Plan Review Details - Permit 08070823
Plan Review Stops For Permit 08070823
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-07-30 Cont ID  
Sent By mperson Date 2008-07-30 Time 16:39 Rev Time 0.00
Received By mperson Date 2008-07-30 Time 16:39 Sent To I
Notes
2008-07-30 16:41:43****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-30 Cont ID  
Sent By mperson Date 2008-07-30 Time 16:41 Rev Time 0.00
Received By mperson Date 2008-07-29 Time 16:39 Sent To PC
Notes
***NONE***