Plan Review Details - Permit 08070612
Plan Review Stops For Permit 08070612
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-25 Cont ID  
Sent By btrobaug Date 2008-07-25 Time 11:01 Rev Time 0.00
Received By btrobaug Date 2008-07-25 Time 10:59 Sent To I
Notes
2008-07-25 11:01:38 
  
  
 PROVISO
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS PERMIT IS BEING ISSUED TO FACILITATE THE REPAIR OF
 THIS RESIDENCE, THE PLANS HOWEVER ARE INCOMPLETE.
 RESUBMIT A REVISION SHOWING ACTUAL ALARM LOCATIONS,
 USING ACCEPTED SYMBOLS ACCEPTED AS STANDARD IN THE
 INDUSTRY, PRIOR TO CALLING ELECTRICAL INSPECTION. THE
 REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF
 INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR
 PLAN REVIEW.
  
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 2} PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY, DRAWN TO
 A MINIMUM OF 1/8 INCH SCALE. PLANS ARE REQUIRED TO
 CLEARLY INDICATE THE SCOPE OF WORK INTENDED IN THE
 DESCRIPTION ON THE APPLICATION, AND SUITABLE FOR RECORD
 RETENTION.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By btrobaug Date 2008-07-25 Time 11:02 Rev Time 0.00
Received By btrobaug Date 2008-07-25 Time 10:59 Sent To PC
Notes
***NONE***