Plan Review Details - Permit 08070857
Plan Review Stops For Permit 08070857
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-02-11 Cont ID  
Sent By mwennerg Date 2009-02-11 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2009-02-11 Time 10:56 Sent To  
Notes
2009-02-11 11:06:23REVISION #3 DATED 1/21/09 AS- BUILTS REFLECTING THE
 CORRECT ROOM NUMBERS ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-25 Cont ID  
Sent By mwennerg Date 2008-11-25 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2008-11-25 Time 11:11 Sent To  
Notes
2008-11-25 11:17:02FIRE ALARM SUBMITTAL OF EQUIPMENT MANUFACTURER
 SPECIFICATION SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-30 Cont ID  
Sent By mwennerg Date 2008-09-30 Time 11:49 Rev Time 0.00
Received By mwennerg Date 2008-09-30 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-15 Cont ID  
Sent By mwennerg Date 2008-08-15 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2008-08-15 Time 10:28 Sent To  
Notes
2008-08-15 10:45:29***DENIED***
  
 1) PLANS SEEM TO SUGGEST SMOKE DETECTORS CONNECTED TO
 THE FIRE ALARM SYSTEM THROUGHOUT THE GUEST SUITES.
 PLEASE NOTE NFPA 101, SEC. 28.3.4.5 REQUIRESAPPROVED
 SINGLE STATION SMOKE ALARMS IN EVERY GUEST ROOM AND
 EVERY LIVING AREA AND SLEEPING ROOM.
  
 2) NFPA 101, SEC. 28.3.4.2 (2) REQUIRES A MANUAL FIRE
 ALARM BOX AT THE HOTEL DESK OR OTHER CENTRAL LOCATION
 UNDER CONTINUOUS SUPERVISION BY RESPONSIBLE EMPLOYEES.
 PLEASE ILLUSTRATE ON PLANS
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE
 ADD NOTE TO PLANS
  
 4) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE PRIOR TO FINAL INSPECTION. PLEASE ADD
 NOTE TO PLANS
  
 5) MORE INFORMATION REQUIRED WITH REGARD TO ELECTRIC
 LOCKS. SPECIAL LOCKING ARRANGEMENTS SHALL COMPLY WITH
 NFPA 101, SEC. 7.2.1.6. ADDITIONALLY, SEPARATE SHOP
 DRAWINGS AND PERMIT IS REQUIRED PRIOR TO INSTALLATION.
 AT TIME OF PERMIT APPLICATION, MANUFACTURER
 SPECIFICATION SHEETS REQUIRED.
  
 6) ALL WORK TO COMPLY WITH NFPA 72, 2002.
  
 7) PLEASE INDICATE TYPE OF DETECTION COVERAGE PER NFPA
 72 AS THERE DOES NOT APPEAR TO BE COVERAGE IN
 ELECTRICAL, MECHANICAL, STORAGE AREAS ETC.
  
 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 9) PLEASE PROVIDE SEQUENCE OF OPERATION TO DRAWINGS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-03 Cont ID  
Sent By adarroug Date 2009-02-03 Time 16:43 Rev Time 0.00
Received By adarroug Date 2009-02-03 Time 16:43 Sent To FIRE
Notes
2009-02-03 16:43:27TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 15:00 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 15:00 Sent To FIRE
Notes
2008-09-05 15:00:32TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-15 Cont ID  
Sent By mwennerg Date 2008-08-15 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2008-07-31 Time 09:38 Sent To  
Notes
2008-07-31 09:38:35TO "F" BOX