Plan Review Details - Permit 08080012
Plan Review Stops For Permit 08080012
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By mperson Date 2008-08-04 Time 16:16 Rev Time 0.00
Received By mperson Date 2008-08-01 Time 16:16 Sent To I
Notes
2008-08-01 16:57:44GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. NOTE: PERMIT APPLICATION STATES THE FOLLOWING
 "INSTALL GAS PIPING PER APPROVED PLANS". PLEASE KNOW
 THAT THE SUBMITTED PLANS ARE NOT APPROVED FOR THE GAS
 PIPING AND THAT A RESIDENTIAL GENERATOR PERMIT IS
 REQUIRED FOR THE PROPOSED EMERGENCY GENERATOR. PLEASE
 KNOW THAT THIS WAS EXPLAINED IN MISC. PERMIT
 APPLICATION #08060901 FOR THE NEW GENERATOR ENCLOSURE
 BY MYSELF AND OTHER PLAN REVIEWERS. PLEASE KNOW THAT
 THE FOLLOWING IS REQUIRED FOR THE RESIDENTIAL GENERATOR
 APPLICATION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATORS LOCATION.
 NOTE: PLEASE KNOW AS OF THE TIME OF THIS PLAN REVIEW A
 RESIDENTIAL GENERATOR PERMIT APPLICATION HAS NOT BEEN
 SUBMITTED FOR SAID ADDRESS. PLEASE REFERENCE THE PERMIT
 INFORMATION OF SAID ADDRESS INDICATING THIS.
  
 2. INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 NOTE: (4)(5) ARE MISSING FROM THE TITLE BLOCK.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: SUBMITTED PLANS DO NOT HAVE AN ISOMETRIC THAT
 SHOWS ALL CUT SECTIONS OF PIPE WITH CORRESPONDING
 LENGTHS AS REQUIRED.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 NOTE: THE ISOMETRIC NEEDS TO CLEARLY INDICATE THE
 PIPING MATERIAL BEING USED AND ALL PIPE SIZES FOR EACH
 FOR EACH CUT SECTION OF PIPE.
  
 5. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 ON THE GAS ISOMETRIC. PER FBC-2004 FUEL GAS SECTION
 401.1 SCOPE.
  
 6. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLANS ARE INDICATING AN "EXIST NATURAL GAS METER
 & PRESSURE REGULATOR". PLEASE INDICATE THE EXISTING BTU
 LOAD AS WELL AS THE PROPOSED GENERATOR BTU LOAD ON THE
 REQUIRED GAS ISOMETRIC.
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE INDICATE THE EXISTING GAS SYSTEMS LONGEST
 LENGTH (SEE COMMENT #6 INDICATING AN EXISTING GAS
 METER).
  
 8. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) ON THE
 REQUIRED GAS ISOMETRIC. PER FBC-2004 FUEL GAS CODE SEC.
 402.2. NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: TWO COPIES OF MANUFACTURE SHEETS FOR THE
 PROPOSED GENERATOR ARE REQUIRED THAT CLEARLY INDICATE
 THE GENERATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (TESTING LAB EXAMPLES ARE= AGA, CSA, UL).
 PLEASE KNOW THAT THE SUBMITTED SENSUS #143 MP REGULATOR
 MANUFACTURER'S SPECIFICATION SHEETS DO NOT INDICATE A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. PLEASE COMPLY ON THE RESUBMITTAL THAT THE
 MP REGULATOR HAS A LISTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 09:14 Rev Time 0.00
Received By mperson Date 2008-08-01 Time 15:49 Sent To PC
Notes
***NONE***