Plan Review Details - Permit 08080260
Plan Review Stops For Permit 08080260
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-08 Cont ID  
Sent By rmcdouga Date 2008-10-08 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2008-10-08 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By rmcdouga Date 2008-09-09 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2008-09-09 Time 15:55 Sent To  
Notes
2008-09-09 15:55:032004 FBC W/2007 REVISIONS
 COMMERCIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) SPECIFY THE CODE EDITION AND DESIGN PARAMETERS USED
 TO DETERMINE WIND LOADS. SEE 2004 FBC W/2007 REVISIONS
 SECTION 1609 AND ASCE 7-02.
  
 3) SPECIFY WINDSPEED AND EXPOSURE CATEGORY ON THE
 PLANS. MINIMUM OF 140 MPH, 3 SECOND GUST FOR CITY OF
 WEST PALM BEACH. SEE FBC 1609.
  
 4) SPECIFY WIND DESIGN DATA REQUIRED BY FBC 1603.1.4 ON
 THE PLANS.
  
 5) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 FUEL TANK TO THE SLAB AT THE 12- 1" DIAMETER ANCHOR
 HOLES SHOWN ON SHEET SD1. FBC 1609.1.3
  
 6) SPECIFY HOW THE GENERATOR WILL BE ATTACHED TO THE
 FUEL TANK. FBC 1609.1.3
  
 7) EQUIPMENT IS LOCATED IN AN AO FLOOD ZONE. ELEVATION
 OF THE TOP OF THE SLAB IS REQUIRED TO BE VERIFIED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-06 Cont ID  
Sent By btrobaug Date 2008-11-04 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2008-11-04 Time 15:36 Sent To PC
Notes
2008-11-04 16:09:58 
  
 PROVISO
  
 250.32(B)(2) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE
 BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS
 METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH
 BUILDING OR STRUCTURE INVOLVED, AND (3) GROUND-FAULT
 PROTECTION OF EQUIPMENT HAS NOT BEEN INSTALLED ON THE
 SUPPLY SIDE OF THE FEEDER(S), THE GROUNDED CONDUCTOR
 RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE SHALL
 BE CONNECTED TO THE BUILDING OR STRUCTURE DISCONNECTING
 MEANS AND TO THE GROUNDING ELECTRODE(S) AND SHALL BE
 USED FOR GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES,
 OR FRAMES REQUIRED TO BE GROUNDED OR BONDED.---IF THESE
 CONDITIONS ARE NOT MET, AN EQUIPMENT GROUND MUST BE
 INSTALLED WITH THE FEEDERS, AND THE NEUTRAL ISOLATED
 INTHE EXISTING MAIN SWITCHGEAR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-10 Cont ID  
Sent By btrobaug Date 2008-10-10 Time 08:51 Rev Time 0.00
Received By btrobaug Date 2008-10-08 Time 15:55 Sent To  
Notes
2008-10-09 16:55:15 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REPEAT COMMENTS FROM THE PREVIOUS REVIEW***INDICATES
 FURTHER EXPLANATION OF PREVIOUS COMMENT
  
 2} SHEET E2, NOTE #9 DOES NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR PER 250.130(A) FOR GROUNDED SYSTEMS
 THE CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT
 GROUNDING CONDUCTOR TO THE GROUNDED SERVICE CONDUCTOR
 AND THE GROUNDING ELECTRODE CONDUCTOR. THEREFORE AS THE
 EQUIPMENT GROUND ORIGINATES FROM THE FIRST MEANS OF
 DISCONNECT IT MUST BE RUN WITH THE FEEDERS FROM
 "NEXGEAR" SWITCHGEAR. RESPONSE NOTE #11 REGARDING
 COMPLIANCE WITH 250.32(B)(2) IS NOT CORRECT
 "250.32(2)(B) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE
 BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS
 METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH
 BUILDING OR STRUCTURE INVOLVED,".THE CONTINUOUS PATH IS
 THE CONTROL WIRING.SEE SHEET E6 AND E4.***THE NEXGEAR
 IS THE FIRST MEANS OF DISCONNECT SEE 250.24(A)(5). NOT
 ALL CONTROL WIRING WILL GO TO NORMALLY OPEN CONTACTS.
 SEE NOTES ON SHEET *6.
  
 3} SHEET E5 HAS A NOTE ON THE EXISTING SWITCHGEAR THAT
 THE "GROUND BONDING JUMPER" IS TO REMAIN, THIS WOULD
 CREATE A PARALLEL PATH BETWEEN THE EQUIPMENT GROUND AND
 THE NEUTRAL IN VIOLATION OF 250.6. THE NEUTRAL MUST BE
 ISOLATED FROM ALL GROUND CONNECTIONS BEYOND THE FIRST
 MEANS OF DISCONNECT*** SEE 250.24(A)(5). THE NEXGEAR IS
 THE FIRST MEANS OF DISCONNECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By btrobaug Date 2008-09-03 Time 12:46 Rev Time 0.00
Received By btrobaug Date 2008-09-03 Time 08:57 Sent To  
Notes
2008-08-29 16:56:54 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NO REQUIRED EMERGENCY LIGHTING OR OTHER REQUIRED
 SYSTEMS MAY OPERATE FROM THIS GENERATOR POWER. IF SO
 THE REQUIRED EGRESS LIGHTING MUST BE BATTERY BACK UP AS
 THIS GENERATOR DOES NOT MEET THE REQUIREMENTS OF A
 LEGALLY REQUIRED SYSTEM, SEE 701.11 2005 NEC. INDICATE
 HOW THE EGRESS LIGHTING IS POWERED IN EMERGENCY
 OPERATION. IF THERE IS A FIRE PUMP OPERATED FROM THIS
 SYSTEM, THE GENERATOR WOULD HAVE TO BE "LEGALLY
 REQUIRED".
  
 2} SHEET E2, NOTE #9 DOES NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR PER 250.130(A) FOR GROUNDED SYSTEMS
 THE CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT
 GROUNDING CONDUCTOR TO THE GROUNDED SERVICE CONDUCTOR
 AND THE GROUNDING ELECTRODE CONDUCTOR. THEREFORE AS THE
 EQUIPMENT GROUND ORIGINATES FROM THE FIRST MEANS OF
 DISCONNECT IT MUST BE RUN WITH THE FEEDERS FROM
 "NEXGEAR" SWITCHGEAR. RESPONSE NOTE #11 REGARDING
 COMPLIANCE WITH 250.32(B)(2) IS NOT CORRECT
 "250.32(2)(B) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE
 BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS
 METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH
 BUILDING OR STRUCTURE INVOLVED,".THE CONTINUOS PATH IS
 THE CONTROL WIRING.SEE SHEET E6 AND E4.
  
 3} SHEET E5 HAS A NOTE ON THE EXISTING SWITCHGEAR THAT
 THE "GROUND BONDING JUMPER" IS TO REMAIN, THIS WOULLD
 CREATE A PARALLEL PATH BETWEEN THE EQUIPMENT GROUND AND
 THE NEUTRAL IN VIOLATION OF 250.6. THE NEUTRAL MUST BE
 ISOLATED FROOM ALL GROUND CONNECTIONS BEYOND THE FIRST
 MEANS OF DISCONNECT.
  
 4} THERE IS ANOTHER GENERATOR ON SHEET E4 AND E4.1,
 INDICATE THE PURPOSE OF THIS GENERATOR AND IF IT IS A
 LEGALLY REQUIRED UNIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-22 Cont ID  
Sent By mwennerg Date 2008-10-22 Time 13:20 Rev Time 0.00
Received By mwennerg Date 2008-10-22 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-12 Cont ID  
Sent By mwennerg Date 2008-09-12 Time 10:37 Rev Time 0.00
Received By mwennerg Date 2008-09-12 Time 10:37 Sent To  
Notes
2008-09-12 11:13:44***DENIED***
  
 1) ONLY ONE SET OF PLANS CONTAINS APPROVAL SIGNATURE
 FROM DERM.
  
 2) VERIFY DISTANCE FROM EXHAUST TERMINUS TO BUILDING
 OPENINGS.
  
 3) INDICATE WHAT BUILDING LIFE SAFETY /FIRE PROTECTION
 EQUIPMENT WILL BE CONNECTED TO THE GENERATOR.
  
 4) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 POWER AND STANDBY SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2008-10-25 Cont ID  
Sent By rregueir Date 2008-10-25 Time 15:20 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 15:20 Sent To PC
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 13:05 Rev Time 0.00
Received By rregueir Date 2008-08-27 Time 13:03 Sent To  
Notes
2008-08-27 13:05:18WHEN RESUBMITTING PLANS, PLEASE PROVIDE 2 SETS OF DERM
 APPROVED PLANS FOR PERMIT RECORD. ONE IS NEEDED FOR THE
 OFFICE SET AND ONE IS NEEDED FOR THE FIELD SET. FUEL
 STORAGE PORTION OF PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-08-14 Cont ID  
Sent By kstevens Date 2008-08-14 Time 13:36 Rev Time 0.00
Received By kstevens Date 2008-08-14 Time 13:36 Sent To  
Notes
2008-08-14 13:38:11DIESEL ONLY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 08:54 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 08:54 Sent To E
Notes
2008-11-04 08:54:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 09:33 Sent To  
Notes
2008-10-02 09:43:44TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-12 Cont ID  
Sent By mwennerg Date 2008-09-12 Time 11:13 Rev Time 0.00
Received By mwennerg Date 2008-08-12 Time 14:09 Sent To  
Notes
2008-08-12 14:09:52TO "COMM" BD#42

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 13:03 Rev Time 0.00
Received By rregueir Date 2008-08-27 Time 13:02 Sent To  
Notes
2008-08-27 13:03:06SEE FUEL REVIEW COMMENTS

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By kdfreema Date 2008-10-03 Time 15:34 Rev Time 0.00
Received By kdfreema Date 2008-10-03 Time 15:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By kdfreema Date 2008-08-27 Time 09:40 Rev Time 0.00
Received By kdfreema Date 2008-08-27 Time 09:40 Sent To  
Notes
2008-08-27 09:43:31***FAILED***
  
 1. PLANS ARE NOT CONSISTENT. 11X17 SHEETS DO NOT SHOW
 THE SIDEWALK THAT IS SHOWN ON THE LARGE SHEET WITH
 SURVEYED BACKGROUND.
  
 2. THE CURBING AND LANDSCAPING AROUND THE TRANSFORMER
 AND XFER SWITCH IS OK, HOWEVER, THE LANDSCAPING SHOWN
 AROUND THE GENERATOR NEEDS TO BE PROTECTED BY CURBING.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.
  