Plan Review Details - Permit 08070715
Plan Review Stops For Permit 08070715
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-17 Cont ID  
Sent By mjacobs Date 2008-10-17 Time 14:18 Rev Time 0.00
Received By mjacobs Date 2008-10-17 Time 13:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By mjacobs Date 2008-10-03 Time 08:47 Rev Time 0.00
Received By mjacobs Date 2008-10-03 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-15 Cont ID  
Sent By mjacobs Date 2008-08-15 Time 07:40 Rev Time 0.00
Received By mjacobs Date 2008-08-15 Time 06:56 Sent To PC
Notes
2008-09-29 07:36:28 
 BUILDING PLAN REVIEW
 PERMIT: 08070715
 ADD: 1255 PBL BLVD
 CONT: DAVCAO RETAIL SERVICES
 TEL: (214)706-4029
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-15-08
 REVIEW 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. SHOW THIS
 INFORMATION ON THE PLANS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5) PLEASE GIVE MORE DETAIL AS TO THE TYPE OF EXAM WHICH
 WILL BE PERFORMED. ADDITIONAL INFORMATION IS REQUIRED
 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 15:21 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 15:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-08 Cont ID  
Sent By btrobaug Date 2008-10-08 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2008-10-07 Time 11:24 Sent To  
Notes
2008-10-07 12:57:25 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW
 DATED 8/13/08 AND HAVE NOT BEEN PROPERLY RESPONDED TO.
  
 1} THE MINIMUM CURRENT CODES ARE NOT INDICATED ON THE
 ELECTRICAL SHEETS.
  
 3} THE LIGHTING CONTROL PANEL OR AUTOMATED LIGHTING
 CONTROLS COULD NOT BE LOCATED ON THE PLANS.
  
 4} NO LIGHTING PERFORMANCE CALCULATIONS WERE GIVEN,
 ONLY FIXTURE WATTAGE PER TYPE.***ALL THAT IS REQUIRED
 FOR THE ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 6} THE RISER ON E2.1A STILL HAS AN EQUIPMENT GROUNDING
 CONDUCTOR RUNNING FROM THE TAP FEEDER TO THE NEW 200
 AMP PANEL***250.6.THIS GROUND WOULD BE REQUIRED AFTER
 THE FIRST MEANS OF DISCONNECT PER 250.122. SEE COMMENT
 #1 BELOW.
  
 NEW COMMENTS THIS REVIEW 10/7/08.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70. INDICATE LOCATION ON PLAN PER 230.72(A)(1).
 THE AHJ HAS DETERMINED THAT "NEAREST POINT OF ENTRANCE"
 SHALL BE NO FARTHER THAN 8' OF UNPROTECTED CONDUCTORS.
 INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN.
  
 2} LABEL NEW PANEL LP-4 ON THE RISER DIAGRAM, SHEET
 E2.1A.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By dpalmer Date 2008-08-13 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2008-08-13 Time 11:44 Sent To  
Notes
2008-08-13 11:46:08 
 ** DENIED PLANS.**
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 FBC 2004 W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW
 HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR
 ADA.
  
 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR AUTOMATED LIGHTING CONTROLS REQUIRED. STATING ON
 PLANS MOTION SENSOR OR STANDARD SWITCH DOES NOT MEET
 THE MINIMUM PER CODE.
  
 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLANS SEEM TO BE SIGNED WITH SOME SORT OF
 INITIAL. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGN PROFESSIONAL PLEASE SUBMIT A SIGNED, DATED AND
 SEALED LETTER FOR SIGNATURE VERIFICATION. THIS LETTER
 NEEDS TO BE ORIGINAL AND NOTARIZED PER FS 117.05.
 FS 471.025
  
 6) NOTE: RISER SHOWS EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED.
 250.6,250.24. THIS CREATES OBJECTIONABLE CURRENTS.
  
 7) NOTE: PLEASE SEE NEW MECHANICAL COMMENTS AS THE
 COOLING LOAD CALCULATIONS WHICH ARE RAISED SEALS OVER A
 PHOTO-COPIED SIGNATURE WHICH IS IN VIOLATION OF FS
 471.025, FAC 61G15-23.002
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 11:39 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 11:31 Sent To  
Notes
2008-10-21 11:35:25*****APPROVED*****
  
  
 PLAN SHEET E1.1A WAS STAMPED, INITIALED, AND DATED;
 SHEETS A1.1B, E1.6B, & FP1.1 WERE PREVIOUSLY
 FIRE-STAMPED ON 10/10/2008.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By mwennerg Date 2008-10-10 Time 11:32 Rev Time 0.00
Received By mwennerg Date 2008-10-10 Time 11:32 Sent To  
Notes
2008-10-10 11:33:24STAMPED SHEETS A1.1B, E1.6B AND FP1.1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By mawillia Date 2008-08-12 Time 11:32 Rev Time 0.00
Received By mawillia Date 2008-08-12 Time 10:11 Sent To  
Notes
2008-08-12 10:59:33*****DENIED*****
  
  
 1.STRUCTURES UNDERGOIG CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO GENERAL DEMOLITION NOTES (SHEET A0.2)
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.AMEND
 GENERAL DEMOLITION NOTE #4 (SHEET A0.2)
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.INDICATE/SHOW HOW THE SCOPE OF WORK WILL HAVE CAUSE
 FOR ANY FIRE ALARM DEVICES TO BE RELOCATED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 11:00 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 11:00 Sent To  
Notes
2008-10-16 11:01:02TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 11:10 Sent To  
Notes
2008-09-23 11:10:34TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 14:07 Sent To  
Notes
2008-08-01 08:45:568/1/08-TO "BOB"#5,PER "RBROWN".PLEASE SEE FRONT
 SCREEN NOTES.
2008-07-29 14:07:33TO "COMM" BD#7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-25 Cont ID  
Sent By tgordon Date 2008-09-25 Time 08:18 Rev Time 0.30
Received By tgordon Date 2008-09-25 Time 08:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By tgordon Date 2008-08-01 Time 13:36 Rev Time 0.00
Received By tgordon Date 2008-08-13 Time 13:38 Sent To  
Notes
2008-08-13 13:47:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE SIGNATURE ON THE COOLING LOAD SUMMARY IS A PHOTO
 COPY, A PHOTO COPY IS NOT ACCEPTABLE IT MUST BE HAND
 WRITTEN. PLEASE CORRECT PER 2004 FBC 13-407.1.ABC.1
 EXCEPT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-16 Cont ID  
Sent By mperson Date 2008-10-16 Time 16:23 Rev Time 0.30
Received By mperson Date 2008-10-16 Time 16:23 Sent To  
Notes
2008-10-16 16:24:32****************PROVISO*****************
 FOR INFORMATION ONLY, REVISION NOT REQUIRED.
 PER ARTICLE III SEWERS AND SEWER DISPOSAL. SECTION
 90-125. PROHIBITIONS AND LIMITATION OF DISCHARGE.
 (20)(D) LOCAL PRETREATMENT STANDARD, TABLE INSET, FOR
 PH (STANDARD UNITS) 5.5--9.5 (MG/L) AND SILVER 4.5
 (MG/L) MAXIMUM ALLOWABLE CONCENTRATION DURING A 24-HOUR
 PERIOD.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-29 Cont ID  
Sent By mperson Date 2008-09-29 Time 13:09 Rev Time 0.30
Received By mperson Date 2008-09-29 Time 13:09 Sent To  
Notes
2008-09-29 13:33:49PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #8 EW-1:
 THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1
 DOES NOT COMPLY WITH THE FBC-2004 PLUMBING . PLEASE
 KNOW THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE
 INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED
 LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004
 PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING
 VALVES.
  
 **RESPONSE NOTED, HOWEVER THE COMMENT HAS NOT BEEN
 ADDRESSED. RESPONSE STATES THAT THE MIXING VALVES TO
 THE HAND SINKS HAVE BEEN REMOVED, HOWEVER THE ORIGINAL
 COMMENT WAS ABOUT THE MIXING VALVE FOR THE EYE WASH NOT
 THE HAND SINKS. PLEASE REVISE PLANS FOR THE EYE WASH
 MIXING VALVE TO READ STANDARD ASSE 1017. PER FBC-2004
 PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING
 VALVES.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 2. SHEET P1.1B WATER HEATER INSTALLATION DETAIL #1: THE
 EXPANSION TANK NEEDS TO BE DOWNSTREAM OF THE WATTS 200
 SERIES PRESSURE REGULATOR VALVE. PER FBC-2004 PLUMBING
 SECTION 607.3.1 PRESSURE-REDUCING VALVE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By mperson Date 2008-08-12 Time 09:25 Rev Time 0.00
Received By mperson Date 2008-08-12 Time 09:25 Sent To  
Notes
2008-08-12 09:33:18PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #8 EW-1:
 THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1
 DOES NOT COMPLY WITH THE FBC-2004 PLUMBING . PLEASE
 KNOW THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE
 INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED
 LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004
 PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING
 VALVES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By adavila Date 2008-08-04 Time 10:35 Rev Time 0.00
Received By adavila Date 2008-08-01 Time 10:35 Sent To  
Notes
2008-08-04 14:15:27PERMIT FOR INTERIOR WORK ONLY.NO SITE OR EXTERIOR
 WORK TO BE DONE AS PART OF THIS PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  