Plan Review Details - Permit 08070827
Plan Review Stops For Permit 08070827
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-06 Cont ID  
Sent By mperson Date 2008-08-06 Time 14:20 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 15:42 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-31 Cont ID  
Sent By mperson Date 2008-07-31 Time 14:05 Rev Time 0.00
Received By mperson Date 2008-07-29 Time 13:45 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-06 Cont ID  
Sent By mperson Date 2008-08-06 Time 14:19 Rev Time 0.00
Received By mperson Date 2008-08-06 Time 14:19 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By mperson Date 2008-07-31 Time 13:45 Rev Time 0.00
Received By mperson Date 2008-07-31 Time 13:45 Sent To I
Notes
2008-07-31 14:04:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE VENT
 HEADER PER FBC-2004 PLUMBING SECTION 903.5 VENT
 HEADERS. STACK VENTS AND VENT STACKS CONNECTED INTO A
 COMMON VENT HEADER AT THE TOP OF THE STACKS AND
 EXTENDING TO THE OPEN AIR AT ONE POINT SHALL BE SIZED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 916.1
 (TABLE 916.1) . THE NUMBER OF FIXTURE UNITS SHALL BE
 THE SUM OF ALL FIXTURE UNITS ON ALL STACKS CONNECTED
 THERETO, AND THE DEVELOPED LENGTH SHALL BE THE LONGEST
 VENT LENGTH FROM THE INTERSECTION AT THE BASE OF THE
 MOST DISTANT STACK TO THE VENT TERMINAL IN THE OPEN
 AIR, AS A DIRECT EXTENSION OF ONE STACK.
 NOTE: CLEARLY INDICATE THE FIXTURES AND FIXTURE UNITS
 FOR EACH STACK ALSO INDICATE THE DEVELOPED LENGTH PER
 SECTION 903.5 AND SIZE PER TABLE 916.1.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]