2008-07-22 16:08:21 | ROOFING, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| ***NOTE:BUILDING PERMIT REFERENCED ON PERMIT |
| APPLICATION IS THREEYEARS OLD AND THERE IS NOT WORK |
| AND INSPECTION ACTIVITY. |
| EXPIRED PERMIT WASREVIEWED UNDER 2001 FBC.CURRENT |
| BUILDING CODE IS 2004 FBC.PERMIT APPLICATION IS TO BE |
| REVIEWED UNDER THE 2004 FBC. |
| |
| 1- CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLYAND |
| SPECIFIC FASTENING OPTION TO BE INSTALLED AS REQUIRED |
| BY CITY POLICY AND PROCEDURE FOR SUBMITTING PRODUCT |
| APPROVALS FOR ROOFING/REROOFING PERMITS. SEE ATTACHED |
| COPY. |
| |
| 2- IF SELECTED ASSEMBLY AND FASTENING OPTION DOESN'T |
| MEET THE DESIGN PRESSURES OF TABLE1609.6.2.1(2) OF |
| FBC 2004 FOR FIELD, PERIMETER AND CORNER AREAS, THEN |
| SIGNEDAND SEALEDRAS 117 CALCULATIONS WILL BE |
| REQUIRED FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS.SEE GENERAL LIMITATION #7 ON SHEET 16 OF 16 OF |
| NOA 06-0601.08 SUBMITTED. |
| |
| ***NOTE: NOTE: IF SELECTED ASSEMBLY IS LIMITED BY |
| GENERAL LIMITATION #9 AND THE DESIGN PRESSURES DON'T |
| MEET THE REQUIREMENTS OF THE ABOVE FBC 2004 TABLE, THEN |
| THE ASSEMBLY CAN'T BE INSTALLED BECAUSE GENERAL |
| LIMITATION #9 DOESN'T ALLOW NAILENHANCING. |
| |
| 3- CLEARLY SPECIFYROOF SQUARE FOOTAGE TO PROPERLY |
| ASSESS PERMIT VALUATION AS REQUIRED BY SEC. 108.3 OF |
| CITY AMENDMENTS TO FBC 2004. |
| |