Plan Review Details - Permit 08070866
Plan Review Stops For Permit 08070866
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 11:39 Sent To FIRE
Notes
2008-11-10 11:40:06ROUTED TO FIRE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 09:20 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 09:20 Sent To FIRE
Notes
2008-10-10 09:20:46 
 ** DENIED 3RD REVIEW**
  
 SCOPE OF WORK ON PLANS HAS NOW ONCE AGAIN BEEN REVISED
 CREATING NEW COMMENTS. THE PLANS/PACKAGE ALSO STILL
 CONTAINS COMMENTS FROM PREVIOUS REVIEW WHICH HAVE STILL
 NOT BEEN ADDRESSED. SEE THE FOLLOWING NOTES.
  
 1) NOTE: SCOPE OF WORK IS CONFUSING ONCE AGAIN. PERMIT
 APPLICATION AND NOTE ON PLANS MENTIONS TO ADD DEVICES
 FOR ELEVATOR RE-CALL ONLY YET THIS DOES NOT
 COORDINATION WITH OTHER NOTES ON PLANS AND DOCUMENTS IN
 PACKAGE. THE PACKAGE OF DOCUMENTS ONCE AGAIN SUBMITTED
 SHOWS A NEW FIRE ALARM PANEL. HOWEVER THE PLANS AND
 APPLICATION HAS BEEN REVISED STATING RECALL ONLY TO
 EXISTING FIRE ALARM PANEL. WHAT SCOPE OF WORK IS BEING
 DONE???
 THE PLANS SHOW OTHER DEVICES ON THE SYMBOL LEGEND SUCH
 AS RELAYS BEING ADDED TO EXISTING PULL STATIONS HOWEVER
 THESE SYMBOLS WHICH WERE ON PREVIOUS PLANS HAVE NOW
 BEEN REMOVED. IN FACT MOST OF THE ITEMS SHOWN ON
 PREVIOUS PLANS HAVE BEEN REMOVED. THESE P/R SYMBOLS ARE
 SHOWN ON RISER HOWEVER NOT ON PLANS.
  
  
 2) NOTE: PLANS ARE NOW SIGNED, DATED AND SEALED BY A
 NEW DESIGN PROFESSIONAL.
  
 3) NOTE: PACKAGE OF DOCUMENTS ETC WILL BE KEPT SO THAT
 A MEETING BETWEEN THE CONTRACTOR AND THE CITY CAN BE
 HAD BEFORE PICKING UP PLANS.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By dpalmer Date 2008-09-23 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2008-09-23 Time 08:55 Sent To FIRE
Notes
2008-09-23 08:56:04 
 ** DENIED 2 REVIEW **
  
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION. THE SCOPE OF
 WORK WAS REVISED HOWEVER AS PER CONVERSATION MR.
 CEPILETTO THE FIRE ALARM PANEL WAS ALSO BEING CHANGED
 OUT AS THE EXISTING PANEL WOULD NOT SUPPORT THE NEW
 SYSTEM. THE SUBMITTED PACKAGE STILL CONTAINS DOCUMENTS
 FOR NEW FIRE ALARM PANEL. PLEASE COORDINATE ALL PLANS,
 DOCUMENTS, PERMIT APPLICATION FOR COMPLETE SCOPE OF
 WORK. 106.1
  
 2) NOTE: PLEASE SEE THE SUBMITTED PLANS AS THE PLANS
 CONTAIN CHANGES MADE AND PHOTO-COPIES OF THE PREVIOUSLY
 DATED, SIGNED AND SEALED PLANS. IT IS A VIOLATION OF
 FLORIDA STATUTES 471.025 TO MAKE CHANGES TO PLANS WHICH
 ARE SIGNED AND SEALED BY ENGINEER AND MAKE PHOTO-COPIES
 OF HIS/HER WORK AND USE FOR ANY PURPOSE.
 THREE SETS OF PLANS WERE SUBMITTED AND ALL THREE SETS
 ARE PHOTO-COPIES OF THE ORIGINAL SIGNED AND SEALED
 PLANS WITH CHANGES MADE OVER PLANS.
 ** TWO SETS WILL BE RETAINED BY THIS OFFICE AND PLACED
 WITH PREVIOUS PLANS RETAINED.
 FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE THE CANDELA RATING AS NOTED ON
 PLANS DOES NOT THE MINIMUM LEVEL FOR ADA IN THE FBC
 11-4.28.3(4).
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 5) NOTE: THE PLANS DO NOT CONTAIN ANY MINIMUM DESIGN
 CODES. FOR EXAMPLE: THE FLORIDA BUILDING CODE, NFPA-72
 2002, NFPA-70 2005. WHAT CODES IS THIS SYSTEM DEISGNED
 UNDER? FLORIDA STATUTES 553.73 LATEST ADOPTED MINIMUM
 CODES ARE LISTED IN THE 2007 REVISIONS TO THE 2004 FBC.
 PLEASE BE SURE TO SUBMIT THE PLANS WIHT REFERENCE TO
 MINIMUM CODES AND DEISGNS.
  
 6) NOTE: PLEASE SEE FBC FOR PULL STATIONS MINIMUM
 DEVICE HEIGHTS. (PULL STATIONS) PLANS NOW SHOW FOR THE
 FIRST TIME DEVICE HEIGHTS. PLEASE SEE FBC CHAPTER 11
 FOR ADA COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 08:54 Sent To PC
Notes
2008-08-28 08:54:18 
 **DENIED**
  
  
  
 1) NOTE: SCOPE OF WORK ON PERMIT APPLICATION CLEARLY
 STATES TO * INSTALL AND UPGRADE OF FIRE ALARM SYSTEM.
 HOWEVER BASED ON THE PLANS SUBMITTED THE PLANS ARE
 INCOMPLETE SHOWING MINIMUM CODE COMPLIANCE.
 PLANS DO NOT INDICATE ANY HEIGHTS OF DEVICES.NFPA-72,
 FBC CHAPTER 9
 PLANS DO NOT INDICATE ANY SCALE WHICH IS REQUIRED. FBC
 106.1.3 ADMINISTRATIVE SECTION
 PLANS DO NOT INDICATE ANY MINIMUM LEVELS FOR DEVICES
 MEETING FBC FOR ADA. 11-4.28.1,.2 AND .3.
 PLANS DO NOT INDICATE DIMENSIONS, OR SUFFICIENT
 INFORMATION AND CLARITY TO DO A REVIEW FOR MINIMUM CODE
 COMPLIANCE. FBC 106.1.1,106.1.2 FOR ADDITIONAL
 INFORMATION
 PLANS DO NOT INDICATE ANY DEDICATED CIRCUIT AS REQUIRED
 FOR FIRE ALARM PANEL PER NFPA-72 4.4.1.4.1 DEDICATED
 BRANCH CIRCUIT. A DEDICATED BRANCH CIRCUIT OF ONE OF
 THE FOLLOWING SHALL SUPPLY PRIMARY POWER:
 (1)COMMERCIAL LIGHT AND POWER.
 (2)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT IN
 ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON SPECIFICALLY
 TRAINED IN ITS OPERATION IS ON DUTY AT ALL TIMES.
 (3)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT
 ARRANGED FOR COGENERATION WITH COMMERCIAL LIGHT AND
 POWER IN ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON
 SPECIFICALLY TRAINED IN ITS OPERATION IS ON DUTY AT ALL
 TIMES.
 PLANS DO NOT INDICATE ANY CODES IN WHICH ANY DESIGN WAS
 ATTEMPTED.
  
 2) NOTE: PLANS ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER AS STATED ON THE TITLE BLOCK AS BEING CIVIL,
 STRUCTURAL AND ARCHITECTURAL. PLEASE SEE THE FOLLOWING
 SECTION WHICH HAS BEEN TAKEN DIRECTLY FROM THE FLORIDA
 STATUTES 471.025 (3)
 (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED
 HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR
 OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
 3) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 WHICH REQUIRES THE PRINTED NAME AND
 PRINTED LICENSE NUMBEROF THE ENGINEER TO BE ON THE
 TITLE BLOCKS.
  
 4) NOTE: PLEASE KNOW BASED ON THE COMMENTS ABOVE THE
 PLANS AND COPY OF PERMIT APPLICATION IS BEING RETAINED
 BY THIS OFFICE.
  
 5) NOTE: PLEASE KNOW AS THE APPLIED SCOPE OF WORK AND
 WORK ON PLANS IS NOT CLEAR THE APPLIED PERMIT VALUE CAN
 NOT BE VERIFIED PER FBC 108.3
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-11-10 Cont ID  
Sent By mwennerg Date 2008-11-10 Time 12:47 Rev Time 0.00
Received By mwennerg Date 2008-11-10 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-20 Cont ID  
Sent By mawillia Date 2008-10-20 Time 14:40 Rev Time 0.00
Received By mawillia Date 2008-10-20 Time 14:18 Sent To  
Notes
2008-10-20 14:38:01*****PROVISO*****
  
  
 THE PLAN SHEET IS TO BE FIRE-STAMPED WHEN ALL OTHER
 REVIEW COMMENTS HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-24 Cont ID  
Sent By mwennerg Date 2008-09-24 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2008-09-24 Time 15:03 Sent To  
Notes
2008-09-24 15:16:27***DENIED***
  
 SOME OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE
 THE FOLLOWING:
  
 1) THERE STILL EXISTS SOME UNCERTAINTY AS TO THE SCOPE
 OF WORK. THE PLANS INDICATE ELEVATOR RECALL ONLY BUT
 OTHER EQUIPMENT IS ILLUSTRATED. PLEASE CLARIFY.
  
 2) WORK SHALL COMPLY WITH NFPA 72. PLEASE ADD NOTE TO
 PLANS.
  
 3) PLANS TO COMPLY WITH REQUIREMENTS OF FBC 106.1.1 AND
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF PROPOSED WORK.
  
 4) OK
  
 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
 PLEASE ADD NOTE TO PLANS.
  
 6) OK
  
 7) PLEASE CLARIFY IF THIS IS A NEW FIRE ALARM SYSTEM AS
 PLANS SEEM TO SUGGEST NEW EQUIPMENT AND FIRE ALARM
 PANEL. AN APPROVED PLAN FOR FIRE RESCUE NOTIFICATION IS
 ACCEPTABLE IN EXISTING INSTALLATIONS. SEC. 9.6.4.3.
 OTHERWISE THE SYSTEM SHALL MEET THE REQUIREMENTS OF
 SEC. 31.3.4 AND SEC. 9.6.
  
 PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING FLORIDA
 STATUTES REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By mwennerg Date 2008-08-13 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2008-08-13 Time 15:32 Sent To  
Notes
2008-08-13 15:54:57***DENIED***
  
 1) MORE INFORMATION REQUIRED FOR COMPLETE FIRE PLAN
 REVIEW. PLEASE INDICATE SCOPE OF WORK.
  
 2) WORK SHALL COMPLY WITH NFPA 72, 2002.
  
 3) PLANS TO COMPLY WITH REQUIREMENTS OF FBC 106.1.1.
 AND SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF PROPOSED WORK.
  
 4) PLEASE INDICATE OCCUPANCY CLASSIFICATION FOR
 BUILDING PER NFPA 101, CHAPTER-6.
  
 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 6) PLEASE INDICATE IF BUILDING IS CURRENTLY PROTECTED
 BY AN AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 7) SINCE THIS IS A NEW INSTALLATION, WILL FIRE ALARM BE
 MONITORED AS THIS IS NOT SHOWN ON PLANS? NFPA 101, SEC.
 31.3.4.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 16:51 Sent To E
Notes
2008-11-07 16:52:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-08 Cont ID  
Sent By adarroug Date 2008-10-08 Time 08:19 Rev Time 0.00
Received By adarroug Date 2008-10-08 Time 08:19 Sent To E
Notes
2008-10-08 08:19:38TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-12 Cont ID  
Sent By adarroug Date 2008-09-12 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-09-12 Time 16:40 Sent To E
Notes
2008-09-12 16:40:52TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING