Plan Review Details - Permit 08070576
Plan Review Stops For Permit 08070576
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-25 Cont ID  
Sent By shill Date 2008-08-25 Time 16:44 Rev Time 0.00
Received By shill Date 2008-08-25 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 15:43 Rev Time 0.00
Received By shill Date 2008-08-18 Time 15:43 Sent To  
Notes
2008-08-18 15:47:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE OPEING 11.SPAN SHOULD BE 124" FOR A 3" EDGE
 DISTANCE.HOWEVER, PANELS LIMITED TO 123".PLEASE
 REVISE.
  
 2.DETAILS 1 AND 4 ARE SPECIFIED, BUT THE PRODUCT
 APPROVAL USES MOUNTING TYPES A THROUGH E.PLEASE
 REVISE TO BE CONSISTENT WITH THE ANCHOR SCHEDULES ON
 THE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 09:10 Rev Time  
Received By shill Date 2008-08-01 Time 16:51 Sent To  
Notes
2008-08-04 09:10:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE OPENING 1.A 34IN OPENING WITH 3IN EDGE
 DISTANCE, SPAN SHOULD BE A MINIMUM OF 40IN, NOT 38IN.
 CHECK ALL; THIS COMMENT MAY APPLY TO OTHER OPENINGS.
  
 2.SEE ACCORDION PRODUCT APPROVAL, PAGE 5 AND 10. WALL
 MOUNT 1 REQUIRES A CONCRETE SUBSTRATE, THIS JOB IS
 CONCRETE BLOCK.PLEASE REVISE AND CHECK ALL.
  
 3.SEE ACCORDION PRODUCT APPROVAL, PAGE11.MINIMUM
 SPACING IS 3?; YOU HAVE SPECIFIED 2.49 FOR OPENINGS
 3-6.ANCHORS CANNOT BE THIS CLOSE TOGETHER AS IT
 COMPROMISES THE SUBSTRATE (CAUSES IT TO SPLIT).PLEASE
 REVISE INSTALLATION SCHEDULE.CHECK ALL AND REVISE.
  
 4.OPENING 3, CHECK SPAN.3 7/8" SHUTTER TO GLASS
 SEPARATION REQUIRED, NOT 3 5/16; SPAN SHOULD BE 106",
 NOT 104", PAGE 11 OF PRODUCT APPROVAL.CHECK ALL AND
 REVISE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 11:32 Sent To B
Notes
2008-08-06 11:33:13TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 09:10 Rev Time 0.00
Received By shill Date 2008-07-21 Time 08:44 Sent To  
Notes
2008-07-21 08:45:50TO "MISC" BOX#1