Plan Review Details - Permit 08070523
Plan Review Stops For Permit 08070523
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-02 Cont ID  
Sent By jgomez Date 2008-09-02 Time 14:08 Rev Time 0.00
Received By jgomez Date 2008-09-02 Time 13:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-07 Cont ID  
Sent By jgomez Date 2008-08-07 Time 11:47 Rev Time 0.00
Received By jgomez Date 2008-08-07 Time 11:46 Sent To PC
Notes
2008-08-07 13:25:05RESIDENTIAL (R3) ROOFING, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-ENGINEERCALCULATIONS PROVIDED DON'T COMPLY WITH
 SECTION 9OF RAS 117 CALCULATIONS. CHECK THE NUMBER
 OF FASTENERS AND FASTENER SPACING REQUIREMENTS. PROVIDE
 ACTUAL CALCULATIONS ANDPROVIDE SKETCH SHOWING
 LOCATION OF FASTENERSAS REQUIRED BY FIGURE 3 OFRAS
 117 CALCULATIONS.
 NOTE: MAKE SURETHE MINIMUM FASTENER SEPARATION MEETS
 THE REQUIREMENTS OF SEC. 8.1 OF RAS 117 CALCULATIONS.
 SEC. 106.1.2 CITY AMENDMENTS TOFBC 2004 TO VERIFY
 COMPLIANCE WITH RAS 117 CALCULATIONS.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FL. ST.THIS MAY BE SUBMITTED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By jgomez Date 2008-07-18 Time 14:42 Rev Time 0.00
Received By jgomez Date 2008-07-18 Time 14:06 Sent To  
Notes
2008-07-18 14:51:16RESIDENTIAL R(3) REROOF BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2-FLAT ROOF SYSTEM:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY AND
 FASTENING OPTION TO BE USED AS REQUIRED BY CITY POLICY
 FOR ROOFING PERMITS. SEE ATTACHED COPY.
  
 B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 *** NOTE: TAKE INTO CONSIDERATION NUMBER OF FASTENERS
 FOR INSULATION. SEE SEC. 9AND FIGURE 1 THRU FIGURE 4
 OF RAS 117 FORSPECIFICNUMBER AND SPECIFIC FASTENER
 PLACEMENT.PROVIDE INFORMATIONAS REQUIRED TO COMPLY
 WITH THIS STANDARD.
  
 3- PLEASE DON'T SUBMIT ROOFING PERMIT APPLICATIONS FROM
 HIGH-VELOCITY ZONE.THEY DON'T APPLY TO THIS
 JURISDICTION.PROVIDE ONLY THE INFORMATION REQUIRED BY
 THE CITY POLICY FOR ROOFING PERMITS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-18 Cont ID  
Sent By jgomez Date 2008-07-18 Time 14:54 Rev Time 0.00
Received By jgomez Date 2008-07-18 Time 14:07 Sent To  
Notes
***NONE***