Plan Review Details - Permit 08080134
Plan Review Stops For Permit 08080134
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-01 Cont ID  
Sent By mjacobs Date 2008-10-01 Time 13:01 Rev Time 0.00
Received By mjacobs Date 2008-10-01 Time 13:01 Sent To PC
Notes
2008-10-01 13:01:37PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By mjacobs Date 2008-09-24 Time 07:26 Rev Time 0.00
Received By mjacobs Date 2008-09-23 Time 12:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-08-22 Cont ID  
Sent By mjacobs Date 2008-08-22 Time 10:12 Rev Time 0.00
Received By mjacobs Date 2008-08-22 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-25 Cont ID  
Sent By btrobaug Date 2008-09-25 Time 09:46 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 09:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 16:31 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 16:00 Sent To  
Notes
2008-08-21 16:25:58 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS RELATE ONLY TO THE AREA WHERE LIGHTING
 CIRCUITS ARE BEING EXTENDED, ADDED OR CHANGED.
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1.THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS.INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE.
  
 2} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
  
  
 SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-29 Cont ID  
Sent By mawillia Date 2008-09-29 Time 14:23 Rev Time 0.00
Received By mawillia Date 2008-09-29 Time 14:17 Sent To B1
Notes
2008-09-29 14:23:41*****APPROVED*****
  
  
 PLAN SHEETS 2 &3 (OF 3) WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-08-18 Cont ID  
Sent By mawillia Date 2008-08-18 Time 13:43 Rev Time 0.00
Received By mawillia Date 2008-08-18 Time 13:03 Sent To  
Notes
2008-08-18 13:46:03*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL OTHER PLAN EXAMINERS HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 09:37 Sent To  
Notes
2008-09-19 09:39:31TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-22 Time   Rev Time 0.00
Received By adarroug Date 2008-08-07 Time 10:58 Sent To  
Notes
2008-08-12 13:32:29TO "BOB"#8
2008-08-07 10:58:50WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-19 Cont ID  
Sent By tgordon Date 2008-09-19 Time 11:46 Rev Time 0.30
Received By tgordon Date 2008-09-19 Time 11:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By tgordon Date 2008-08-13 Time 16:28 Rev Time 0.40
Received By tgordon Date 2008-08-13 Time 16:27 Sent To  
Notes
2008-08-13 16:39:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE STATE ON PLAN PAGE 3 WHAT THE 6" OUTDOOR AIR
 DUCT IS ATTACHED TO AT THE OUT SIDE OF THE BUILDING AND
 THE SIZE. IF A LOUVER PLEASE SUBMIT PRODUCT APPROVAL OR
 AN NOA FOR THE LOUVER, PER FS 553.842(1) AND FAC RULE
 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-23 Cont ID  
Sent By mperson Date 2008-09-23 Time 11:15 Rev Time 0.00
Received By mperson Date 2008-09-23 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-18 Cont ID  
Sent By mperson Date 2008-08-18 Time 10:51 Rev Time 0.00
Received By mperson Date 2008-08-18 Time 10:51 Sent To  
Notes
2008-08-18 11:27:59PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2, FLOOR PLAN: THE CLEAR FLOOR SPACE FOR THE
 S-1 SINK IN THE LOUNGE IS BEING INDICATED WRONG. PER
 FBC-2004 CHAPTER 11, SECTION 11-4.24.5 CLEAR FLOOR
 SPACE SHALL BE 30" X 48" AND CLEAR FLOOR SPACE SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH SINK. PLEASE PROVIDE
 AN ELEVATION DETAIL WITH THE OTHER FOLLOWING
 REQUIREMENTS FOR THE ACCESSIBLE SINK PER FBC- 2004
 CHAPTER 11 SECTIONS.
  
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. SINK CABINETS SHALL BE OPEN FRONT FOR SINK,
 PLEASE REFERENCE COMMENT #1..
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEET 3, SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THE SIZE OF THE FIXTURE DRAINS AND TRAPS FOR
 THE PROPOSED EWC DRINKING FOUNTAIN AND S-1 SINK. PLEASE
 KNOW THAT THE RELOCATED S-1 SINK FIXTURE DRAIN SHALL BE
 2 INCH (2") WITH AN 1-1/2 INCH (1-1/2") TRAP. PER
 FBC-2004 PLUMBING TABLE 906.1 MAXIMUM DISTANCE OF
 FIXTURE TRAPS FROM VENT. PER (W.P.B. AS AMENDED)
 SECTION 106.3.5.1.3 PLUMBING (4)(13).
  
 3. NOTE: A POTABLE WATER ISOMETRIC RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED EWC DRINKING FOUNTAIN AND S-1
 SINK. CLEARLY INDICATE THE PIPE SIZE PER FBC-2004
 PLUMBING SECTION 601.1 SCOPE, A WATER HAMMER ARRESTOR
 FOR THE REF. ICE MAKER PER FBC-2004 PLUMBING SECTION
 604.9 WATER HAMMER, AND CLEARLY INDICATE THAT THERE IS
 AN EXISTING BACKFLOW PREVENTER PER FBC-2004 PLUMBING
 SECTION 608 PROTECTION OF POTABLE WATER SUPPLY. PER
 (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]