Plan Review Details - Permit 08070835
Plan Review Stops For Permit 08070835
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-13 Cont ID  
Sent By jwitmer Date 2009-05-13 Time 13:11 Rev Time 0.77
Received By jwitmer Date 2009-05-13 Time 12:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By jwitmer Date 2008-11-24 Time 12:52 Rev Time 1.66
Received By jwitmer Date 2008-11-24 Time 12:52 Sent To  
Notes
2008-11-24 13:09:46BUILDING PLAN REVIEW
 PERMIT: 08070835
 ADD: 1256 PALM BEACH LAKES BLVD.
 CONT: MASTER CONSTRUCTION
 TEL: (561)248-5498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION. NOC FILED ON 7/22/08 WILL NEED TO BE FILED
 OVER 90 DAY OLD NO WORK.
  
 NOTE!!! THE PERMIT APPLICATION INDICATES THIS PERMIT IS
 TO FINISH WORK STATED UNDER THE EXPIRED PERMIT 05070295
 BUT THE PLANS INDICATE THE TOTAL SCOPE OF THE
 PROJECT.I'VE SPOKE WITH THE BUILDING OFFICIAL NEIL
 MELICK ABOUT THIS PROJECT. NEIL ADVISED EITHER THE
 CONTRACTOR TO PROVIDE A LETTER INDICATING THE SCOPING
 OF WORK TO BE COMPLETED UNDER THIS PERMIT. THE CHIEF
 INSPECTOR KEN CONRAD TO MAKE A JOBSITE VISIT TO CONFIRM
 THE SCOPING INDICATED WITHIN THE LETTER REFLECTS THE
 CORRECT AMOUNT OF WORK LEFT TO COMPLETEE THE PROJECT.
 WE WILL BE REVIEWING THE REMAINDER OF THE PROJECT UNDER
 THE 2004 FLORIDA BUILDING CODE, EXISTING BUILDING CODE.
 LETTER FROM THE CONTRACTOR FOR THE REMAINDER OF WORK TO
 BE COMPLETED UNDER THIS PERMIT IS ATTACHED TO PLAANS
 AND PERMIT APPLICATION.
 AS STATED IN THE CONTRACTORS LETTER SUB-PERMITS WILL
 ALSO NEED TO BE REAPPLIED FOR: ELECTRIC,PLUMBING,
 MECHANICAL, FIRE SPRINKLER, ROOFING, DUMPSTER ENCLOSURE
 AND SIGNAGE.
  
 2) 2ND REQUEST, THE DESIGNER WILL NEED TO UPDATE THE
 PLANS TO READ THE DESIGN NOT TO THE CURRENT CODE BUT TO
 THE 2004 FBC EXISTING BUILDING CODE 301.5 THE DESIGN
 PROFESSIONAL SHALL ELECT TO WHAT LEVEL ALTERATION THEY
 ARE DESIGNING TOO. LEVEL 1, LEVEL 2 OR LEVEL3.
  
 3) 2ND REQUEST, PLANS SUBMITTED DO NOT HAVE ANY ENERGY
 CALCULATIONS SUBMITTED, 2004 FBC EXISTING BUILDING CODE
 SECTION 611.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT
 TO THIS CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By jwitmer Date 2008-08-13 Time 10:31 Rev Time 2.22
Received By jwitmer Date 2008-08-13 Time 10:31 Sent To  
Notes
2008-08-13 10:42:00BUILDING PLAN REVIEW
 PERMIT: 08070835
 ADD: 1256 PALM BEACH LAKES BLVD.
 CONT: MASTER CONSTRUCTION
 TEL: (561)248-5498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 NOTE!!!! THE PERMIT APPLICATION INDICATES THIS PERMIT
 IS TO FINISH WORK STATED UNDER THE EXPIRED PERMIT
 05070295 BUT THE PLANS INDICATE THE TOTAL SCOPE OF THE
 PROJECT.I'VE SPOKE WITH THE BUILDING OFFICIAL NEIL
 MELICK ABOUT THIS PROJECT. NEIL ADVISED EITHER THE
 CONTRACTOR TO PROVIDE A LETTER INDICATING THE SCOPING
 OF WORK TO BE COMPLETED UNDER THIS PERMIT. THE CHIEF
 INSPECTOR KEN CONRAD TO MAKE A JOBSITE VISIT TO CONFIRM
 THE SCOPING INDICATED WITHIN THE LETTER REFLECTS THE
 CORRECT AMOUNT OF WORK LEFT TO COMPLETEE THE PROJECT.
 WE WILL BE REVIEWING THE REMAINDER OF THE PROJECT UNDER
 THE 2004 FLORIDA BUILDING CODE, EXISTING BUILDING CODE.
 LETTER FROM THE CONTRACTOR FOR THE REMAINDER OF WORK TO
 BE COMPLETED UNDER THIS PERMIT IS ATTACHED TO PLAANS
 AND PERMIT APPLICATION.
 AS STATED IN THE CONTRACTORS LETTER SUB-PERMITS WILL
 ALSO NEED TO BE REAPPLIED FOR: ELECTRIC,PLUMBING,
 MECHANICAL, FIRE SPRINKLER, ROOFING, DUMPSTER ENCLOSURE
 AND SIGNAGE.
  
 2) THE DESIGNER WILL NEED TO UPDATE THE PLANS TO READ
 THE DESIGN NOT TO THE CURRENT CODE BUT BE SPECIFIC AS
 TO THE DESIGN CRITERIA. 2004 FBC EXISTING BUILDING CODE
 301.5 THE DESIGN PROFESSIONAL SHALL ELECT TO WHAT LEVEL
 ALTERATION THEY ARE DESIGNING TOO.
  
 3) PLANS SUBMITTED DO NOT HAVE ANY ENERGY CALCULATIONS
 SUBMITTED, 2004 FBC EXISTING BUILDING CODE SECTION
 611.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS
 CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4) THE FIRE AREA OF THIS BUILDING IS OVER 12,000 SQ FT
 REQUIRING FIRE SPRINKLERS, IN 903.2.6(1). THE EXISTING
 BUILDING CODE SECTION 601.2 IN ADDITION TO THE
 REQUIREMENTS TO THEREQUIEMENTS OF THIS CHAPTER, ALL
 WORK SHALL COMPLY WITH CHAPTER 5 OF THE EXISTING
 BUILDING CODE. SECTION 504.1 LEVEL 1 ALTERATIONS SHALL
 NOT BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF
 FIRE PROTECTION PROVIDED. PLEASE SUBMIT PLANS FOR FIRE
 SPRINKLERS TO MEEET THE REQUIREMENTS OF 903.2.6(1) AND
 504.1 EXISTING BUILDING CODE. NOTE SEPERATE PLANS WILL
 ALSO BE REQUIRED FOR THE FIRE SPRINKLER PERMIT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-07 Cont ID  
Sent By dpalmer Date 2009-05-07 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-05-07 Time 14:39 Sent To  
Notes
2009-05-07 14:39:54**PROVISO PLANS**
  
  
  
 1) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULES.
  
 RTU FOR CIRCUITS L20,20,24 ON PANEL, HOWEVER NOT THE
 SAME ON PLANS
 RECEPTACLE IN TENANT SPACE NO CIRCUIT. ( NEXT TO A
 PANEL.)
 EM LIGHT IN TENANT SPACE WHICH SHOULD BE ON L PANEL IS
 SHOWN CIRCUITED TO A-29. MUST BE IN THE SAME TENANT.
 LIGHT FIXTURES IN OFFICES AND BATHROOM SHOW NOW
 CIRCUITS.
 OTHER CIRCUITS SUCH AS THE RECEPTACLES SHALL BE
 SPECIFIC. STATING *RECEPTACLES* IS NOT ACCEPTABLE.
 PLEASE SEE COMMENTARY IN THE 2005 NEC UNDER 408.4. FOR
 EXAMPLE: THE RECEPTACLES ALONG THE REAR WALL WOULD
 STATE JUST THAT; * RECEPTACLES REAR WALL* OR WORDS TO
 THAT SAME AFFECT.
  
 408.4, FBC 106.1.1, 106.3.5
  
 ** ANY AND ALL LOW VOLTAGE SHALL BE UNDER SEPARATE
 PERMITS, FEES AND PLANS.
  
 ** THE PLANS MUST BE UPDATED, SUBMITTED AS A REVISION
 AND ON-SITE BEFORE INSPECTIONS. PLEASE KEEP IN MIND,
 RE-INSPECTION FEES WILL BE ASSESSED PER BUILDING
 OFFICIAL IF PLANS ARE NOT REVISED BEFORE INSPECTIONS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 11:24 Sent To  
Notes
2008-12-01 11:24:43 
 ** FAILED REVIEW
  
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE DONE
 UNDER THE INCORRECT VERSION NOT ADOPTED BY THE FBC.
 PLEASE SEE FBC 13-400.A.3
 PLEASE GO THE ENERGY GAUGE WEBSITE AS IT IS UNDERSTOOD
 BY THIS OFFICE THERE IS A PATCH AVAIL FOR THE CORRECT
 VERSION OF 2.5. IT IS ALSO UNDERSTOOD THAT THERE IS NO
 FEE ASSOCIATED WITH THE PATCH. THIS IS BASED ON
 INFORMATION GIVEN BY NUMEROUS DESIGNERS WHICH HAVE HAD
 TO UPDATE THE VERSION.
  
 2) NOTE: PLEASE SEE THAT METHOD *A* SUBMITTED FOR THE
 OFFICE SPACE IS NOT APPLICABLE.13-101. THE TENANT SPACE
 IS NOT A WHOLE BUILDING.
 PLEASE COORDINATE ALL ELECTRICAL ON PLANS AND OTHER
 COMPONENTS WITH THE SUBMITTED INPUT DATA REPORT.
 PLEASE SEE 13-101.1.6 FOR BUILDINGS WHICH ARE NOT
 COMPLETE. METHODS B OR C ARE THE ONLY CHOICE. NOT *A*.
 PIPING IS NOTED AS BEING INSULATED AS REQUIRED FOR HOT
 WATER HOWEVER THE ELECTRICAL PLANS AS WELL AS THE IDR
 DOES NOT INDICATE ANY INPUT FOR A HOT WATER HEATER?
  
 3) NOTE: PLEASE KNOW THAT HAND DRAWN ITEMS ARE NOT
 PERMITTED ON PLANS SIGNED, DATED AND SEALED. FS
 471.025. THIS IS NOT PERMITTED TO PLANS BY ARCHITECT OR
 ANY OTHER DESIGNER RESPONSIBLE FOR DRAWINGS.
 MANY OF THESE HAVE BEEN HIGH-LIGHTED ON PLANS.
  
 4) NOTE: THE SUBMITTED ENERGY CALCULATIONS MAKE NOTE TO
 LIGHTING CONTROL PANEL/CENTRAL CONTROLS HOWEVER THE
 PLANS DO NOT INDICATE THE LIGHTING CONTROLS AS
 REQUIRED. 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
  
 5) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE PANEL SCHEDULES. ONE EXAMPLE IS THE SIGN CIRCUIT
 WHICH PER 600.5 IS REQUIRED AT THE FRONT ENTRANCE FOR
 EACH SPACE AND IS REQUIRED TO BE ON DEDICATED
 CIRCUIT(S).
 PLEASE SEE ONE TENANT WHICH HAS CIRCUIT A-17 SHOWN AS
 GFI FOR SOME DEVICE.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETE OR ON PLANS FOR REVIEW A COMPLETE REVIEW OF
 SOME COULD NOT BE DONE AT THIS TIME. PLEASE BE SURE TO
 CALL TO GO OVER ANY QUESTIONS.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By dpalmer Date 2008-08-27 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2008-08-27 Time 16:26 Sent To  
Notes
2008-08-27 16:26:50** PLANS WERE ON HOLD. REMOVED FROM HOLD ON 8/26
  
  
 **DENIED**
  
  
  
 1) NOTE: PLEASE SUBMIT PLANS UNDER MINIMUM DESIGN FOR
 THE FOLLOWING CODES.
  
 2004 FBC W/2007 REVISIONS
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 *** PLEASE BE SURE TO SEE COMPLIANCE WITH THE CURRENT
 FLORIDA BUILDING CODE AND ALL OF CHAPTER 13 IS
 REQUIRED.
 PLEASE BE SURE TO COMPLETE PLANS FOR ALL OTHER
 REQUIREMENTS.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2009-04-29 Time   Rev Time 2.00
Received By mgonzale Date 2009-04-29 Time 11:00 Sent To  
Notes
2009-04-29 14:35:10*** PASSED WITH PROVISO ***
  
 DUMPSTER DETAIL DOES NOT SHOW DIMENSIONS.
 DUMPSTER MUST CONFORM TO MIMIMUM CITY WPB STANDARD.
 LATEST DETAIL MAY BE FOUND AT THE LINK BELOW. DETAIL
 GC-9
  
 HTTP://WWW.WPB.ORG/ENGINEERING/STANDARDS/ENGINEERING_ST
 ANDARDS_TABLE_CONTENTS.PDF
  
 NOTE: PLEASE ALSO KNOW THAT ADDITIONAL PERMIT IS
 REQUIRED FOR FIRELINE PIPING ON-SITE. UNDERGROUND
 PERMIT.
 SUCH PIPING WILL BE INSPECTED AND CERTIFIED BY ENGINEER
 OF RECORD.
  
 REVIEWED BY [email protected]
 ENGINEERING SECTION
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By mgonzale Date 2008-11-19 Time 09:26 Rev Time 1.00
Received By mgonzale Date 2008-11-19 Time 09:22 Sent To  
Notes
2008-11-19 09:26:08- FAILED -
  
 PLEASE BE ADVISED THAT YOU MUST GET YOUR FIRELINE PLANS
 APPRPVED BY CWPB ENGINEERING.
 PLEASE MAKE CONTAC WITH:
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR (561) 494-1040
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-15 Cont ID  
Sent By mawillia Date 2009-05-15 Time 15:03 Rev Time 0.00
Received By mawillia Date 2009-05-15 Time 14:15 Sent To  
Notes
2009-05-15 15:11:54*****APPROVED*****
  
  
 AFTER RECEIVING THE REQUESTED ADDITIONAL INFORMATION
 FOR THE SUBMITTED PLAN SETS, SHEETS A2, A3, AND MEP1
 WERE STAMPED, INITIALED, AND DATED ON 5/21/2009.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-12-03 Cont ID  
Sent By mwennerg Date 2008-12-03 Time 15:12 Rev Time 0.00
Received By mwennerg Date 2008-12-03 Time 15:12 Sent To  
Notes
2008-12-03 15:21:23***DENIED***
  
 SOME OF THE COMMENTS FROM THE FIRST REVIEW HAVE BEEN
 ADDRESSED. PLEASE SEE THE FOLLOWING COMMENTS:
  
 1) PROVIDE COMPLETE ADDRESS INCLUDING NUMERICAL ON EACH
 SHEET SUBMITTED.
  
 2) PLANS INDICATE THAT PROJECT WILL BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. IN ADDITION TO THE
 SEPARATE SHOP DRAWINGS AND PERMIT, PLEASE SHOW
 SPRINKLER LAYOUT WITH THIS SUBMITTAL. SPRINKLERS MAY BE
 SHOWN ON REFELECTED CEILING PLAN. COMMENT TAKEN FROM
 FIRST REVIEW.
  
 3) PLANS REFERENCE WORK TO COMPLY WITH NFPA 72, 2002.
 PLEASE CLARIFY IF BUILDING WILL BE PROVIDED WITH FIRE
 ALARM SYSTEM. INFORMATION INCLUDED SHOULD BE LIMITED TO
 WORK THAT IS RELEVANT TO THIS PROJECT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By mwennerg Date 2008-08-28 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2008-08-28 Time 13:48 Sent To P
Notes
2008-08-28 14:03:28***DENIED***
  
 1) SOME SHEETS ARE DIFFICULT TO READ. FBC 106.1.1
 REQUIRES CONSTRUCTION DOCUMENTS TO BE OF SUFFICIENT
 CLARITY TO REVIEW FOR CODE COMPLIANCE AND CONFORMANCE
 WITH RELEVANT LAWS, ORDINANCES RULES AND REGULATIONS.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 5) FIRE SPRINKLER SYSTEMS ARE REQUIRED FOR MERCANTILE
 OCCUPANCIES EXCEEDING 12,000 SQ'. NFPA 101, SEC.
 36.3.5.1 (2). PROVIDE FIRE SPRINKLER LAYOUT AS REQUIRED
 BY FBC. ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED PRIOR TO SYSTEM INSTALLATION.
  
 6) ADDRESS SHALL BE MINIMUM OF 6" IN HEIGHT, 1" WIDTH
 AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL
 BUILDINGS.
  
 7) PROVIDE LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-31 Cont ID  
Sent By btrobaug Date 2009-07-31 Time 15:12 Rev Time 0.00
Received By btrobaug Date 2009-07-31 Time 15:12 Sent To FIRE
Notes
2009-07-31 15:12:50TO FIRE IN BOX
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-31 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 15:11 Rev Time 0.00
Received By btrobaug Date 2009-05-26 Time 10:45 Sent To  
Notes
2009-05-26 10:52:00TO MAGGIE FOR KELLEY./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 16:57 Sent To  
Notes
2009-04-28 17:00:44TO C-2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-10 Cont ID  
Sent By adarroug Date 2008-11-10 Time 08:30 Rev Time 0.00
Received By adarroug Date 2008-11-10 Time 08:29 Sent To  
Notes
2008-11-10 08:33:14TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-28 Cont ID  
Sent By mwennerg Date 2008-08-28 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2008-07-31 Time 08:56 Sent To  
Notes
2008-07-31 09:01:40TO "COMM" BD#62

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-06-08 Cont ID  
Sent By kdfreema Date 2009-06-08 Time 10:31 Rev Time 0.00
Received By kdfreema Date 2009-06-08 Time 10:31 Sent To  
Notes
2009-06-08 10:31:43SEE PLANNING PROVISOS.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-05-13 Cont ID  
Sent By rkussner Date 2009-05-13 Time 10:42 Rev Time 0.00
Received By rkussner Date 2009-05-13 Time 10:42 Sent To  
Notes
2009-05-13 10:43:54***LANDSCAPE REVIEW FAILED***
  
 SEE 5/1/09 ZONING COMMENTS AND PREVIOUS LANDSCAPE
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By rkussner Date 2008-11-18 Time 15:37 Rev Time 0.00
Received By rkussner Date 2008-11-18 Time 15:37 Sent To  
Notes
2008-11-18 15:37:29***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPE PLAN MUST BE SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT.
  
 2. PURSUANT TO SECTION 94-445(4)(A), SHADE AND
 FLOWERING TREES SHALL BE A MINIMUM OF EIGHT FEET IN
 HEIGHT AND POSSESS A MINIMUM OF FIVE FEET OF CLEAR
 TRUNK SPACE. THE CREPE MYRTLE TREES DO NOT MEET THIS
 REQUIREMENT.
  
 3. PURSUANT TO SECTION 94-443(C)(3)A, EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH (EXCLUDING
 THE REQUIRED CURB) AND NOT LESS THAN THE LENGTH OF THE
 ADJACENT PARKING STALL. THE LANDSCAPED ISLAND SHALL
 HAVE A MINIMUM RADIUS OF 21/2 FEET AT ITS END SO AS TO
 ALLOW CAR MANEUVERING. THE LANDSCAPED ISLAND SHALL
 CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE. THE
 PARKING ROW EAST OF THE MAIN ENTRY, ADJACENT TO THE
 HANDICAP PARKING STALL IS MISSING THE REQUIRED
 LANDSCAPE ISLAND AND TREE AT THE WEST END. A TREE IS
 MISSING IN THE TERMINAL LANDSCAPE ISLAND AT THE EAST
 END OF THAT PARKING ROW.
  
 4. THE CAR STOPS SHALL BE ELIMINATED ALONG THE WEST AND
 NORTH PERIMETER OF THE SITE AND REPLACED WITH CURBING.
 THE ASPHALT SHALL BE REMOVED WITHIN THE 2 FOOT OVERHANG
 AREA. THIS WILL ALLOW ADDTIONAL GREEN SPACE FOR THE
 ROOTS OF THE TREES TO DEVELOP. NO TREES OR SHRUBS CAN
 BE PLANTED WITHIN THE 2 FOOT OVERHANG AREA.
  
 5. THE PERIMETER HEDGE ALONG THE WEST PERIMETER OF THE
 SITE SHALL BE PLACED ALONG THE INSIDE PERIMETER OF THE
 LANDSCAPE BUFFER WITH SOD OR GROUND COVER PLANTED ALONG
 THE STREET SIDE OF THE HEDGE. THE HEDGE ALONG THE NORTH
 PERIMETER OF THE SITE SHALL BE PLANTED ALONG THE
 PROPERTY LINE WITH SOD OR GROUND COVER PLANTED ALONG
 THE INSIDE OF THE LANDSCAPE BUFFER.
  
 6. PROVIDE THE TABULATION NECESSARY TO DEMONSTATE
 COMPLIANCE WITH ARTICLE XIV OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS. THE PLAN
 REFERENCED COUNTY REQUIREMENTS WHICH HAS NOTHING TO DO
 WITH CITY REQUIREMENTS.
  
 7. PROVIDE THE TABULATION NECESSARY TO DEMONSTRATE
 COMPLIANCE WITH SECTION 94-442(G) "XERISCAPE
 REQUIREMENT".
  
 8. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. THIS APPLIES
 TO THE AUSTRALIAN AVENUE RIGHT-OF-WAY. ALL LANDSCAPED
 AREAS SHALL BE IRRIGATED, INCLUDING THE RIGHT-OF-WAY
 AREAS.
  
 9. PURSUANT TO SECTION 94-442(B)(1), ALL OPEN SPACE,
 EXCLUDING VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES
 AND SURFACE PARKING, SHALL BE COVERED WITH GRASS,
 GROUND COVER, SHRUBBERY, OR OTHER SUITABLE PLANT
 MATERIAL. THE LANDSCAPE ISLANDS SHALL EITHER BE
 COMPLETELY COVERED WITH GROUND COVER OR SOD. MULCH,
 WITHOUT PLANTING, IS NOT ACCEPTABLE.
  
 10. THE SPECIES OF OAK PROPOSED DOES NOT GROW IN THIS
 ZONE. PLEASE CHANGE THE SPECIES.
  
 11. YOU SHALL COMPLY WITH FPL'S "PLANT THE RIGHT TREE
 IN THE RIGHT PLACE" PROGRAM. PLEASE SHOW ALL OVERHEAD
 POWER LINES. OAK TREES CANNOT BE PLANTED WITHIN 30 FEET
 OF OVERHEAD LINES.
  
 12. ON THE LANDSCAPE PLAN, PLEASE PROVIDE THE LOCATION
 OF ALL SITE LIGHTING, UTILITIES AND ANYTHING ELSE THAT
 MAY INTERFERE WITH THE PROPOSED TREES.
  
 13. PROVIDE THE DUMPSTER LOCATION AND DETAILS OF HOW IT
 WILL BE FULLY SCREENED.
  
 14. PROVIDE THE QUANTITY OF PLANTS IN EACH LOCATION.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @(561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-14 Cont ID  
Sent By rregueir Date 2009-05-14 Time 14:43 Rev Time 0.00
Received By rregueir Date 2009-05-14 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-12 Cont ID  
Sent By tgordon Date 2008-11-12 Time 11:41 Rev Time 1.00
Received By tgordon Date 2008-11-12 Time 11:41 Sent To  
Notes
2008-11-12 11:56:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLAN MEP4 WAS NOT PART OF THE REVISED PLANS. PLEASE
 REVISE PLAN TO INCLUDE AN A/C EQUIPMENT SCHEDULE WITH
 ALL THE PERTINENT INFORMATION ON IT, PER 2004 FBC
 106.3.5.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, PER 2004
 FBC/M 403.2.
  
 3) SUBMIT COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By tgordon Date 2008-08-12 Time 14:42 Rev Time 1.30
Received By tgordon Date 2008-08-12 Time 14:42 Sent To  
Notes
2008-08-12 15:30:54PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE, CITY
 OF WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 *** DENIED ***
 ** WHEN THE MECHANICAL PLAN WAS REVIEW ON APRIL 14,2006
 A PROVISO WAS ATTACHED TO IT, THE REQUIREDMENTS OF THE
 PROVISO WERE NOT MET SO THE PLAN MUST BE REVISED BEFOR
 A NEW PERMIT CAN BE ISSUED.
  
 1) RTU-6 IS NOT SHOWN ON PLAN MEP4 EQUIPMENT SCHEDULE,
 PLEASE CORRECT PER 2001 FBC 104.3.1.1.
  
 2) PLAN MEP-2 SHOW THE SIZE ON THE RETURN AIR DUCT
 (FLEX) TO THE OFFICE (SEE YELLOW HIGH LIGHT ON
 MECHANICAL PLAN). PER 2004 FBC/M 601.4.
  
 3) CORRECTED.
  
 4) PLEASE SHOW ON PLANS, COMPLIANCE WITH 2001 FBC/M
 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 ** ADDITIONAL CORRECTIONS TO BE MADE TO PLAN MEP3.
  
 5) RTU-6 SHOW THE SUPPLY DUCT (FLEX) AND SIZE, GOING TO
 THE SUPPLY AIR GRILL IN THE OFFICE WITH NO DUCT (SEE
 YELLOW HIGH LIGHT ON MECHANICAL PLAN).
  
 6) RTU-6 PLAN SHOWS FLEX GOING FROM THE RETURN PLENUM
 TO A MIXING BOX OR IS THAT A GRILL, PLEASE CLARIFY IF
 IT'S A MIXING BOX OR A GRILL, SHOW THE SIZE OF THE FLEX
 AND IF GRILL SHOW SIZE (SEE YELLOW HIGH LIGHT ON
 MECHANICAL PLAN).
  
 7) RTU-5 SHOW THE SIZE OF THE RETURN AIR GRILL (SEE
 YELLOW HIGH LIGHT ON MECHANICAL PLAN).
  
 8) RTU-5 PLAN MEP3 SHOWS AN ITEM NEAR THE WALL OF THE
 RESTROOMS (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN) IS
 THIS A SUPPLY AIR GRILL OR A WATER FOUNTAIN, PLEASE
 CLARIFY.
  
 9) PLEASE SUBMIT TWO SIGNED AND SEALED COPIES OF
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-05-05 Cont ID  
Sent By kstevens Date 2009-05-05 Time 14:18 Rev Time 0.00
Received By kstevens Date 2009-05-05 Time 14:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-12-03 Cont ID  
Sent By kstevens Date 2008-12-03 Time 16:42 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 16:42 Sent To  
Notes
2008-12-03 16:46:10DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT MEP4 FROM SET OF PLANS APPROVED FOR REISSUE ON
 8-29-08 WERE DELETED FROM THIS SET. PLEASE SUBMIT 2
 COMPLETE SETS OF PLANS FOR REVIEW. SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-08-29 Cont ID  
Sent By kstevens Date 2008-08-07 Time 10:34 Rev Time 0.00
Received By kstevens Date 2008-08-07 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2009-06-08 Cont ID  
Sent By kdfreema Date 2009-06-08 Time 10:29 Rev Time 0.00
Received By kdfreema Date 2009-06-08 Time 10:29 Sent To  
Notes
2009-06-08 10:30:57***PROVISO***
  
 1. THE LAYOUT OF THE HIGHLIGHTED PARKING AREA SHALL
 MATCH THE ATTACHED DIAGRAM.
  
 2. ALL CURBING SHALL BE TYPE D.
  
 3. WHEELSTOPS SHALL BE SINGLE SIDED.
  
 CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 WITH
 QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2009-05-01 Cont ID  
Sent By kdfreema Date 2009-05-01 Time 10:40 Rev Time 0.00
Received By kdfreema Date 2009-05-01 Time 10:40 Sent To  
Notes
2009-05-01 10:46:32***FAILED***
  
 1. THE PARKING LOT LAYOUT IN PK1 AND THE LAYOUT IN L-1
 ARE INCONSISTENT WITH ONE ANOTHER, ESPECIALLY AGAINST
 THE NORTH SIDE OF THE EXISTING STRIP OF SHOPS. THE SITE
 PLAN SHOWS 8 PARKING SPACES AND THE LANDSCAPE PLAN
 SHOWS 11 SPACES. ADJUST THE LANDSCAPE PLAN TO MATCH THE
 DIMENSIONS AND SPACE COUNTS ON THE SITE PLAN.
  
 2. IT IS SUGGESTED THAT GROUPS OF 3 SABAL PALM BE
 INSTALLED IN THE EAST AND WEST ISLANDS ALONG THE
 PARKING ROW MENTIONED ABOVE. THEY WILL PROVIDE BETTER
 VERTICAL ELEMENTS AGAINST THE BUILDING AND TIE IN WITH
 THE SABALS ON THE SIDE FACING AUSTRALIAN AVE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1458 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By kdfreema Date 2008-11-18 Time 14:57 Rev Time 0.00
Received By kdfreema Date 2008-11-18 Time 14:57 Sent To  
Notes
2008-11-18 15:02:20***FAILED***
  
 1. PLEASE SHOW THE LOCATION OF THE DUMPSTER AND
 CODE-COMPLIANT SCREENING IN CONFORMANCE WITH THE ZONING
 CODE.
  
 2. A PARKING LOT STRIPING DETAIL SHALL BE PROVIDED THAT
 CONFORMS TO THE ZONING CODE.
  
 NOTE THAT I HAVE ATTACHED DETAIL SHEETS FOR EACH OF THE
 ABOVE REQUIREMENTS. WHEN YOU RESUBMIT, PLEASE SHOW THE
 DETAILS ON THE PLAN PAGES WHERE APPLICABLE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By kdfreema Date 2008-08-13 Time 15:38 Rev Time 0.00
Received By kdfreema Date 2008-08-13 Time 15:38 Sent To  
Notes
2008-08-13 15:39:28***FAILED***
  
 1. PLEASE CLEARLY INDICATE THE DIMENSIONS OF DRIVE
 AISLES, PARKING SPACES, AND LANDSCAPE ISLANDS.
 REFERENCE SEC. 94-458(J)(2) FOR MINIMUM AISLE AND
 PARKING SPACE DIMENSIONS.
  
 2. A DUMPSTER ENCLOSURE MEETING THE DIMENSIONAL
 REQUIREMENTS OF SEC. 94-444 MUST BE PROVIDED.
  
 3. PLEASE REVIEW THE REQUIREMENTS OF SEC. 94-443(B) FOR
 THE MINIMUM STANDARDS OF THE PERIMETER LANDSCAPE
 BUFFER. IT IS HIGHLY RECOMMENDED THAT THE PROPOSED OAKS
 IN THE NORTH BUFFER BE REPLACED FOR A LOWER GROWING
 SPECIES THAT WILL NOT INTERFERE WITH THE OVERHEAD POWER
 LINES.
  
 4. THE INTERIOR PARKING LOT LANDSCAPING IS REGULATED BY
 SEC. 94-446(C)(3) AND (5). PLEASE REVIEW THE STANDARDS
 AND MAKE CHANGES ACCORDINGLY. NOTE THAT EACH PARKING
 ROW NEEDS TO BE TERMINATED WITH A LANDSCAPE ISLAND NOT
 LESS THAN 5 FEET IN WIDTH. THE TERMINAL ISLANDS MUST
 EXTEND THE FULL LENGTH OF THE ADJACENT PARKING SPACE
 AND CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE. ALL
 NEW LANDSCAPED AREAS MUST BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY EITHER TYPE D CURB OR WHEEL STOPS.
  
 5. PLEASE PROVIDE A LANDSCAPE PLAN MEETING THE
 REQUIREMENTS OF SEC. 94-441 THROUGH SEC. 94-450 AS
 APPLICABLE.
  
 NOTE THAT KELLY FREEMAN, PLANNER, AND ROBERT KUSSNER,
 LANDSCAPE PLANNER, MET WITH THE PROPERTY OWNER AUGUST
 13, 2008, TO DISCUSS SOME POTENTIAL CHANGES TO THE
 PLANS AND SUPPLIED HER WITH A CONCEPTUAL SKETCH TO
 MODIFY THE PARKING LOT LAYOUT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.