Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-05 Cont ID  
Sent By jgomez Date 2008-08-05 Time 15:09 Rev Time 0.00
Received By jgomez Date 2008-08-05 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By jgomez Date 2008-08-04 Time 14:44 Rev Time 0.00
Received By jgomez Date 2008-08-04 Time 14:44 Sent To PC
Notes
2008-08-04 15:36:02RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULE CALLS FOR CONCRETE BLOCK AS
 THE SUBSTRATE. REVISE ANCHOR SPACING AS REQUIRED TO
 REFLECT THE SPACINGSHOWN ON SHEET 4 OF 4OF STORM
 SHUTTERS FOR CONCRETE BLOCK INSTALLATION.
  
 2- REVISE ANCHOR TYPE SPECIFIED FOR OPENING #9.PANEL
 MATE ANCHORS ARE NOT FOR WOOD INSTALLATION. SEE SHEET 4
 OF 4.
  
 3-REVISE SHUTTER SPAN FOR OPENING #9. IT CAN'T BE 39
 X 12.SEE OPENING SIZE.
  
 4-REVISE SHUTTER SPANTO REFLECT OPENING SIZE AND
 EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE.
 ***NOTE: EDGE DISTANCEDOESN'T INCLUDE STUCCO FINISH
 OR ANY OTHER WALL FINISH.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By jgomez Date 2008-07-31 Time 13:51 Rev Time 0.00
Received By jgomez Date 2008-07-31 Time 13:40 Sent To PC
Notes
2008-07-31 14:17:14RESIDENTIAL R(3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-PRODUCT APPROVAL FOR SHUTTERS NOA 02-1120.02
 SUBMITTED IS EXPIRED. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL. ALSO, PLEASE MAKE SURE COMPLETE PRODUCT
 APPROVAL IS SUBMITTED. INFORMATION SUBMITTEDIS
 MISSING THE COVER PAGES OF THIS NOA.
  
 2-INSTALLATION SCHEDULE SUBMITTED:
 A) SPECIFY THE OPENING DESIGN PRESSURES AS REQUIRED
 BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: YOU MAY USE TABLE R301.2(2) FOR REFERENCE. SEE
 ATTACHED COPY.
  
 B) REVISE ANCHOR SPACING AS REQUIRED TO MATCH TYPE
 OF CONNECTION. SEE SHEET 2 OF 4 FOR TYPE OF MOUNTING
 (EG: WALL MOUNT)AND CONNECTION TYPE TO BE USEDAND
 ANCHOR SPACING SCHEDULE ON SHEET 4 OF 4 FOR MAXIMUM
 SPACING. ACCORDING TO THE CONNECTION TYPE.
  
 C) SPECIFY ANCHOR SPACING FOR OPENING #9.ALSO,
 SHUTTER SPAN CAN'T BE THE SAME SIZE AS THE OPENING.
 REVISE AS REQUIRED.ALSO, SPECIFY THE EDGE DISTANCE ON
 THIS INSTALLATION. INFORMATION ON INSTALLATION SCHEDULE
 IS BLANK.
  
 D) REVISE EDGE DISTANCE FOR OPENING #10 AT CONCRETE
 BLOCK INSTALLATION.
  
 E) REVISE SHUTTER SPAN FOR OPENINGS #1 AND #2. TO
 REFLECT THE 2.5" EDGE DISTANCESHOWN ON THE
 INSTALLATION SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-31 Cont ID  
Sent By jgomez Date 2008-07-31 Time 14:32 Rev Time 0.00
Received By jgomez Date 2008-07-31 Time 13:40 Sent To  
Notes
***NONE***