Plan Review Details - Permit 08070718
Plan Review Stops For Permit 08070718
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-08 Cont ID  
Sent By rmcdouga Date 2008-10-08 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2008-10-08 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By rmcdouga Date 2008-08-28 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2008-08-28 Time 10:58 Sent To  
Notes
2008-08-28 11:00:02SEE REVIEW BY JIM WITMER ON PERMIT # 08070721 FOR
 COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-12 Cont ID  
Sent By btrobaug Date 2008-11-12 Time 16:36 Rev Time 0.00
Received By btrobaug Date 2008-11-12 Time 16:15 Sent To FIRE
Notes
2008-11-14 15:37:12 
  
 TOOK OFF BOARD, SENT TO FIRE./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-10 Cont ID  
Sent By btrobaug Date 2008-10-10 Time 10:34 Rev Time 0.00
Received By btrobaug Date 2008-10-10 Time 09:40 Sent To  
Notes
2008-10-10 09:49:31 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REPEAT COMMENTS FROM THE PREVIOUS REVIEW***INDICATES
 FURTHER EXPLANATION OF PREVIOUS COMMENT
  
 1} THE MANUFACTURERS SPECIFICATION FOR THE GENERATOR
 ARE PARTIALLY INDISCERNIBLE, PLEASE SUBMIT READABLE
 COPIES***THE SAME SPEC'S RESUBMITTED.
  
 2} THE RESPONSE TO THE PREVIOUS REVIEW COMMENT #3WAS
 THAT THE OCP IS IN THE GENERATOR CONTROL PANEL, THERE
 IS NO INDICATION OF THAT IN THE SPECIFICATIONS
 SUBMITTED.***CORRECT, THE 3000AMP OCP IS NOTED ON SHEET
 E2.
  
 3} INDICATE IF ANY REQUIRED EMERGENCY LIGHTING OR OTHER
 SYSTMS WILL OPERATE FROM THIS GENERATOR POWER.PROVIDE A
 RISER DIAGRAM INDICATING WHICH PANELS WILL BE FED FROM
 THIS GENERATOR. THE SUBMITTED PLAN SHOWS THE GENERATOR
 FEEDING "MDP."*** NO RESPONSE GIVEN TO THIS COMMENT.
  
 NEW COMMENT GENERATED AS THE DISCONNECTING MEANS IN THE
 NEXGEAR NOW IS THE FIRST MEANS OF DISCONNECT.
  
 4} SHEET E2, NOTE #9 DOES NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR PER 250.130(A) FOR GROUNDED SYSTEMS
 THE CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT
 GROUNDING CONDUCTOR TO THE GROUNDED SERVICE CONDUCTOR
 AND THE GROUNDING ELECTRODE CONDUCTOR. THEREFORE AS THE
 EQUIPMENT GROUND ORIGINATES FROM THE FIRST MEANS OF
 DISCONNECT IT MUST BE RUN WITH THE FEEDERS FROM
 "NEXGEAR" SWITCHGEAR. "250.32(2)(B) GROUNDED CONDUCTOR
 WHERE (1) AN EQUIPMENT GROUNDING CONDUCTOR IS NOT RUN
 WITH THE SUPPLY TO THE BUILDING OR STRUCTURE, (2) THERE
 ARE NO CONTINUOUS METALLIC PATHS BONDED TO THE
 GROUNDING SYSTEM IN EACH BUILDING OR STRUCTURE
 INVOLVED,".THE CONTINUOUS PATH IS THE CONTROL
 WIRING.SEE SHEET E6 AND E4.***THE NEXGEAR IS THE FIRST
 MEANS OF DISCONNECT SEE 250.24(A)(5). NOT ALL CONTROL
 WIRING WILL GO TO NORMALLY OPEN CONTACTS. SEE NOTES ON
 SHEET *6.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 10:56 Rev Time 0.00
Received By btrobaug Date 2008-07-30 Time 16:27 Sent To  
Notes
2008-08-01 16:10:25 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE MANUFACTURERS SPECIFICATION FOR THE GENERATOR
 ARE PARTIALLY INDISCERNIBLE, PLEASE SUBMIT READABLE
 COPIES.
  
 2} THE RESPONSE TO THE PREVIOUS REVIEW COMMENT #3WAS
 THAT THE OCP IS IN THE GENERATOR CONTROL PANEL, THERE
 IS NO INDICATION OF THAT IN THE SPECIFICATIONS
 SUBMITTED.
  
 3} INDICATE IF ANY REQUIRED EMERGENCY LIGHTING OR OTHER
 SYSTMS WILL OPERATE FROM THIS GENERATOR POWER.PROVIDE A
 RISER DIAGRAM INDICATING WHICH PANELS WILL BE FED FROM
 THIS GENERATOR. THE SUBMITTED PLAN SHOWS THE GENERATOR
 FEEDING "MDP."
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-21 Cont ID  
Sent By mwennerg Date 2008-11-21 Time 13:10 Rev Time 0.00
Received By mwennerg Date 2008-11-21 Time 13:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-10-28 Cont ID  
Sent By mwennerg Date 2008-10-28 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2008-10-28 Time 15:07 Sent To  
Notes
2008-10-28 15:08:201) WHAT EQUIPMENT WILL THE GENERATOR SUPPLY WITHIN THE
 STORE?
  
 2) PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3) IN ADDITION TO APPLICABLE BUILDING CODES, WORK SHALL
 COMPLY WITH NFPA 101, 2003, AND NFPA 110, STANDARD FOR
 EMERGENCY POWER AND STANDBY SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2008-08-22 Time 14:09 Sent To Z
Notes
2008-08-22 14:14:52***DENIED***
  
 COMMENTS FROM THE REVIEW OF THE EXPIRED PERMIT WERE
 ADDRESSED, BUT SOME INFORMATION CAN NOT BE FOUND WITH
 THIS SUBMITTAL.
  
 1) WHAT EQUIPMENT WILL THE GENERATOR SUPPLY WITHIN THE
 STORE?
  
 2) PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3) IN ADDITION TO APPLICABLE BUILDING CODES, WORK SHALL
 COMPLY WITH NFPA 101, 2003, AND NFPA 110, STANDARD FOR
 EMERGENCY POWER AND STANDBY SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 15:03 Rev Time 0.10
Received By tgordon Date 2008-07-25 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 09:14 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 09:14 Sent To  
Notes
2008-11-04 09:16:59TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 09:10 Sent To  
Notes
2008-10-02 09:12:00TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2008-07-24 Time 13:58 Sent To  
Notes
2008-08-27 09:35:168-27-08TO "BUILD" ROBERT MCD.
2008-07-24 13:58:26TO "COMM" BD#12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 15:03 Rev Time 0.30
Received By tgordon Date 2008-07-25 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-07-29 Cont ID  
Sent By mperson Date 2008-07-29 Time 15:54 Rev Time 0.00
Received By mperson Date 2008-07-29 Time 15:54 Sent To  
Notes
2008-07-29 15:57:26NOTE: STANBY GENERATOR HAS A FUEL SOURCE OF DIESEL.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-08-27 Cont ID  
Sent By kdfreema Date 2008-08-27 Time 08:52 Rev Time 0.00
Received By kdfreema Date 2008-08-27 Time 08:52 Sent To  
Notes
***NONE***