Plan Review Details - Permit 08080371
Plan Review Stops For Permit 08080371
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-30 Cont ID  
Sent By mjacobs Date 2008-09-30 Time 07:11 Rev Time 0.00
Received By mjacobs Date 2008-09-30 Time 06:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By mjacobs Date 2008-09-03 Time 16:33 Rev Time 0.00
Received By mjacobs Date 2008-09-03 Time 13:44 Sent To  
Notes
2008-09-03 16:22:57BUILDING PLAN REVIEW
 PERMIT: 08080371
 ADD: 250 S. AUSTRALIAN AVE #600
 CONT: FISHER CONTRACTING CORP.
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-0 MAKES REFERENCE TO THE 2001 CODE. PLANS
 SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE EXISTING
 FLOOR LAYOUT, AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO THE EXISTING FLOOR PLAN. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE. FBC 106.1.1
  
 6) SHEET FP1.1. ANY PENETRATION THROUGH THE FIRE
 PARTITION SHALL MEET THE REQUIREMENTS OF FBC 712.3.1.2.
 PROVIDE THE UL ASSEMBLY DETAIL AND THE UL NUMBER FOR
 ALL PENETRATIONS (FIRE SPRINKLER PIPES) OF THE NEW FIRE
 WALL: SHOW ALL DETAILS ON THE PLANS.
  
 7) SHEET A-1 MAKES REFERENCE TO DETAIL #2 ON THE SHEET,
 HOWEVER, DETAIL #2 REFERS TO THE FINISH SCHEDULE. ON
 THIS SAME SHEET DOOR TYPE ?B? DOES NOT INDICATE THE
 RATING (HOUR) OF THE DOOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-08-27 Cont ID  
Sent By btrobaug Date 2008-08-27 Time 14:39 Rev Time 0.00
Received By btrobaug Date 2008-08-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-29 Cont ID  
Sent By mawillia Date 2008-09-29 Time 15:36 Rev Time 0.00
Received By mawillia Date 2008-09-29 Time 14:33 Sent To  
Notes
2008-09-29 15:15:28*****APPROVED*****
  
  
 PLAN SHEETS A-1, A-4, E1.2, AND FP1.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 10:07 Sent To  
Notes
2008-08-29 10:12:54***PROVISO***
  
 1) PLEASE ILLUSTRATE THE LOCATION OF REQUIRED 2A-10B,C
 RATED FIRE EXTINGUISHERS.
  
 2) IF DUCT SMOKE DETECTORS ARE WITHIN THE SCOPE OF THIS
 WORK, THEY SHALL INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE
 ADD TO APPLICABLE CODE INFORMATION.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 15:06 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 15:06 Sent To  
Notes
2008-09-24 15:10:19TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 16:54 Sent To  
Notes
2008-08-21 08:47:58TO "BOB"#18
2008-08-15 16:55:16WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-26 Cont ID  
Sent By tgordon Date 2008-09-26 Time 08:09 Rev Time 0.30
Received By tgordon Date 2008-09-26 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By tgordon Date 2008-08-21 Time 14:31 Rev Time 0.45
Received By tgordon Date 2008-08-21 Time 14:31 Sent To  
Notes
2008-08-21 14:43:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN A-0 APPLICABLE CODE INFORMATION STATES 'FLORIDA
 STATE CODE 2001' THE PERMIT BEING APPLIED FOR IS UNDER
 THE 2004 FBC WITH 2007 SUPPLEMENTS, PLEASE CORRECT
 PLAN.
  
 2) PLEASE ADD A DETAIL TO THE MECHANICAL PLANS FOR THE
 INSTALLATION OF THE FIRE DAMPERS. PER 2004 FBC/M THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-09-05 Cont ID  
Sent By mflis Date 2008-09-05 Time 08:39 Rev Time 0.00
Received By mflis Date 2008-09-05 Time 08:39 Sent To  
Notes
2008-09-05 08:39:30ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR BUILD-OUT ONLY
  
 MATT FLIS - 822-1445