Plan Review Stops For Permit 08070695 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-09-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-09-11 |
Time |
13:01 |
Rev Time |
0.88 |
Received By |
jwitmer |
Date |
2008-09-11 |
Time |
13:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-12 |
Time |
16:30 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-08-12 |
Time |
16:30 |
Sent To |
|
|
Notes |
2008-08-12 16:47:46 | BUILDING PLAN REVIEW | | PERMIT: 08070695 | | ADD: 848 SOUTHERN BLVD | | CONT: PLAN REVIEW ? DUSTIN HICKS | | TEL: (561)542-5537 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL FL S S 713.13NOTICE OF | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | INSPECTION. | | | | 1C)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. | | | | 2) LS-1 BUILDING DATA SUMMARY CONSTRUCTION TYPE IS | | INDICATED AS A III-B, NOTE THE BUILDING TYPE IS FOR THE | | WHOLE BUILDING NOT THE TENANT BUILDOUT, THERE IS | | APPROXIMATELY 106,325 SQ FT IN THIS BUILDING AND THE | | DATA SUMMARY INDICATES THIS IS NOT AFIRE SPRINKLERED | | BUILDING. PLEASE LOOK AT TABLE 503 AND ALLOWABLE AREAS | | FOR MERCANTILE AND THE MINIMUM BUILDING TYPE. | | | | 3)LS-1 DOES NOT INDICATE IF THE INTERIOR PARTITIONS | | ARE NEW OR EXISTING? 106.1.2 ADDITIONAL INFORMATION | | REQUIRED. | | | | 4) LS-1 DOES NOT INDICATE THE 2004 EXISTING BUILDING | | CODE OR LEVEL OF ALTERATION PLEASE SEE 2004 EXISTING | | BUILDING CODE 301.5. | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-09-26 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-09-26 |
Time |
10:47 |
Sent To |
FIRE |
|
Notes |
2008-09-26 10:53:51 | | | | | | | MANUFACTURER SPECIFICATION SHEETS FOR THE FIXTURES | | SUBMITTED BY THE ARCHITECT SUPPORT DENSITY | | CALCULATIONS./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-09-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-24 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-24 |
Time |
16:01 |
Sent To |
|
|
Notes |
2008-09-24 16:02:09 | ** DENIED 3RD REVIEW ** | | | | | | ** 2ND REVIEW UNDER PERMIT APPLICATION. | | | | | | 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOW | | SUBMITTED FOR FIRST REVIEW ARE NOT CORRECT AND DO NOT | | MEET FBC 13-415.2,13-415.2.ABC.1.1, .1.2. | | PLEASE SEE IN FACT THE LIGHTING WATTAGES AS SHOWN FOR | | MOST ALL OF THE FIXTURES IS INDICATING EACH FIXTURE AS | | 35WATTS. HOW IS THIS POSSIBLE WHEN THE FIXTURE LEGEND | | CLEARLY INDICATES MANY OF THESE FIXTURES CONTAINING 3- | | T-8 BULBS? WHAT ARE THE WATTAGES OF THESE T-8 BULBS. | | BASED ON MOST MANUFACTURES ON THE MARKET, THIS OFFICE | | COULD NOT LOCATE ANY 11-13 WATT T-8 BULBS WHICH WOULD | | BE THE TOTAL AS SHOWN FOR EACH FIXTURE ON CALCULATIONS. | | PLEASE KNOW THAT EVEN WITH THE MOST EFFICIENT BALLAST | | ON THE MARKET KNOWN TO DATE, THE POWER FACTOR RATING | | WILL NOT TAKE 3-32WATT STANDARD T-* BULBS WHICH IS | | 96WATTS AND TAKE THE RATING DOWN TO 35WATTS FOR ALL | | THREE BULBS IN A SINGLE FIXTURE. AS SHOWN ON PLANS THE | | AMOUNT OF LIGHT EXCEEDS THE ALLOWANCES IN THE FLORIDA | | BUILDING CODE. | | THE WATTAGE WHICH IS REQUIRED TO BE USED IS THE FIXTURE | | WATTAGE NOT THE BULB WATTAGE. BASED ON PLANS AND | | INFORMATION AT THIS TIME THIS DOES NOT MEET THE FBC | | SECTIONS AS NOTED. | | ** PLEASE BE SURE TO COMPLETE THE FIXTURES ON LEGEND. | | AN EXAMPLE WOULD BE THE RESTROOM LIGHT WHICH IS NOT | | SPECIFIED. | | | | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | NOTICE GIVEN AT THIS TIME. PLEASE KNOW ONE COPY OF | | ELECTRICAL PLANS/SHEETS HAVE BEEN RETAINED BY THIS | | OFFICE. | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-09-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-12 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-12 |
Time |
11:14 |
Sent To |
|
|
Notes |
2008-09-12 11:15:01 | ** DENIED REVIEW ** | | | | ** FIRST REVIEW UNDER PERMIT APPLICATION. | | | | | | | | 1) NOTE: PLEASE SEE THAT NO LIGHTING PERFORMANCE | | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2 WERE | | SUBMITTED. | | NO REVIEW OF THESE COULD BE DONE WHEN THEY ARE NOT ON | | PLANS OR IN PACKAGE. | | PLEASE SEE TABLES 13-415.2.B, 13-415.2.C | | | | ** THIS WAS ON PREVIOUS REVIEW COMMENTS. | | | | 2) NOTE: PLEASE INDICATE THE AIC RATINGS OF NEW SERVICE | | EQUIPMENT. 110.9. THIS WAS NOT ON PREVIOUS REVIEW AS | | SERVICE WAS NOT THE SAME. | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-11 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-11 |
Time |
14:52 |
Sent To |
|
|
Notes |
2008-08-11 14:52:42 | | | **DENIED** | | | | 1) NOTE: PLEASE KNOW PLANS ARE ONLY BEING SUBMITTED FOR | | PLAN REVIEW AND ARE NOT BEING SUBMITTED UNDER PERMIT | | APPLICATION. PLEASE KNOW EVEN ONCE PLANS ARE FOUND TO | | BE CODE COMPLIANT PLANS WILL REMAIN IN A FAILED STATUS | | UNTIL PERMIT IS APPLIED FOR. LICENSING OF DESIGNERS ETC | | WILL BE VERIFIED AFTER PERMIT APPLICATION. | | | | ** PLEASE ALSO VERIFY THAT THE PLANS WERE ALREADY | | SUBMITTED FOR *PLAN REVIEW * IN MARCH 08 UNDER TRACKING | | NUMBER 08030346. | | | | 2) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN | | THE FOLLOWING MINIMUM CODES. | | 2004 FBC W/2007 REVISIONS | | 2003 NFPA-101 | | 2002 NFPA-72 (WHERE APPLICABLE) | | 2005 NFPA-70 | | | | ** STATING THE LATEST EDITION IS NOT PERMITTED. | | | | 2) NOTE: PLEASE KNOW BASED ON RISER AS SHOWN THE NEW | | SERVICE IS NOT PERMITTED OR FALL UNDER THE EXCEPTIONS | | OF 230.2 TO GRANT AN ADDITIONAL SERVICE. | | | | 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND | | PROVIDE NOTES ON PLANS ACCORDINGLY. | | | | 4) NOTE: PLEASE PROVIDE LIGHTING CONTROLS ARE REQUIRED | | PER 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE SEE 13-415.1.ABC.1.4 FOR ANY OUTSIDE LIGHTING. | | SOME NOTES ON PLANS INDICATE SENSOR TYPE DEVICES OF | | SOME KIND HOWEVER NOT ENOUGH INFORMATION IS PROVIDED. | | NO TIMES ON DEVICES, DEVICES ARE NOT LISTED ON SYMBOL | | LEGEND, NO OTHER INFORMATION PROVIDED. ETC. | | | | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2. | | MUST ALSO SUBMIT A COMPLETED FIXTURE LEGEND WITH ALL | | NEW FIXTURES. | | | | 6) NOTE: PLANS INDICATE CEILING MOUNTED OUTLET BOXES BY | | LANDLORD HOWEVER AS THIS IS A SEPARATE LEGAL TENANT | | SPACE COMMON AREAS SHALL NOT FEED INTO TENANT | | SPACE(S). | | PLEASE CONFIRM THAT THESE OUTLET BOXES ARE ACTUALLY | | LOCATED ON THE OUTSIDE OF THIS TENANT SPACE. | | | | 7) NOTE: PLEASE INDICATE THE REQUIRED SHOW WINDOW | | RECEPTACLES PER 210.62 AND LOADS PER 220.43A | | | | 8) NOTE: RISER SHOWS A 200AMP SERVICE HOWEVER | | CONDUCTORS ON RISER ARE ONLY RATED FOR 150AMPS. 310.16 | | | | 9) NOTE: RISER INDICATES EQUIPMENT GROUNDING CONDUCTOR | | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT | | PERMITTED 250.6,250.24 | | | | 10) NOTE: PLEASE EXPLAIN HOW WATER HEATER IS BEING | | FIGURED INTO THE LOAD CALCULATIONS. PLEASE SEE 422.13 | | AS WATER HEATER (STORAGE TYPE) ARE CONSIDERED A | | CONTINUOUS LOAD AND NEEDS TO BE FIGURED AT 125%. | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-26 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-26 |
Time |
13:54 |
Sent To |
|
|
Notes |
2008-09-26 13:55:03 | STAMPED NEW LS-1 SHEETS (2) |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-16 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-16 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-08-20 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-08-20 |
Time |
11:10 |
Sent To |
|
|
Notes |
2008-08-20 11:16:52 | PLAN REVIEW ONLY | | | | PLANS WILL REMAIN IN FAILED STATUS EVEN AFTER APPROVAL | | UNTIL APPLICATION FOR PERMIT HAS BEEN REVIEWED AND | | APPROVED. | | | | 1) ADDRESS ON PLANS ARE DIFFERENT FROM THE PLAN REVIEW | | SUBMITTAL. PLEASE CORRELATE INFORMATION. | | | | 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH THE REQUIREMENTS OF NFPA 241. | | | | 4) STAIRS REQUIRED TO HAVE HANDRAILS ON BOTH SIDES. | | (101, SEC. 7.2.2.4.1.1.) | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-22 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-22 |
Time |
14:01 |
Sent To |
P |
|
Notes |
2008-10-22 14:02:22 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-09-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-18 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-18 |
Time |
08:44 |
Sent To |
|
|
Notes |
2008-09-18 08:46:52 | TO "COMM" BD#49 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-09-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-02 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-02 |
Time |
11:24 |
Sent To |
|
|
Notes |
2008-09-02 11:26:58 | TO "COMM" BD#6--PROJ TO PERMIT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-08-20 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-07-24 |
Time |
10:10 |
Sent To |
|
|
Notes |
2008-07-24 10:24:56 | TO "COMM" BD#60 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-09-10 |
Time |
10:33 |
Rev Time |
0.40 |
Received By |
tgordon |
Date |
2008-09-10 |
Time |
10:33 |
Sent To |
|
|
Notes |
2008-09-10 10:37:15 | *** PROVISO *** | | 1) BATHROOM EXHAUST FAN MUST COMPLY WITH 2004 FBC/M | | 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY | | MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS | | AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM | | WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A | | VENTILATING SYSTEM. | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-07-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-24 |
Time |
11:37 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-07-24 |
Time |
11:37 |
Sent To |
|
|
Notes |
2008-07-24 11:59:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | FOR PLAN REVIEW ONLY NOT FOR PERMIT. | | *** DENIED *** | | | | 1) PLAN PAGE A-0 STATES "NO MECHANICAL WORK PROPOSED" | | BUT PLAN PAGE E-1 LIGHTING PLAN SHOWS 6 NEW 12X12 | | RETURN AIR TRANSFER GRILLS WITH NO DUCTS. IS THE INTENT | | TO TURN THE ATTIC SPACE INTO A OPEN PLENUM? PLEASE | | SUBMIT MECHANICAL PLANS SHOWING ALL NEW AND ALTERED | | WORK, PER 2004 FBC 106.3.5. | | | | 2) PLAN E-1 SHOW A NEW BATHROOM EXHAUST FAN BEING | | INSTALLED, PLEASE SHOW ON MECHANICAL PLAN AND SHOW WERE | | IT WILL DISCHARGE TO, PER 2004 FBC/M 401.5.2. | | | | 3) PLAN E-1 ALSO SHOWS TWO NEW 24X48 RETURN AIR GRILLS | | AND ALL 24X24 SUPPLY AIR GRILLS BEING RELOCATED. PLEASE | | SHOW ON MECHANICAL PLAN WITH CFM'S AT ALL SUPPLY AIR | | GRILLS AND IF DUCT SIZES ARE BEING CHANGED SHOW NEW | | SIZE, PER 2004 FBC 106.3.5. | | | | 4) PLEASE SHOW ON MECHANICAL PLAN OUTDOOR AIR | | CALCULATIONS, PER 2004 FBC/M 403.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-10-27 |
Time |
09:25 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2008-10-27 |
Time |
09:25 |
Sent To |
PC |
|
Notes |
2008-10-27 09:27:23 | REVISION #2, SHEET P-1: "OK" CHANGED VENTS THRU ROOF TO | | AIR ADMITTANCE VALVES. *MRPERSON. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-09-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-04 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-04 |
Time |
09:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-07-30 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-07-31 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-07-30 |
Time |
09:07 |
Sent To |
|
|
Notes |
2008-07-30 09:23:30 | PLUMBING PLAN REVIEW: | | DENIED:**FOR PLAN REVIEW ONLY NOT FOR PERMIT** | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. SHEET A-0 REQUIRED PLUMBING FIXTURES: THE | | REQUIREMENTS SHOULD BE BASED ON THE FBC- PLUMBING | | SECTION TABLE 403.1 FOR MERCANTILE NOT BUSSINESS. | | PLEASE CORRELATE THE REQUIRED PLUMBING FIXTURES WITH | | THE OCCUPANCY SUMMARY. PER FBC-2004 PLUMBING SECTION | | 401.1 SCOPE AND TABLE 403.1 MINIMUM NUMBER OF REQUIRED | | PLUMBING FIXTURES. | | | | 2. SHEET P-1 SANITARY PLUMBING ISOMETRIC DETAIL #2: | | ONLY THE FIXTURES WITHIN THE BATHROOM GROUP SHALL | | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. (THE | | MOP SINK SHALL CONNECT DOWNSTREAM OF THE BATHROOM | | FIXTURES). PER FBC- PLUMBING SECTION 909.1 WET VENT | | PERMITTED. | | | | 3. SHEET P-1 GENERAL PLUMBING NOTES #15, STATES THE | | FOLLOWING "FURNISH AND INSTALL APPROVED AIR CHAMBERS AT | | EACH PLUMBING FIXTURE AND PDI APPROVED SHOCK ARRESTORS | | ON MAIN LINES AND RISERS". PLEASE KNOW THAT AIR | | CHAMBERS ARE NOT APPROVED BY FBC-2004 PLUMBING SECTION | | 604.9 WATER HAMMER AND SHOULD BE DELETED FROM PLANS. | | 604.9 WATER HAMMER. | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | MANUFACTURER'S SPECIFICATIONS. WATER-HAMMER ARRESTORS | | SHALL CONFORM TO ASSE 1010. | | | | 4. SHEET P-1 POTABLE WATER PLUMBING ISOMETRIC DETAIL | | #2: PLEASE PROVIDE THE FOLLOWING PER FBC-2004 PLUMBING | | SECTIONS. | | | | A} DELETE THE AIR CHAMBERS ON THE RISER DIAGRAM. PER | | SECTION 604.9 WATER HAMMER (REFERENCE COMMENT #3). | | | | B} PROVIDE THE REQUIRED THERMAL EXPANSION CONTROL FOR | | THE WATER HEATER. PER SECTION 607.3 THERMAL EXPANSION | | CONTROL. | | | | 5. SHEET P-1 WATER HEATER DETAIL #6: PLEASE PROVIDE | | THE FOLLOWING PER FBC-2004 PLUMBING SECTIONS. | | | | A} CLEARLY INDICATE THE HEIGHT OF THE WATER HEATER | | SHELF FROM FINNISH FLOOR TO THE TOP OF THE SHELF. PER | | SECTION 501.1 SCOPE. | | | | B} CLEARLY INDICATE THE REQUIRED TEMPERATURE AND | | PRESSURE RELIEF VALVE. PER SECTION 504.4 RELIEF VALVE. | | | | C} CLEARLY INDICATE THE T & P RELIEF VALVE IN THE TOP | | 6 INCHES OF THE TANK BEING SERVED. PER SECTION 504.4.1 | | INSTALLATION. | | | | D} CLEARLY INDICATE THAT THE T & P RELIEF VALVE SHALL | | DISCHARGE FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS | | THE FLOOR, WATER HEATER PAN, OUTSIDE THE BUILDING OR AN | | INDIRECT WASTE RECEPTOR. THE DISCHARGE PIPE SHALL NOT | | HAVE ANY TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR | | GAP OR AIR GAP FITTING IN THE SAME ROOM AS THE WATER | | HEATER. PER SECTION 504.6.1 DISCHARGE. | | | | E} CLEARLY INDICATE THAT THE WATER HEATER PAN SHALL | | NOT BE LESS THAN 1-1/2 INCHES DEEP AND THE PAN DRAIN | | PIPE SIZE SHALL BE MINIMUM OF 3/4 INCHES IN DIAMETER. | | PER SECTION 504.7.1 PAN SIZE AND DRAIN. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-08-01 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-08-01 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
bpowell |
Date |
2008-08-01 |
Time |
17:46 |
Sent To |
|
|
Notes |
|
|