Plan Review Details - Permit 08070614
Plan Review Stops For Permit 08070614
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-25 Cont ID  
Sent By mperson Date 2008-07-25 Time 10:57 Rev Time 0.00
Received By mperson Date 2008-07-25 Time 10:57 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By mperson Date 2008-07-22 Time 09:23 Rev Time 0.00
Received By mperson Date 2008-07-22 Time 09:23 Sent To I
Notes
2008-07-22 09:38:19GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE AND THE CITY OF WEST
 PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE SUBMITTED DRAWING IS INDICATING THE LONGEST
 LENGTH AS BEING 90', HOWEVER THIS CALCULATION IS WRONG.
 THE ADDED SUM OF THE INDICATED MEASUREMENTS COMES TO
 105' AND THAT NOT ADDING UP THE CUT SECTIONS OF PIPE
 FROM THE REQUIRED ISOMETRIC (REFERENCE COMMENT #1).
  
 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 (W.P.B. AS AMENDED) SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-25 Cont ID  
Sent By mperson Date 2008-07-25 Time 10:57 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 10:57 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By mperson Date 2008-07-22 Time 09:38 Rev Time 0.00
Received By mperson Date 2008-07-21 Time 09:21 Sent To PC
Notes
***NONE***