2008-07-24 09:01:09 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| 1. NOTE: THE SUBMITTED GAS PLANS CAN NOT BE APPROVED |
| DUE TO THE FACT THAT THERE IS ALREADY AN APPROVED GAS |
| PLAN FOR THE COMMERCIAL GENERATOR ON GEN/COM PERMIT |
| #07040466 THAT IS SIGNED AND SEALED BY AN ARCHITECT. |
| PLEASE KNOW THAT YOUR SUBMITTED PLANS ARE DIFFERENT |
| THAN THE APPROVED PLANS BEING THAT THE APPROVED PLANS |
| ARE INSTALLING 1-1/2" SCHEDULE 40 METALLIC ABOVE GROUND |
| AND YOUR PLANS ARE USING 2" PE PIPING UNDERGROUND. |
| IN ORDER TO RECIEVE A GAS PERMIT FOR THIS JOB THE |
| RESUBMITTED PERMIT APPLICATION SHOULD STATE IN THE |
| "DESCRIBE PROJECT IN DETAIL" SECTION OF THE PERMIT |
| APPLICATION THE FOLLOWING, "GAS PERMIT PER APPROVED |
| GEN/COM PERMIT #07040466." PLEASE KNOW THAT ANY CHANGES |
| FROM THE APPROVED SET OF PLANS WILL HAVE TO HAVE THE |
| ORIGINAL DESIGN PROFESSIONAL LEONARD LAFOREST RA |
| #AROO14784 SUBMIT A SIGNED, SEALED, AND DATED REVISED |
| GAS ISOMETRIC RISER DIAGRAM. PER CHAPTER 481, FLORIDA |
| STATUTES, PART 1 AND FAC 61G1-16.004. |
| |
| END OF COMMENTS: |
| |