Plan Review Details - Permit 08070695
Plan Review Stops For Permit 08070695
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 13:01 Rev Time 0.88
Received By jwitmer Date 2008-09-11 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 16:30 Rev Time 2.22
Received By jwitmer Date 2008-08-12 Time 16:30 Sent To  
Notes
2008-08-12 16:47:46BUILDING PLAN REVIEW
 PERMIT: 08070695
 ADD: 848 SOUTHERN BLVD
 CONT: PLAN REVIEW ? DUSTIN HICKS
 TEL: (561)542-5537
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) LS-1 BUILDING DATA SUMMARY CONSTRUCTION TYPE IS
 INDICATED AS A III-B, NOTE THE BUILDING TYPE IS FOR THE
 WHOLE BUILDING NOT THE TENANT BUILDOUT, THERE IS
 APPROXIMATELY 106,325 SQ FT IN THIS BUILDING AND THE
 DATA SUMMARY INDICATES THIS IS NOT AFIRE SPRINKLERED
 BUILDING. PLEASE LOOK AT TABLE 503 AND ALLOWABLE AREAS
 FOR MERCANTILE AND THE MINIMUM BUILDING TYPE.
  
 3)LS-1 DOES NOT INDICATE IF THE INTERIOR PARTITIONS
 ARE NEW OR EXISTING? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 4) LS-1 DOES NOT INDICATE THE 2004 EXISTING BUILDING
 CODE OR LEVEL OF ALTERATION PLEASE SEE 2004 EXISTING
 BUILDING CODE 301.5.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-09-26 Cont ID  
Sent By btrobaug Date 2008-09-26 Time 10:55 Rev Time 0.00
Received By btrobaug Date 2008-09-26 Time 10:47 Sent To FIRE
Notes
2008-09-26 10:53:51 
  
  
 MANUFACTURER SPECIFICATION SHEETS FOR THE FIXTURES
 SUBMITTED BY THE ARCHITECT SUPPORT DENSITY
 CALCULATIONS./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2008-09-24 Time 16:01 Sent To  
Notes
2008-09-24 16:02:09** DENIED 3RD REVIEW **
  
  
 ** 2ND REVIEW UNDER PERMIT APPLICATION.
  
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOW
 SUBMITTED FOR FIRST REVIEW ARE NOT CORRECT AND DO NOT
 MEET FBC 13-415.2,13-415.2.ABC.1.1, .1.2.
 PLEASE SEE IN FACT THE LIGHTING WATTAGES AS SHOWN FOR
 MOST ALL OF THE FIXTURES IS INDICATING EACH FIXTURE AS
 35WATTS. HOW IS THIS POSSIBLE WHEN THE FIXTURE LEGEND
 CLEARLY INDICATES MANY OF THESE FIXTURES CONTAINING 3-
 T-8 BULBS? WHAT ARE THE WATTAGES OF THESE T-8 BULBS.
 BASED ON MOST MANUFACTURES ON THE MARKET, THIS OFFICE
 COULD NOT LOCATE ANY 11-13 WATT T-8 BULBS WHICH WOULD
 BE THE TOTAL AS SHOWN FOR EACH FIXTURE ON CALCULATIONS.
 PLEASE KNOW THAT EVEN WITH THE MOST EFFICIENT BALLAST
 ON THE MARKET KNOWN TO DATE, THE POWER FACTOR RATING
 WILL NOT TAKE 3-32WATT STANDARD T-* BULBS WHICH IS
 96WATTS AND TAKE THE RATING DOWN TO 35WATTS FOR ALL
 THREE BULBS IN A SINGLE FIXTURE. AS SHOWN ON PLANS THE
 AMOUNT OF LIGHT EXCEEDS THE ALLOWANCES IN THE FLORIDA
 BUILDING CODE.
 THE WATTAGE WHICH IS REQUIRED TO BE USED IS THE FIXTURE
 WATTAGE NOT THE BULB WATTAGE. BASED ON PLANS AND
 INFORMATION AT THIS TIME THIS DOES NOT MEET THE FBC
 SECTIONS AS NOTED.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURES ON LEGEND.
 AN EXAMPLE WOULD BE THE RESTROOM LIGHT WHICH IS NOT
 SPECIFIED.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME. PLEASE KNOW ONE COPY OF
 ELECTRICAL PLANS/SHEETS HAVE BEEN RETAINED BY THIS
 OFFICE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 11:14 Sent To  
Notes
2008-09-12 11:15:01** DENIED REVIEW **
  
 ** FIRST REVIEW UNDER PERMIT APPLICATION.
  
  
  
 1) NOTE: PLEASE SEE THAT NO LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2 WERE
 SUBMITTED.
 NO REVIEW OF THESE COULD BE DONE WHEN THEY ARE NOT ON
 PLANS OR IN PACKAGE.
 PLEASE SEE TABLES 13-415.2.B, 13-415.2.C
  
 ** THIS WAS ON PREVIOUS REVIEW COMMENTS.
  
 2) NOTE: PLEASE INDICATE THE AIC RATINGS OF NEW SERVICE
 EQUIPMENT. 110.9. THIS WAS NOT ON PREVIOUS REVIEW AS
 SERVICE WAS NOT THE SAME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By dpalmer Date 2008-08-11 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2008-08-11 Time 14:52 Sent To  
Notes
2008-08-11 14:52:42 
 **DENIED**
  
 1) NOTE: PLEASE KNOW PLANS ARE ONLY BEING SUBMITTED FOR
 PLAN REVIEW AND ARE NOT BEING SUBMITTED UNDER PERMIT
 APPLICATION. PLEASE KNOW EVEN ONCE PLANS ARE FOUND TO
 BE CODE COMPLIANT PLANS WILL REMAIN IN A FAILED STATUS
 UNTIL PERMIT IS APPLIED FOR. LICENSING OF DESIGNERS ETC
 WILL BE VERIFIED AFTER PERMIT APPLICATION.
  
 ** PLEASE ALSO VERIFY THAT THE PLANS WERE ALREADY
 SUBMITTED FOR *PLAN REVIEW * IN MARCH 08 UNDER TRACKING
 NUMBER 08030346.
  
 2) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 2004 FBC W/2007 REVISIONS
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
 2005 NFPA-70
  
 ** STATING THE LATEST EDITION IS NOT PERMITTED.
  
 2) NOTE: PLEASE KNOW BASED ON RISER AS SHOWN THE NEW
 SERVICE IS NOT PERMITTED OR FALL UNDER THE EXCEPTIONS
 OF 230.2 TO GRANT AN ADDITIONAL SERVICE.
  
 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND
 PROVIDE NOTES ON PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE PROVIDE LIGHTING CONTROLS ARE REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.ABC.1.4 FOR ANY OUTSIDE LIGHTING.
 SOME NOTES ON PLANS INDICATE SENSOR TYPE DEVICES OF
 SOME KIND HOWEVER NOT ENOUGH INFORMATION IS PROVIDED.
 NO TIMES ON DEVICES, DEVICES ARE NOT LISTED ON SYMBOL
 LEGEND, NO OTHER INFORMATION PROVIDED. ETC.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2.
 MUST ALSO SUBMIT A COMPLETED FIXTURE LEGEND WITH ALL
 NEW FIXTURES.
  
 6) NOTE: PLANS INDICATE CEILING MOUNTED OUTLET BOXES BY
 LANDLORD HOWEVER AS THIS IS A SEPARATE LEGAL TENANT
 SPACE COMMON AREAS SHALL NOT FEED INTO TENANT
 SPACE(S).
 PLEASE CONFIRM THAT THESE OUTLET BOXES ARE ACTUALLY
 LOCATED ON THE OUTSIDE OF THIS TENANT SPACE.
  
 7) NOTE: PLEASE INDICATE THE REQUIRED SHOW WINDOW
 RECEPTACLES PER 210.62 AND LOADS PER 220.43A
  
 8) NOTE: RISER SHOWS A 200AMP SERVICE HOWEVER
 CONDUCTORS ON RISER ARE ONLY RATED FOR 150AMPS. 310.16
  
 9) NOTE: RISER INDICATES EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED 250.6,250.24
  
 10) NOTE: PLEASE EXPLAIN HOW WATER HEATER IS BEING
 FIGURED INTO THE LOAD CALCULATIONS. PLEASE SEE 422.13
 AS WATER HEATER (STORAGE TYPE) ARE CONSIDERED A
 CONTINUOUS LOAD AND NEEDS TO BE FIGURED AT 125%.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-26 Cont ID  
Sent By mwennerg Date 2008-09-26 Time 13:54 Rev Time 0.00
Received By mwennerg Date 2008-09-26 Time 13:54 Sent To  
Notes
2008-09-26 13:55:03STAMPED NEW LS-1 SHEETS (2)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-16 Cont ID  
Sent By mwennerg Date 2008-09-16 Time 09:08 Rev Time 0.00
Received By mwennerg Date 2008-09-16 Time 09:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By mwennerg Date 2008-08-20 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2008-08-20 Time 11:10 Sent To  
Notes
2008-08-20 11:16:52PLAN REVIEW ONLY
  
 PLANS WILL REMAIN IN FAILED STATUS EVEN AFTER APPROVAL
 UNTIL APPLICATION FOR PERMIT HAS BEEN REVIEWED AND
 APPROVED.
  
 1) ADDRESS ON PLANS ARE DIFFERENT FROM THE PLAN REVIEW
 SUBMITTAL. PLEASE CORRELATE INFORMATION.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH THE REQUIREMENTS OF NFPA 241.
  
 4) STAIRS REQUIRED TO HAVE HANDRAILS ON BOTH SIDES.
 (101, SEC. 7.2.2.4.1.1.)
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 14:01 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 14:01 Sent To P
Notes
2008-10-22 14:02:22TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 08:44 Sent To  
Notes
2008-09-18 08:46:52TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 11:24 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 11:24 Sent To  
Notes
2008-09-02 11:26:58TO "COMM" BD#6--PROJ TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-20 Cont ID  
Sent By mwennerg Date 2008-08-20 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2008-07-24 Time 10:10 Sent To  
Notes
2008-07-24 10:24:56TO "COMM" BD#60

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-10 Cont ID  
Sent By tgordon Date 2008-09-10 Time 10:33 Rev Time 0.40
Received By tgordon Date 2008-09-10 Time 10:33 Sent To  
Notes
2008-09-10 10:37:15*** PROVISO ***
 1) BATHROOM EXHAUST FAN MUST COMPLY WITH 2004 FBC/M
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By tgordon Date 2008-07-24 Time 11:37 Rev Time 0.30
Received By tgordon Date 2008-07-24 Time 11:37 Sent To  
Notes
2008-07-24 11:59:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
  
 1) PLAN PAGE A-0 STATES "NO MECHANICAL WORK PROPOSED"
 BUT PLAN PAGE E-1 LIGHTING PLAN SHOWS 6 NEW 12X12
 RETURN AIR TRANSFER GRILLS WITH NO DUCTS. IS THE INTENT
 TO TURN THE ATTIC SPACE INTO A OPEN PLENUM? PLEASE
 SUBMIT MECHANICAL PLANS SHOWING ALL NEW AND ALTERED
 WORK, PER 2004 FBC 106.3.5.
  
 2) PLAN E-1 SHOW A NEW BATHROOM EXHAUST FAN BEING
 INSTALLED, PLEASE SHOW ON MECHANICAL PLAN AND SHOW WERE
 IT WILL DISCHARGE TO, PER 2004 FBC/M 401.5.2.
  
 3) PLAN E-1 ALSO SHOWS TWO NEW 24X48 RETURN AIR GRILLS
 AND ALL 24X24 SUPPLY AIR GRILLS BEING RELOCATED. PLEASE
 SHOW ON MECHANICAL PLAN WITH CFM'S AT ALL SUPPLY AIR
 GRILLS AND IF DUCT SIZES ARE BEING CHANGED SHOW NEW
 SIZE, PER 2004 FBC 106.3.5.
  
 4) PLEASE SHOW ON MECHANICAL PLAN OUTDOOR AIR
 CALCULATIONS, PER 2004 FBC/M 403.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-27 Cont ID  
Sent By mperson Date 2008-10-27 Time 09:25 Rev Time 0.45
Received By mperson Date 2008-10-27 Time 09:25 Sent To PC
Notes
2008-10-27 09:27:23REVISION #2, SHEET P-1: "OK" CHANGED VENTS THRU ROOF TO
 AIR ADMITTANCE VALVES. *MRPERSON.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 09:02 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-30 Cont ID  
Sent By mperson Date 2008-07-31 Time 09:07 Rev Time 0.00
Received By mperson Date 2008-07-30 Time 09:07 Sent To  
Notes
2008-07-30 09:23:30PLUMBING PLAN REVIEW:
 DENIED:**FOR PLAN REVIEW ONLY NOT FOR PERMIT**
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-0 REQUIRED PLUMBING FIXTURES: THE
 REQUIREMENTS SHOULD BE BASED ON THE FBC- PLUMBING
 SECTION TABLE 403.1 FOR MERCANTILE NOT BUSSINESS.
 PLEASE CORRELATE THE REQUIRED PLUMBING FIXTURES WITH
 THE OCCUPANCY SUMMARY. PER FBC-2004 PLUMBING SECTION
 401.1 SCOPE AND TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES.
  
 2. SHEET P-1 SANITARY PLUMBING ISOMETRIC DETAIL #2:
 ONLY THE FIXTURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. (THE
 MOP SINK SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES). PER FBC- PLUMBING SECTION 909.1 WET VENT
 PERMITTED.
  
 3. SHEET P-1 GENERAL PLUMBING NOTES #15, STATES THE
 FOLLOWING "FURNISH AND INSTALL APPROVED AIR CHAMBERS AT
 EACH PLUMBING FIXTURE AND PDI APPROVED SHOCK ARRESTORS
 ON MAIN LINES AND RISERS". PLEASE KNOW THAT AIR
 CHAMBERS ARE NOT APPROVED BY FBC-2004 PLUMBING SECTION
 604.9 WATER HAMMER AND SHOULD BE DELETED FROM PLANS.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 4. SHEET P-1 POTABLE WATER PLUMBING ISOMETRIC DETAIL
 #2: PLEASE PROVIDE THE FOLLOWING PER FBC-2004 PLUMBING
 SECTIONS.
  
 A} DELETE THE AIR CHAMBERS ON THE RISER DIAGRAM. PER
 SECTION 604.9 WATER HAMMER (REFERENCE COMMENT #3).
  
 B} PROVIDE THE REQUIRED THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER. PER SECTION 607.3 THERMAL EXPANSION
 CONTROL.
  
 5. SHEET P-1 WATER HEATER DETAIL #6: PLEASE PROVIDE
 THE FOLLOWING PER FBC-2004 PLUMBING SECTIONS.
  
 A} CLEARLY INDICATE THE HEIGHT OF THE WATER HEATER
 SHELF FROM FINNISH FLOOR TO THE TOP OF THE SHELF. PER
 SECTION 501.1 SCOPE.
  
 B} CLEARLY INDICATE THE REQUIRED TEMPERATURE AND
 PRESSURE RELIEF VALVE. PER SECTION 504.4 RELIEF VALVE.
  
 C} CLEARLY INDICATE THE T & P RELIEF VALVE IN THE TOP
 6 INCHES OF THE TANK BEING SERVED. PER SECTION 504.4.1
 INSTALLATION.
  
 D} CLEARLY INDICATE THAT THE T & P RELIEF VALVE SHALL
 DISCHARGE FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS
 THE FLOOR, WATER HEATER PAN, OUTSIDE THE BUILDING OR AN
 INDIRECT WASTE RECEPTOR. THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING IN THE SAME ROOM AS THE WATER
 HEATER. PER SECTION 504.6.1 DISCHARGE.
  
 E} CLEARLY INDICATE THAT THE WATER HEATER PAN SHALL
 NOT BE LESS THAN 1-1/2 INCHES DEEP AND THE PAN DRAIN
 PIPE SIZE SHALL BE MINIMUM OF 3/4 INCHES IN DIAMETER.
 PER SECTION 504.7.1 PAN SIZE AND DRAIN.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By bpowell Date 2008-08-01 Time 17:46 Rev Time 0.00
Received By bpowell Date 2008-08-01 Time 17:46 Sent To  
Notes
***NONE***