2008-08-28 08:54:18 | |
| **DENIED** |
| |
| |
| |
| 1) NOTE: SCOPE OF WORK ON PERMIT APPLICATION CLEARLY |
| STATES TO * INSTALL AND UPGRADE OF FIRE ALARM SYSTEM. |
| HOWEVER BASED ON THE PLANS SUBMITTED THE PLANS ARE |
| INCOMPLETE SHOWING MINIMUM CODE COMPLIANCE. |
| PLANS DO NOT INDICATE ANY HEIGHTS OF DEVICES.NFPA-72, |
| FBC CHAPTER 9 |
| PLANS DO NOT INDICATE ANY SCALE WHICH IS REQUIRED. FBC |
| 106.1.3 ADMINISTRATIVE SECTION |
| PLANS DO NOT INDICATE ANY MINIMUM LEVELS FOR DEVICES |
| MEETING FBC FOR ADA. 11-4.28.1,.2 AND .3. |
| PLANS DO NOT INDICATE DIMENSIONS, OR SUFFICIENT |
| INFORMATION AND CLARITY TO DO A REVIEW FOR MINIMUM CODE |
| COMPLIANCE. FBC 106.1.1,106.1.2 FOR ADDITIONAL |
| INFORMATION |
| PLANS DO NOT INDICATE ANY DEDICATED CIRCUIT AS REQUIRED |
| FOR FIRE ALARM PANEL PER NFPA-72 4.4.1.4.1 DEDICATED |
| BRANCH CIRCUIT. A DEDICATED BRANCH CIRCUIT OF ONE OF |
| THE FOLLOWING SHALL SUPPLY PRIMARY POWER: |
| (1)COMMERCIAL LIGHT AND POWER. |
| (2)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT IN |
| ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON SPECIFICALLY |
| TRAINED IN ITS OPERATION IS ON DUTY AT ALL TIMES. |
| (3)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT |
| ARRANGED FOR COGENERATION WITH COMMERCIAL LIGHT AND |
| POWER IN ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON |
| SPECIFICALLY TRAINED IN ITS OPERATION IS ON DUTY AT ALL |
| TIMES. |
| PLANS DO NOT INDICATE ANY CODES IN WHICH ANY DESIGN WAS |
| ATTEMPTED. |
| |
| 2) NOTE: PLANS ARE SIGNED, DATED AND SEALED BY AN |
| ENGINEER AS STATED ON THE TITLE BLOCK AS BEING CIVIL, |
| STRUCTURAL AND ARCHITECTURAL. PLEASE SEE THE FOLLOWING |
| SECTION WHICH HAS BEEN TAKEN DIRECTLY FROM THE FLORIDA |
| STATUTES 471.025 (3) |
| (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED |
| HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY |
| PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR |
| OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT |
| LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER |
| PROFESSION OR SPECIALTY THEREIN. |
| 3) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002 WHICH REQUIRES THE PRINTED NAME AND |
| PRINTED LICENSE NUMBEROF THE ENGINEER TO BE ON THE |
| TITLE BLOCKS. |
| |
| 4) NOTE: PLEASE KNOW BASED ON THE COMMENTS ABOVE THE |
| PLANS AND COPY OF PERMIT APPLICATION IS BEING RETAINED |
| BY THIS OFFICE. |
| |
| 5) NOTE: PLEASE KNOW AS THE APPLIED SCOPE OF WORK AND |
| WORK ON PLANS IS NOT CLEAR THE APPLIED PERMIT VALUE CAN |
| NOT BE VERIFIED PER FBC 108.3 |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |