Plan Review Details - Permit 08080212
Plan Review Stops For Permit 08080212
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-06 Cont ID  
Sent By jgomez Date 2009-07-06 Time 09:51 Rev Time 0.00
Received By jgomez Date 2009-07-06 Time 09:51 Sent To  
Notes
2009-07-06 09:51:47REVISED ENERGY CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-16 Cont ID  
Sent By jgomez Date 2008-10-16 Time 10:37 Rev Time 0.00
Received By jgomez Date 2008-10-16 Time 10:25 Sent To PC
Notes
2008-10-16 10:38:40DRAWINGS SUBMITTED WITH PALM BEACH COUNTY IMPACT FEES
 STAMP AND COPY OF PAID RECEIPT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2008-09-30 Cont ID  
Sent By jgomez Date 2008-09-30 Time 16:27 Rev Time 0.00
Received By jgomez Date 2008-09-30 Time 16:27 Sent To PC
Notes
2008-09-30 16:37:37BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- RESUBMIT THE ENERGY CALCULATIONS.
 A) NEED TO USE REVISED FORM 600A-2004 R.
 B) CEILING FAN CREDIT CAN'T BE TAKEN. CEILING FAN IS ON
 THE LOGGIA WHICH IS A NON/AC AREA.
 C) COMPLETE INFORMATION ON TOP OF FORM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By jgomez Date 2008-08-21 Time 17:00 Rev Time 0.00
Received By jgomez Date 2008-08-20 Time 07:47 Sent To PC
Notes
2008-08-21 17:30:28RESIDENTIAL (R3) ADDITION AND RENOVATION BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTYTO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2.2 FBC 2004.
 NOTE: PLEASE MAKE SURE CORRECT REVISED FORM IS USED
 AND IS FILLED COMPLETELY TO AVOID UNNECESSARY DELAYS.
  
 3-PLANS TO SPECIFY SAFETY GLASS FOR WINDOWS BY
 BREAKFAST AREA AND BY SHOWER AREA AS REQUIRED BY SEC.
 R308.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A)FIXED ARCHED WINDOW. SEE PLANS.
  
 B) WINDOW MULLION. SEEPLANS.
  
 C) SINGLE HUNG WINDOWS. NEED TO PROVIDE PRODUCT
 APPROVAL THAT MEETS ALL THE DESIGN PRESSURES CALCULATED
 FOR WINDOW W2.
  
 D) FLAT ROOF:
 (1) SPECIFYSPECIFIC APPROVED ASSEMBLY TO BE USED.
  
 (2) SPECIFY SPECIFIC BASE SHEET FASTENING OPTION TO
 BE USED.
 (3) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER &CORNER AREAS AS REQ'D BY GENERAL
 LIMITATION #7 ONNOA 07-0111.03.
  
 5- SHEET SP-1:DESIGN CRITERIA CALLS FOR EXPOSURE "C",
 WHILE STRUCTURAL SHEETSS-1 AND S-3 CALL FOR EXPOSURE
 "B". REVISE AS REQUIRED TO MATCH.
  
 6- SHEET A-1:
 A) CRAWL SPACE VENTILATION TO COMPLY WITH THE
 MINIMUM SIZE,LOCATION AND ACCESS REQUIREMENTS OF SEC.
 R408 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS
 REQUIRED.
 NOTE:REVISE EXTERIOR ELEVATIONS TO REFLECT LOCATION
 OF VENTS AS WELL.
  
 B) REVISE UNDER FLOOR VENTILATION NOTES:REFERENCE
 CODE SECTIONSFROM THE FLORIDA RESIDENTIAL CODE, NOT
 FROM THEFBC.
  
 C) REVISE RISER TREAD RATIO TO COMPLY WITH SEC.
 R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 NOTE: REVISE THIS INFORMATION ON STRUCTURAL DRAWINGS
 ALSO.
  
 7- SHEET A-2:
 A) EMERGENCY ROOF DRAIN SCUPPERS TO COMPLY WITH
 SEC. R903.4.1 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY
 HEIGHT FROM THE FINISHED ROOF COVERING.
  
 B) REVISE ROOF DRAINAGE NOTES:REFERENCE CODE
 SECTIONSFROM THE 2004 FLORIDA RESIDENTIAL CODE, NOT
 THE 2004 FBC.
  
 8- SHEET A-4:
 A) TYPICAL WALL SECTION:
 (1) CLARIFY WHYVENTING IS NOT REQUIRED. SPECIFY
 WHICH CODE SECTIONS STATES THAT NO VENTILATION IS
 REQUIRED ON ROOF.ACCORDING TO SEC. R806 OF 2004
 FLORIDA RESIDENTIAL CODECROSS VENTILATION IS
 REQUIRED. SPECIFYIN PLANS/ELEVATIONS SIZE AND
 LOCATION OF CROSS VENTILATION.
  
 (2) SPECIFYHOW PROVIDING PROTECTION TO THE FLOOR
 JOIST AS REQUIRED BY SEC. R319 .1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 (3) REVISE SIZE OF FLOOR JOIST TO MATCH SIZE SHOWN
 ON STRUCTURAL PLANS.
  
 9- SHEET S-2:REVISE NOTES ON TYPICAL WIND PRESSURE
 BOX SHOWN ON THE FLOOR PLAN D.DISTANCE "A" TO BE
 4'-0" MIN. AS REQUIRED BY NOTE A ON FIGURE R301.2(8) OF
 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE:REVISE SAME INFORMATION ON SHEET S-3.
  
 10- OWES $5.02 FOR RADON FEES FOR NEW ADDITION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-29 Cont ID  
Sent By btrobaug Date 2008-09-29 Time 14:24 Rev Time 0.00
Received By btrobaug Date 2008-09-29 Time 13:31 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-18 Cont ID  
Sent By btrobaug Date 2008-08-18 Time 16:36 Rev Time 0.00
Received By btrobaug Date 2008-08-18 Time 15:13 Sent To B
Notes
2008-08-18 15:53:52 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 200 AMP SERVICE IS ADEQUATE HOWEVER THE LOAD
 CALCULATIONS AT 153 AMPS ALL SEEMS TO BE IN THE 100 AMP
 PANEL "B". SEE SHEET E-2. VIOLATION OF ARTICLE 408.30 "
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THE
 MINIMUM FEEDER CAPACITY REQUIRED FOR THE LOAD
 CALCULATED IN ACCORDANCE WITH ARTICLE 220".THE
 CONDUCTORS ARE ALSO TOO SMALL FOR THE LOAD PER 310.16.
  
 2} CIRCUIT 1,3 FOR THE "EXISTING A/C" HAS A 5.8 KW
 LOAD, #8 WIRE ON A 60 AMP OCP. 5800/240=24 AMPS X 1.25%
 (ARTICLE 424.3(B) )=30.2 AMPS.PER 240.6(A) A 35 AMP
 BREAKER WOULD BE THE MAXIMUM PERMITTED.ALSO SEE SHEET
 M-1 INDICATING A NEW 5 KW AIR HANDLER IS TO BE
 INSTALLED.CORRELATE THE SHEETS WITH THE CORRECT
 INFORMATION.
  
 3} CIRCUIT #30, PANEL "B" IS LISTED AS LAUNDRY BUT
 APPEARS TO BE A SMALL APPLIANCE CIRCUIT ON SHEET
 E-1.PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-10-01 Cont ID  
Sent By mperson Date 2008-10-01 Time 10:38 Rev Time 0.00
Received By mperson Date 2008-10-01 Time 10:38 Sent To PC
Notes
2008-10-01 10:44:08****************PROVISO****************
 *INFORMATION ONLY*
 NOTE: PER PHONE CONVERSATION WITH CONTRACTOR PAUL
 NEWMAN THE GAS ISOMETRIC ON SHEET P-1 HAS BEEN REMOVED
 FROM THE PLANS. A SEPERATE GAS PERMIT AND PLANS WILL BE
 APPLIED FOR AT A LATER DATE.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-25 Cont ID  
Sent By mperson Date 2008-09-25 Time 09:09 Rev Time 0.30
Received By mperson Date 2008-09-25 Time 09:09 Sent To E
Notes
2008-09-25 09:34:46GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE KNOW
 THAT THE RESUBMITTED GAS ISOMETRIC HAS A DIFFERENT
 DESIGN FROM THE ORIGINAL REVIEWED. PLEASE KNOW THAT THE
 FOLOWING COMMENTS ARE FOR SHEET P-1 GAS ISOMETRIC.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE RESUBMITTED GAS ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 INDICATING THIS.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE RESUBMITTED GAS ISOMETRIC IS INDICATING A
 TOTAL DISTANCE OF 7'-0", HOWEVER THERE IS NO WAY TO
 VERIFY THE TOTAL DISTANCE WITHOUT COMMENT #1 BEING
 ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 11:31 Sent To B
Notes
2008-10-15 11:31:52TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 09:08 Sent To Z
Notes
2008-09-19 09:09:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-21 Cont ID  
Sent By jgomez Date 2008-08-21 Time 17:00 Rev Time 0.00
Received By jgomez Date 2008-08-08 Time 16:23 Sent To  
Notes
2008-08-08 16:25:03TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-09-24 Cont ID  
Sent By rkussner Date 2008-09-24 Time 14:10 Rev Time 0.00
Received By rkussner Date 2008-09-24 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-30 Cont ID  
Sent By tgordon Date 2008-09-30 Time 08:21 Rev Time 0.30
Received By tgordon Date 2008-09-30 Time 08:21 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 11:27 Rev Time 0.45
Received By tgordon Date 2008-08-14 Time 11:27 Sent To E
Notes
2008-08-14 11:55:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE MECHANICAL PLAN PAGE M-1. PLEASE MAKE THE FLOOR
 PLAN OF THE HOUSE DARKER AS OUR ELECTRONIC SCANNER FOR
 RECORD RETENTION WILL NOT BE ABLE TO RECORD IT, PER
 2004 W.P.B. AMEND. 106.1.3.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2. SHORT FORM 600C-04 MAY BE USED AS THE
 ADDITION IS UNDER 600 SQ. FT., SEE 2004 FBC
 13-600.3.C.
  
 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS FOR THE
 ADDITION, IF SUBMITTED FOR THE WHOLE HOUSE PLEASE
 SEPARATE EXISTING HOUSE FROM ADDITION BY ZONES, ON
 CALCULATIONS ONLY. PER 2004 FBC 13-607.1.ABC.1.
  
 4) THE RETURN AIR MAY NOT BE TAKEN FROM THE KITCHEN,
 PER 2004 FBC/R M1601.6.4.5 (A RETURN AIR DUCT MAY BE
 RAN TO THE DINING ROOM).
  
 5) PLEASE ADD AN EQUIPMENT SCHEDULE TO THE PLAN SHOWING
 THE PERTINENT INFORMATION FOR THE NEW AIR HANDLER, PER
 2004 W.P.B. AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-25 Cont ID  
Sent By mperson Date 2008-09-25 Time 09:07 Rev Time 0.30
Received By mperson Date 2008-09-25 Time 09:07 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By mperson Date 2008-08-14 Time 16:37 Rev Time 0.00
Received By mperson Date 2008-08-13 Time 16:37 Sent To M
Notes
2008-08-13 16:58:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1 SANITARY ISOMETRIC AND PLUMBING FLOOR
 PLAN: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004
 PLUMBING CODE SECTIONS.
  
 A} THE WASHING MACHINE MUST DRAIN DOWN STREAM OF THE
 NEW MATER BATH WET VET. ONLY FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT. PER SECTION 909.1
 WET VENT PERMITTED.
  
 B} CLEARLY INDICATE THE SIZE TO ALL FIXTURE TRAPS
 (WASHING MACHINE MINIMUM 2" AND LAVATORY MINIMUM 1-1/4"
 TRAPS ARE NOT SIZED). PER SECTION 701.1 SCOPE.
  
 C} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER AS BEING A
 TWO-WAY CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN
 AND BUILDING SEWER JUNCTION.
  
 2. SHEET P-1 PLUMBING FLOOR PLAN IS TO LIGHT AND HARD
 TO READ, PLEASE CORRECT. PER (W.P.B. AS AMENDED)
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SHEET P-1 GAS ISOMETRIC: PLEASE KNOW THAT THE
 CORRECT SIZING TABLE IS 402.4(2) NOT 402.4(1) DUE TO
 FLORIDA PUBLIC UTILITIES PROVIDING A 12" WC WITH A .5"
 PRESSURE DROP. PER FBC-2004 FUEL GAS TABLE 402.4(2).
  
 4. PLEASE KNOW THAT ENERGY CALCULATIONS FOR THE NEW
 TANKLESS WATER HEATER AND HOT WATER PIPE INSULATION ARE
 REQUIRED. PER FBC-2004 CHAPTER 13 SECTION 13-612.1.C.1
 ADDITIONS, TABLE 13-612.1.ABC.3.2 MINIMUM PERFORMANCE
 STANDARDS WATER HEATING EQUIPMENT, AND TABLE
 611.1.ABC.1 MINIMUM PIPE INSULATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By mcruz Date 2008-09-24 Time 11:21 Rev Time 0.00
Received By mcruz Date 2008-09-24 Time 11:16 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By mcruz Date 2008-08-12 Time 10:42 Rev Time 0.00
Received By mcruz Date 2008-08-12 Time 10:41 Sent To P
Notes
2008-08-12 10:42:20**ZONING FAILED **
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDRS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT