEET HAS A TITLE BLOCK WITH MLA
 DESIGNS, INC. ON IT.
  
 INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT SEE
 FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 NOTE: NUMBER (2), (4), (5), AND (6) ARE MISSING FROM
 THE TITLE BLOCK.
  
 2. CLEARLY INDICATE IN "GENERAL NOTES" IF THE EXISTING
 PLUMBING IS TO REMAIN OR BE REMOVED. PER (W.P.B. AS
 AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-29 Cont ID  
Sent By aaponte Date 2008-08-29 Time 13:38 Rev Time 0.00
Received By aaponte Date 2008-08-29 Time 13:38 Sent To  
Notes
***NONE***