2008-08-01 16:57:44 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| 1. NOTE: PERMIT APPLICATION STATES THE FOLLOWING |
| "INSTALL GAS PIPING PER APPROVED PLANS". PLEASE KNOW |
| THAT THE SUBMITTED PLANS ARE NOT APPROVED FOR THE GAS |
| PIPING AND THAT A RESIDENTIAL GENERATOR PERMIT IS |
| REQUIRED FOR THE PROPOSED EMERGENCY GENERATOR. PLEASE |
| KNOW THAT THIS WAS EXPLAINED IN MISC. PERMIT |
| APPLICATION #08060901 FOR THE NEW GENERATOR ENCLOSURE |
| BY MYSELF AND OTHER PLAN REVIEWERS. PLEASE KNOW THAT |
| THE FOLLOWING IS REQUIRED FOR THE RESIDENTIAL GENERATOR |
| APPLICATION. |
| |
| ******IMPORTANT INFORMATION****** |
| AS OF 8/25/06 GENERATOR (GEN/RES AND |
| GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| MATION AND GAS (OR DIESEL) INFORMATION |
| IS ALL SUBMITTED AT THE SAME TIME. THE |
| GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| FORMATION WILL BE ROUTED TOGETHER. THIS |
| WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| THE MANUFACTURER'S SPECI- |
| FICATIONS AND INSTALLATION INSTRUCTIONS) |
| ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| |
| A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| A GEN/RES PERMIT APPLICATION HAS BEEN |
| APPLIED FOR AND APPROVED BY ZONING FOR |
| THE GENERATORS LOCATION. |
| NOTE: PLEASE KNOW AS OF THE TIME OF THIS PLAN REVIEW A |
| RESIDENTIAL GENERATOR PERMIT APPLICATION HAS NOT BEEN |
| SUBMITTED FOR SAID ADDRESS. PLEASE REFERENCE THE PERMIT |
| INFORMATION OF SAID ADDRESS INDICATING THIS. |
| |
| 2. INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT |
| SEE FAC 61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| SEE CITY WPB AMEND. 106.1.1). |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| NOTE: (4)(5) ARE MISSING FROM THE TITLE BLOCK. |
| |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| NOTE: SUBMITTED PLANS DO NOT HAVE AN ISOMETRIC THAT |
| SHOWS ALL CUT SECTIONS OF PIPE WITH CORRESPONDING |
| LENGTHS AS REQUIRED. |
| |
| 4. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| NOTE: THE ISOMETRIC NEEDS TO CLEARLY INDICATE THE |
| PIPING MATERIAL BEING USED AND ALL PIPE SIZES FOR EACH |
| FOR EACH CUT SECTION OF PIPE. |
| |
| 5. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| ON THE GAS ISOMETRIC. PER FBC-2004 FUEL GAS SECTION |
| 401.1 SCOPE. |
| |
| 6. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: PLANS ARE INDICATING AN "EXIST NATURAL GAS METER |
| & PRESSURE REGULATOR". PLEASE INDICATE THE EXISTING BTU |
| LOAD AS WELL AS THE PROPOSED GENERATOR BTU LOAD ON THE |
| REQUIRED GAS ISOMETRIC. |
| |
| 7. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: PLEASE INDICATE THE EXISTING GAS SYSTEMS LONGEST |
| LENGTH (SEE COMMENT #6 INDICATING AN EXISTING GAS |
| METER). |
| |
| 8. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) ON THE |
| REQUIRED GAS ISOMETRIC. PER FBC-2004 FUEL GAS CODE SEC. |
| 402.2. NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: TWO COPIES OF MANUFACTURE SHEETS FOR THE |
| PROPOSED GENERATOR ARE REQUIRED THAT CLEARLY INDICATE |
| THE GENERATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, |
| AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY (TESTING LAB EXAMPLES ARE= AGA, CSA, UL). |
| PLEASE KNOW THAT THE SUBMITTED SENSUS #143 MP REGULATOR |
| MANUFACTURER'S SPECIFICATION SHEETS DO NOT INDICATE A |
| LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY. PLEASE COMPLY ON THE RESUBMITTAL THAT THE |
| MP REGULATOR HAS A LISTING. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |