Plan Review Details - Permit 08080106
Plan Review Stops For Permit 08080106
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-12 Cont ID  
Sent By jgomez Date 2008-08-12 Time 15:43 Rev Time 0.00
Received By jgomez Date 2008-08-12 Time 15:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-07 Cont ID  
Sent By jgomez Date 2008-08-07 Time 16:56 Rev Time 0.00
Received By jgomez Date 2008-08-07 Time 16:56 Sent To PC
Notes
2008-08-07 17:02:00RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATIONSCHEDULE CALLS FOR 3" EDGE DISTANCE.
 NEED TO REVISE ANCHOR SPACING AS REQUIRED BY MAXIMUM
 ANCHOR SPACING NOTE SHOWN ON SHEET 7 OF 8 OF SHUTTER
 DRAWINGS SUBMITTED.ANCHOR SPACING SHOWN ON SHEET 7 OF
 8IS VALID ONLY FOR 3 1/2" EDGE DISTANCE.
 NOTE: COORDINATE PANEL SPAN ANDEDGE DISTANCE AS
 REQUIRED.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FL. ST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 14:19 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 14:19 Sent To B
Notes
2008-08-12 14:19:50TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-07 Cont ID  
Sent By jgomez Date 2008-08-07 Time 17:02 Rev Time 0.00
Received By jgomez Date 2008-08-07 Time 16:56 Sent To  
Notes
***NONE***