Plan Review Details - Permit 08070864
Plan Review Stops For Permit 08070864
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-05 Cont ID  
Sent By jgomez Date 2008-08-05 Time 13:44 Rev Time 0.00
Received By jgomez Date 2008-08-05 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By jgomez Date 2008-08-01 Time 16:43 Rev Time 0.00
Received By jgomez Date 2008-08-01 Time 16:42 Sent To PC
Notes
2008-08-01 16:56:50RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2-SHUTTERSPANS LESS THAN 32" ARE NOT ACCEPTABLE.
 SEE NOTE #3 ONSHEET 7 OF DRAWING 05-578SUBMITTED.
 REVISE SIZE OF PANEL SPAN FOR OPENING #7.
  
 3- CLARIFY SIZE OF PANELSSPAN SHOWN ON INSTALLATION
 SCHEDULE.IF THE PANELS WILL BE INSTALLED WITH AN EDGE
 DISTANCE OF 1",THENHOW COMESHUTTERS ARE LIKE 6
 INCHES BIGGER THAN THE OPENING SIZE. REVISE/CLARIFY AS
 REQUIRED.
 NOTE: IN WOOD FRAMEDBUILDINGS THE PANELS NEED TO BE
 ATTACHED TO THE OPENING FRAMING, NOTTO THE PLYWOOD
 SHEATHING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By jgomez Date 2008-08-01 Time 16:56 Rev Time 0.00
Received By jgomez Date 2008-08-01 Time 16:42 Sent To  
Notes
***NONE***