Plan Review Details - Permit 08070743
Plan Review Stops For Permit 08070743
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-18 Cont ID  
Sent By jgomez Date 2008-09-18 Time 16:56 Rev Time 0.00
Received By jgomez Date 2008-09-18 Time 16:38 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By jgomez Date 2008-08-12 Time 16:51 Rev Time 0.00
Received By jgomez Date 2008-08-12 Time 16:51 Sent To PC
Notes
2008-08-12 16:54:42RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SINGLE HUNG WINDOWS FOR WINDOW TO BE REPLACED IN
 LIVING ROOM.
 B PRECAST LINTELS.
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
  
 2- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 NOTE: MAY USE THE STANDARD SHOP DRAWINGS APPROVAL STAMP
 OR ANY OTHERWRITING METHOD.
  
 3- PROVIDE NOTICE OF COMMENCEMENT. SEC. 713.13 FLORIDA
 STATUTE.
 ***NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK
 UP.
  
 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE.BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 5- PROVIDE ENERGY CALCULATIONS. SEC. 13-101.2.2FBC
 2004. PLEASE MAKE SURE CORRECT AND UPDATED FORM IS USED
 TO AVOID DELAYS.
  
 6-SPECIFY HOWTHE1X6 T & G SHEATHING ON NEW PORCH
 (DETAIL A/A-3)IS GOING TO BE FASTENED. ROOF SHEATHING
 NAILING SCHEDULE ON SHEET A-3 DOESN'T APPLY TO THIS
 TYPE OF SHEATHING.
  
 7- TYPICAL WALL SECTION ON SHEET A-2:
 A) FOOTING SIZE DOESN'T MATCH SIZE SHOWN ON
 FOUNDATION PLAN. REVISE AS REQUIRED.
 B) SPECIFY FOOTING EMBEDMENTBELOW GRADE TO VERIFY
 COMPLIANCE WITH SEC. R406.1.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 8- OWES $3.28 FOR RADON FEES.
  
 9- SHEET A-3:
 A) WIND INFORMATION: UPDATE NOTE #6.FOR ONE & TWO
 FAMILY RESIDENCES THE CODE TO BE REFERENCED IS THE 2004
 FLORIDA RESIDENTIAL CODE (SEE SEC. R301),NOT CHAPTER
 16 OF FBC. REVISE AS REQUIRED.
 ALSO, UPDATENOTE BELOWNOTE #15. CURRENTREVISIONS
 ARE 2007, NOT 2006.
  
 B) TYPICAL PORCH SECTION: REVISESECTION CITED FOR
 SHINGLES.BUILDING IS REVIEWED UNDER THE 2004 FLORIDA
 RESIDENTIAL CODE, NOT THE 2004 FBC.
  
 10- SURVEY NEEDS TO HAVE SURVEYOR'S ORIGINAL SIGNATURE,
 NOT COPY AS REQUIRED BY SEC. 61G17-7.0025 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER472 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By btrobaug Date 2008-09-24 Time 10:45 Rev Time 0.00
Received By btrobaug Date 2008-09-24 Time 06:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-30 Cont ID  
Sent By btrobaug Date 2008-07-30 Time 07:23 Rev Time 0.00
Received By btrobaug Date 2008-07-30 Time 07:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:16 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:16 Sent To Z
Notes
2008-09-03 16:16:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 09:14 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 09:14 Sent To M
Notes
2008-08-04 09:15:13TO "SFR" "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-12 Cont ID  
Sent By jgomez Date 2008-08-12 Time 16:54 Rev Time 0.00
Received By jgomez Date 2008-07-30 Time 07:02 Sent To  
Notes
2008-07-29 12:21:23"SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-09-08 Cont ID  
Sent By rkussner Date 2008-09-08 Time 14:03 Rev Time 0.00
Received By rkussner Date 2008-09-08 Time 14:03 Sent To  
Notes
2008-09-08 14:10:39***PROVISO***
  
 1. IRRIGATION SYSTEM, APPROVED THROUGH THE BUILDING
 PERMIT PROCESS, SHALL BE INSTALLED PRIOR TO ISSUANCE OF
 C/O FOR THE ADDITION.
  
 2. ALL EXISTING TREES, SHRUBS AND GROUND COVER MUST BE
 FLORIDA #1 GRADE OR BETTER. OTHERWISE, REPLACEMENT MAY
 BE REQUIRED.
  
  
  
 FOR ANY INFORMATION REGARDING THIS PROVISO, CONTACT
 ROBERT KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By rkussner Date 2008-09-08 Time 08:42 Rev Time 0.00
Received By rkussner Date 2008-09-08 Time 08:42 Sent To  
Notes
2008-09-08 10:00:18***LANDSCAPE FAILED***
  
 PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. PLEASE PROVIDE AN
 IRRIGATION PLAN AND SUBMIT APPLICATION.
  
 ALL EXISTING LANDSCAPE MATERIAL TO BE COUNTED TOWARD
 MEETING THE LANDSCAPE CODE, SHALL BE FLORIDA #1 GRADE
 OR BETTER.
  
  
 FOR ANY QUESTIONS REGARDING THESE COMMENTS, PLEASE
 CONTACT ROBERT KUSSNER @ (561) 822-1462.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By tgordon Date 2008-08-04 Time 13:45 Rev Time 0.25
Received By tgordon Date 2008-08-04 Time 13:45 Sent To P
Notes
2008-08-04 13:46:50NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 *** NOTE; A MECHANICAL PERMIT WILL BE REQUIRED FOR THE
 BATHROOM EXHAUST FAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-22 Cont ID  
Sent By mperson Date 2008-09-22 Time 09:12 Rev Time 0.00
Received By mperson Date 2008-09-22 Time 09:12 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By mperson Date 2008-08-05 Time 08:50 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 08:50 Sent To B
Notes
2008-08-05 09:41:24PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 FLOOR PLAN: CLEARLY IDENTIFY ALL PLUMBING
 FIXTURES ON THE FLOOR PLAN. PER FBC-20004 PLUMBING
 SECTION 401.1 SCOPE.
  
 2. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM: THE
 SUBMITTED ISOMETRIC DOES NOT REFLECT THE FLOOR PLAN ON
 SHEET A-1. THE LAVATORIES, TUB, AND SHOWER ARE BEING
 INDICATED IN THE WRONG LOCATIONS. PLEASE PROVIDE A FLAT
 FLOOR PLAN DRAWING OF THE UNDERGROUND SANITARY PLUMBING
 AND CORRELATE THE RESUBMITTED SANITARY PLUMBING
 ISOMETRIC ACCORDINGLY. PER FBC-2004 PLUMBING SECTION
 701.1 SCOPE.
  
 3. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM:
 CLEANOUTS ARE REQUIRED AT THE BASE OF THE LAVATORY
 WASTE STACKS AND CLEARLY INDICATE THE CLEANOUT AT THE
 JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER AS
 BEING A TWO-WAY CLEANOUT. PER FBC-2004 PLUMBING SECTION
 708.3.4 BASE OF STACK AND SECTION 708.3.5 BUILDING
 DRAIN AND BUILDING SEWER JUNCTION.
  
 4. SHEET A-1 FLOOR PLAN AND A-4 ELECTRICAL PLAN ARE
 INDICATING THE FOLLOWING "ADD NEW SHOWER HEAD W/
 CONTROLS". PLEASE CLARIFY IF THIS IS AN OUTSIDE SHOWER.
 IF THIS IS AN OUTSIDE SHOWER WHY IS IT NOT BEING
 INDICATED ON THE ELEVATION DRAWINGS ON SHEET A-1. IF
 THIS IS AN OUTSIDE SHOWER CLEARLY INDICATE WHERE IT IS
 GOING TO DRAIN (SUCH AS A GRASSY AREA). PER FBC-2004
 PLUMBING SECTION 417.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 (SHEET A-4 HAS NO ONE TAKING RESPONSIBILITY FOR IT)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By mcruz Date 2008-09-09 Time 11:01 Rev Time 0.00
Received By mcruz Date 2008-09-09 Time 11:01 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 11:11 Rev Time 0.00
Received By mcruz Date 2008-09-09 Time 11:00 Sent To I
Notes
2008-08-03 11:11:14**ZONING FAILED **
  
 1.PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2.PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDRS.
  
 3.NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION
 MAY GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT