Plan Review Details - Permit 08080316
Plan Review Stops For Permit 08080316 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2009-04-07 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2009-04-07 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2009-04-07 |
Time |
11:20 |
Sent To |
|
|
Notes |
2009-04-07 11:21:30 | SEE MASTER |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-20 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-20 |
Time |
11:30 |
Sent To |
|
|
Notes |
2008-08-20 11:34:05 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. MANUF. SPECIFICATION SHEETS FOR THE DRYERS DOES NOT | | INDICATE A LISTING FROM AN APPROVED TESTING AGENCY. | | SECTION 301.3. | | | | 2. THE WELDING CERTIFICATIONS SHALL BE SUBMITTED WITH A | | PHOTO IDENTIFICATION OF THE WELDER PER AWS | | CERTIFICATION. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-20 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-14 |
Time |
11:45 |
Sent To |
|
|
Notes |
2008-08-14 11:45:21 | TO "G" BOX |
|
|
|