Plan Review Details - Permit 08070467
Plan Review Stops For Permit 08070467
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-08-31 Cont ID  
Sent By jwitmer Date 2009-08-31 Time 17: Rev Time 1.00
Received By jwitmer Date 2009-08-31 Time 17:00 Sent To  
Notes
2009-08-31 17:32:02BUILDING PLAN REVIEW
 PERMIT: 08070467
 ADD: 303 BANYAN BLVD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 AUGUST 31, 2009
  
 BUILDING PROVISO:
  
 1) PROVIDE AN APPROVED HANDRAIL ON ONE SIDE IN BOTH
 EXISTING STAIRWELLS PURSUANT TO 605.9 FL 2004 EXISTING
 BUILDING CODE.
  
 2) PROVIDE OPERATIONAL MEANS OF EGRESS LIGHTING IN BOTH
 STAIRWELLS PURSUANT TO 605.7 FL 2004 EXISTING BUILDING
 CODE AND 1006 OF THE 2004 FBC.
  
 3) EAST STAIRWELL 3RD FLOOR, PLEASE PROVIDE COMPLIANCE
 WITH 11-4.13.6 MANEUVERING CLEARENCES AT DOORS SEE
 FIGURE 25(A) FRONT APPROACH REQUIRES A 60 INCHES CLEAR,
 PROVIDE REVISION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-07-25 Cont ID  
Sent By jwitmer Date 2009-07-25 Time 14:35 Rev Time 1.11
Received By jwitmer Date 2009-07-25 Time 13:30 Sent To  
Notes
2009-07-25 14:25:02REVISIONS PER SKETCHES:
 SKETCH NUMBER& DATE :
 1) SSK-FC-1 3-17-09
 2) SSK-FC-2 3-17-09
 3) SSK-FC-4 3-17-09
 4) SSK-FC-3 3-24-09
 5) SSK-FC-5 3-24-09
 6) SSK-FC-6 3-24-09
 7) SKA-1 4-06-09
 8) SKA-2 4-06-09
 9) SK-12R 4-21-09
 10) SK14R 4-21-09
 11) SK-15 4/03/09
 12)SK-16 4/22/09
 13)SK-17 5/01/09
 14)SK-01/AD1.2 5/01/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-07-23 Cont ID  
Sent By jwitmer Date 2009-07-23 Time 13:00 Rev Time 0.50
Received By jwitmer Date 2009-07-23 Time 12:30 Sent To  
Notes
2009-07-23 14:48:46EXPEDITED PLAN REVIEW: 11X17 WALL MOUNTED CONDENSING
 UNIT BRAKETS DATED 7/13/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 08:59 Rev Time 0.77
Received By jwitmer Date 2009-04-06 Time 08:41 Sent To  
Notes
2009-04-06 09:00:47REVISION# 7 SHEETS: AD1.2, A2.1, A2.2 & A3.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-11 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 16:01 Rev Time 1.55
Received By jwitmer Date 2008-12-11 Time 16:01 Sent To  
Notes
2008-12-11 16:04:28REVISION# 5 DATED 12/05/08
 A1.1, A1.2, A2.1, A2.2, A3.1, A3.2 A3.3, S-1, S-2 S-3,
 S-4 S-5, S-5, S-7 AND S-9

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-18 Cont ID  
Sent By jwitmer Date 2008-11-18 Time 11:41 Rev Time 5.55
Received By jwitmer Date 2008-11-18 Time 08:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 07:41 Rev Time 1.77
Received By jwitmer Date 2008-10-23 Time 16:54 Sent To  
Notes
2008-10-24 07:46:20BUILDING PLAN REVIEW
 PERMIT: 08070467
 ADD: 303 BANYAN BLVD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
 OCT. 24, 2008
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) COMPLIED.
 D) COMPLIED
 E) COMPLIED.
 F) COMPLIED
 G) COMPLIED
 H) COMPLIED
 I) COMPLIED.
  
 3)COMPLIED, VALUE OF $850,000.00.
  
 4-7) COMPLIED.
  
 8)SEMI-COMPLIED, THESE ARE NEW PRODUCT APPROVALS WITH
 NEW ISSUES. 609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE3
 COPIES,OF PRODUCT APPROVALS YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING (3) PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) STOREFRONT NOA 03-0801.04 MISSILE IMPACT RARING:
 NONE/ REQUIRES SHUTTERS
 8B) CURTAIN WALL SYSTEM SMALL MISSILE RATING IT APPEARS
 THIS SYSTEM WILL BE USED ONLY AT THE FRONT ENTRY
 REQUIRING LARGE MISSILE IMPACT
 8C) DOORS GLAZED- COMPLIED
 8D) DOORS LOUVERS NO SUBMITTALS
 8E) METAL INSULATED EXTERIOR DOORS- NO SUBMITTALS
 8F) LOUVERS- COMPLIED
 8G) STORM SHUTTERS/ USE OF WINDOWS WITH OUT LARGE
 MISSILE IMPACT
  
 8H) IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1606.1.4. FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9-15) COMPLIED
  
 16) NEW COMMENT: REVISION TO PLANS SHEET A2.1 & A2.2
 BOTH INDICATE A CHANGE FROM STONE REVEAL AND MOLDINGS
 TO A FOAM TRIM PLEASE SEE 1406.2.2. USE OF FOAM
 MOLDINGS OR TRIM ABOVE 40 FEET.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 14:08 Rev Time 2.22
Received By jwitmer Date 2008-09-11 Time 14:08 Sent To  
Notes
2008-09-11 14:29:54BUILDING PLAN REVIEW
 PERMIT: 08070467
 ADD: 303 BANYAN BLVD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 SEPT.11,2008
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) COMPLIED.
  
 D) 2ND REQUEST.THE TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6, TABLE 601. WITH THE VAARIABLE NOW KNOWN AND
 THIS BUILDING HAVING BEEN FULLY SPRINKLERED AT
 COMPLETION OF PROJECT CAN BE DECLARED EITHER A TYPE
 III-B( UNPROTECTED) OR A V-A (1 HOUR PROTECED) WITH
 VERTICAL INCREASE OF ONE STORY (FULLY SPRINKLERED) PER
 SECTION 504.2
  
  
  
 E) COMPLIED. AN AUTOMATIC SPRINKLER SYSTEM IS BEING
 PROVIDED AS PART OFTHE SCOPE OF THIS PROJECT.
 F) COMPLIED
 G) COMPLIED
 H) COMPLIED HEIGTH OF BUILDING, AND HIGHEST OCCUPIALBE
 FLOOR.45'-4"
 I) COMPLIED. SQ. FT. FOOTPRINT/ AREA INCREASES
 TAKEN?11,329 SQ FT
  
 3)COMPLIED, VALUE OF $850,000.00.
  
 4-7) COMPLIED.
  
 8) 609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE3
 COPIES,OF PRODUCT APPROVALS YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING (3) PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) STOREFRONT
 8B) MULLIONS
 8C) DOORS GLAZED
 8D) DOORS LOUVERS
 8E) METAL INSULATED EXTERIOR DOORS
 8F) LOUVERS
  
 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 11-15) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 07:50 Rev Time 8.88
Received By jwitmer Date 2008-08-12 Time 07:50 Sent To  
Notes
2008-08-12 09:16:37BUILDING PLAN REVIEW
 PERMIT: 08070467
 ADD: 303 BANYAN BLVD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) 2004 EXISTING BUILDING CODE, TO WHAT LEVEL
 ALTERATION IS WORK BEING COMPLETED UNDER THIS PERMIT?
 2004 EXIST BUILD CODE 301.5
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 D) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .H) HEIGTH OF BUILDING, AND HIGHEST OCCUPIALBE FLOOR.
 I) SQ. FT. FOOTPRINT/ AREA INCREASES TAKEN?
  
 3) PLEASE INDICATE FULLY THE SCOPE OF WORK TO BE
 COMPLETED UNDER THIS PERMIT, FOR THE REPLACEMENT OF
 WINDOWS AND STUCCO WORK VALUE OF WORK IS CONSIDERBLY
 LOW. IS THE REINFORCEMENT AROUND WINDOWS TO BE
 CONSIDERED AS PART OF THE PERMIT? IS THE GRANITE VENEER
 PART OF THIS PERMIT AS WELL AS THE SYNTHETIC STONE
 WORK? ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 4) THIS IS A 4 STORY BUILDING, WITH STRUCTURAL WORK
 ENVOKING THE THRESHOLD BUILDING REQUIREMENTS OF FL S S
 553.71:
 4A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 4C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 5) THE INTERIOR DEMO PLANS (AD1.2) INDICATE THAT ON THE
 FOURTH FLOOR THE REMOVAL OF A WALL AND DOOR THAT
 ENCLOSE THE 2HR FIRE RATED STAIRWELL AT THE NORTHEAST
 CORNER OF THE BUILDING AN SHEET A1.2 DOES NOT INDICATE
 THE WALL NOR DOOR BEING REPLACED. THIS WALL AND DOOR
 SHOULD HAVE NEVER BEEN REMOVED UNDER THE INTERIOR DEMO
 PERMIT. EXISTING BUILDING CODE 603.2.3.
  
 6) STRUCTURAL SHEET S-6CODES AND STANDARDS REFERENCES
 THE 2007 FBC PLEASE CORRECT TO THE 2004 FBC WITH THE
 2007 SUPPLEMENTS. THE 2007 FBC WILL NOT BE IN EFFECT
 UNTIL DEC 31,2008.
  
 7) SHEET S-5 THE NORTH ELEVATION BOTTOM RIGHT CORNER
 INDICATES A LOUVERED DOOR THAT IS IN ZONE 5 BUT
 INDICATES ZONE FOUR PRESSURES, PLEASE CORRECT, FIGURE
 1609.2.1, NOTATION 10A.
  
 8) 609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 8A) STOREFRONT
 8B) MULLIONS
 8C) DOORS GLAZED
 8D) DOORS LOUVERS
 8E) METAL INSULATED EXTERIOR DOORS
 8F) LOUVERS
  
 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 11) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 12) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 13)SHEET A2.2 SYNTHETHIC STONE SURROUND AND VENEER,
 PLEASE PROVIDE INFORMATION ON THE TYPE OF SYSTEM TO BE
 INSTALLED AND THE FASTENING OR INSTALLATION FOR SYSTEM.
 1406.2, 1406.2.2./ 2605.
  
 14) SHEET A2.1 GRANITE VENEER, NO CUT SECTIONS
 INDICATING THE TYPE OF ATTACHMENT PLEASE SEE 1405.6 OR
 1405.7. PROVIDE ATTACHMENT METHODS.
  
 15) A2.1INDICATE AWNINGS AGAIN THERE IS NO INFORMATION
 AS TO IF EXISTING OR NEW? IF NEW PROVIDE DESIGN CRTERIA
 , AND ATTACHMENT METHODS.ALSO SEE LREQUIRED LETTER FROM
 OWNER.
 A LETTER FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY
 ALL FABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO
 ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING
 COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED
 WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER MUST BE
 SIGNED BY THE OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-10-28 Cont ID  
Sent By btrobaug Date 2009-10-28 Time 12:30 Rev Time 0.00
Received By btrobaug Date 2009-10-28 Time 12:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-09-07 Cont ID  
Sent By dpalmer Date 2009-09-07 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2009-09-07 Time 10:03 Sent To FIRE
Notes
2009-09-07 10:06:31 
 ** DENIED REVIEW OF REVISIONS**
  
 ** PLANS ARE FOR FINAL. NEED TO SHOW ALL ITEMS AS NOTES
 BELOW.
  
 1) NOTE: PLEASE SEE REDLINED PLANS NOTES FROM PREVIOUS
 REVIEW DATED 7/28/09 WITH RESPECT TO DISCONNECTS ON
 SHEETS NOT COORDINATING WITH RISER.
  
 2) NOTE: PLANS HAVE NOW BEEN REVISED FOR 3RD FLOOR
 REMOVING MOST LIGHTING EXCEPT FOR EGRESS PATH TO EXITS.
 HOWEVER NO LIGHTING CONTROLS FOR THESE LIGHTS ARE
 SHOWN?
 PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2 ( 2004 FBC. )
 PLEASE ALSO SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 FOR
 ANY AUTOMATED CONTROLS SUCH AS OCCUPANCY SENSORS WHICH
 SHALL BE *FAIL SAFE ON* TYPE DEVICES.
  
 3) NOTE: THIS IS NOTED FOR INFORMATION ONLY. ASME-17
 FOR ELEVATOR LOBBY LIGHTING AT SILLS/LANDINGS. STATE
 ELEVATOR LIGHTING LEVELS.
 THIS IS NOTED ONLY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 14:47 Sent To M
Notes
2009-07-28 14:48:12** REDLINED REVIEW **
  
 1) NOTE: THE REVISED ELEVATOR DISCONNECTS ON RISER ON
 M5 ARE NOT THE SAME AS ON M8. M5 SHOWS 200AMP WITH
 125AMP FUSES, WHEREAS M8 SHOWS 100AMP DISCONNECTS WITH
 100AMP FUSES.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 13:32 Sent To PC
Notes
2009-07-28 13:32:35EXTERIOR REVISIONS OK>

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-06-29 Cont ID  
Sent By dpalmer Date 2009-06-29 Time 13:41 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 13:41 Sent To PC
Notes
2009-06-29 13:41:58** DENIED PLANS **
  
 ** SUBMITTED REVISIONS TO CHANGE SCOPE OF WORK TO ADD
 EXTERIOR LIGHTS.
  
  
 1) NOTE: PLANS NEED TO BE SUBMITTED REVISED BY THE
 ELECTRICAL DESIGNER OF RECORD.
 FS 471
  
 2) NOTE: WHEN SUBMITTING REVISED ELECTRICAL PLANS FOR
 ADDED SCOPE OF WORK FOR EXTERIOR LIGHTS. PLEASE SHOW
 COMPLIANCE FOR NEW OR EXISTING CONTROLS MEETING FBC
 13-415.1.ABC.1.4.
  
 3) NOTE: PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR
 LIGHTING.
  
 4) NOTE: PLEASE INCLUDE ANY NEW CIRCUITING. PLEASE KNOW
 THAT SPECS FOR INTERIOR OR EXTERIOR FIXTURES ARE NOT
 REQUIRED HOWEVER THE FIXTURE SCHEDULE ON PLANS NEEDS TO
 BE UPDATED TO INCLUDE ANY NEW FIXTURES, OR REVISED
 FIXTURES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-04-14 Cont ID  
Sent By dpalmer Date 2009-04-14 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2009-04-14 Time 14:25 Sent To  
Notes
2009-04-14 14:25:35REDLINED REQUIRED GFI 210.63 FOR A/C CU

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-11-07 Cont ID  
Sent By dpalmer Date 2008-11-07 Time 10:35 Rev Time 0.00
Received By dpalmer Date 2008-11-07 Time 10:35 Sent To  
Notes
2008-11-07 10:36:12NEW SHEET ME7, STAMPED, REDLINE FROM PREVIOUS REVIEW
 REMAINS. NO REVISION NEEDED. 230.2E

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By dpalmer Date 2008-10-22 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2008-10-22 Time 14:27 Sent To  
Notes
2008-10-22 14:27:52REDLINED PLANS.
  
 RISER DOES NOT LABEL MAINS. 1 OF 2 AND 2 OF 2. 230.2E.
 REDLINED AND NO REVISION IS NEEDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 16:05 Sent To  
Notes
2008-09-10 16:06:12 
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ALONG
 WITH NEW NOTES DUE TO INFORMATION NOW SHOWN ON PLANS
 WHICH WAS NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE LEVELS FOR
 EACH FLOOR NEEDS TO BE SHOWN. THE AMOUNT OF LIGHTING IN
 DESIGN DOES NOT EXCEED ALLOWANCE PER 13-415.2.C TABLE
 HOWEVER THE TOTAL DESIGN WATTAGE IS ABOUT HALF OF THE
 ACTUAL WATTAGE FOR EACH FLOOR BASED ON THE FIXTURES ON
 THE SCHEDULE.
 13-415.2.ABC.2.1, .2.2.
  
 2) NOTE: PLEASE COMPLETE ALL FIXTURES ON PLANS. FOR
 EXAMPLE THERE ARE A COUPLE OF FIXTURES WITH NOT
 DESIGNATIONS AT ALL. *3RD FLOOR SOUTHEAST CORNER, AND
 4TH FLOOR CENTER. THESE COULD BE *ASSUMED* HOWEVER
 PLANS NEED TO BE SPECIFIC.
 ** THIS IS ONLY A NOTE, HOWEVER THERE IS ONLY *ONE*
 TYPE *A* FIXTURE. ALL FIXTURES ON LIGHTING PLANS ARE
 SHOWN AS *AE* WITH THE EXCEPTIONS AS NOTED.
 PLEASE COORDINATE.
 **** PLEASE COORDINATE THE FIXTURE DESIGNATIONS AND
 OTHER INFORMATION FOR FIXTURES ON THE PHOTO-METRIC
 PLANS WITH THE LIGHTING PLANS. THE NORMAL LIGHTING
 LEVEL PHOTO-METRIC PLANS CALL FOR ALL TYPE *A* FIXTURES
 YET THIS DOES NOT CORRESPOND TO LIGHTING PLANS. THIS
 WAS NOTED PREVIOUSLY AND RESPONSE MENTIONS THIS WAS
 CORRECTED HOWEVER BASED ON PLANS SUBMITTED THIS IS NOT
 THE CASE.
 13-415.2.ABC.1.1, .1.2.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE 230.2. AS STATED ON PREVIOUS REVIEW
 AT THIS TIME THE NEW SERVICE AS SHOWN CAN NOT BE
 PERMITTED. IN PHONE CONVERSATION WITH ENGINEER BEFORE
 PLANS WERE RESUBMITTED, THIS REVIEWER ASKED TO PROVIDE
 WHERE THIS WOULD MEET AN EXCEPTION TO ALLOW ANOTHER
 SERVICE. THE RESPONSE LETTER MENTIONS BECAUSE OF THE
 LOADS. HOWEVER BASED ON THE SECTION OF THE CODE AS
 NOTED IF A SERVICE REACHES THE LIMIT OF 2000AMPS, THEN
 AN ADDITIONAL SERVICE MAY BE GRANTED BY SPECIAL
 PERMISSION. (SEE DEFINITIONS OF SPECIAL PERMISSION).
 AT THIS TIME THE SERVICE IS NOT A SEPARATE VOLTAGE, IS
 NOT OVER 2000 AMPS ETC.
  
 4) NOTE: PLEASE VERIFY EQUIPMENT GROUNDING PATH FROM
 MAINS TO SUB PANELS.
 250.110,250.122
 NEW NOTE:
  
 5) NOTE: PLEASE CORRECT CODES ON ELECTRICAL NOTES.
 PLEASE SEE NOTES MENTIONS THE STANDARD BUILDING CODE
 AND MARTIN COUNTY AMENDMENTS.
 THIS APPEARS TO BE A MISPRINT.
  
 SHOULD READ AS FOLLOWS.
 2004 FBC /W2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 AS ON OTHER SHEETS.
  
 6) NOTE: VALUE FOR COMPLETE SCOPE OF WORK WAS INCREASED
 BASED ON RESPONSE LETTER AND FEE BALANCE OF $7, 777.00
 WILL BE DUE BEFORE PERMIT CAN BE PRINTED. THE PERMIT
 APPLICATION STATES TO DESCRIBE PROJECT IN DETAIL. THIS
 WAS NOTED ON PREVIOUS REVIEW HOWEVER THE VALUE WAS
 INCREASED BY THIS OFFICE AND APPLICATION NEEDS TO BE
 DONE BY THE CONTRACTOR.
 FBC 108.3
  
 7) NOTE: PLEASE SHOW CIRCUTING AND HOW LIGTHING WILL BE
 CONTROLLED IN STAIRS. THE RESPONSE DOES NTO MENTION HOW
 THIS WAS ADDRESSED AND PLANS DO NOT INDICATE ANY
 CONTROLS. NFPA- 101 7.8.1.2.2, FBC 1006.1.2
  
 8) NOTE: PLEASE LIST MAXIMUM TIMES ON OCCUPANCY
 SENSORS. IF THIS WAS THE ONLY COMMENT THIS WOULD HAVE
 BEEN REDLINED. 13-415.1.ABC.1.1.
  
  
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By dpalmer Date 2008-08-01 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2008-08-01 Time 16:45 Sent To  
Notes
2008-08-01 16:45:41 
 **DENIEDREVIEW**
  
 1) NOTE: PLEASE SEE THE LIFE SAFETY CODE NFPA-101 2003
 CHAPTER 7. PLEASE SEE SECTIONS 7.8 AND 7.9. PLEASE
 EXPLAIN HOW THE LIGHTING SHOWN FOR NORMAL USE IS
 DIFFERENT FIXTURES THAN THE LIGHTING SHOWN FOR
 EMERGENCY USE. THE FACT IS THESE ARE SHOWN AS
 COMPLETELY DIFFERENT FIXTURES.
 PLEASE SEE MISSING EXIT LIGHTS IN SEVERAL LOCATIONS.
 THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL.
 PLEASE SEE 7.8.1.3, 7.9.2.1, 7.9.2.2 AND PLEASE SEE
 7.8.1.2.2 FOR FAIL SAFE CONTROLS. THIS IS ALSO IN FBC
 1006.1.2 (SEE COMMENTS BELOW FOR CHAPTER 13 LIGHTING
 CONTROLS REQUIRED).
 PLEASE SEE SECTIONS 7.10.1.1, 7.10.5.1 ETC. LOCATIONS
 WILL ALSO BE NOTED BY THE FIRE MARSHAL.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MINIMUM CONTROLS REQUIRED FOR LIGHTING. PLEASE SEE
 NOTES ABOVE WITH RESPECT TO LIGHTING IN EGRESS AREAS.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 11. 11-4.28.1,.2,.3.
 PLEASE INDICATE THE MINIMUM LEVELS FOR ADA COMPLIANCE
 FOR ALL HORN/STROBE DEVICES.
  
 4) NOTE: PLEASE SEE 230.2AS THE NEW SERVICE WHICH IS
 NOW BEING SHOWN DOES NOT MEET THE EXCEPTIONS TO GRANT A
 NEW SERVICE.
 PLEASE SEE THE NEW MDP AS THIS SHOWS NEW 400AMP FEED TO
 NEW PANELS ON THIRD AND FORTH FLOORS YET BASED ON THE
 PANEL SCHEDULES THESE PANELS ARE SHOWN WITH A RATING OF
 400AMPS YET THEY ARE ALSO SHOWN WITH 150AMPMAIN LUG
 ONLY.
 WHAT IS THE VOLTAGE ON THE EXISTING SERVICE? SHOWN AS
 120/208 YET RISER ALSO SHOWS A TRANSFORMER.
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1,..1.2.
  
 6) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1,.2.2.
  
 7) NOTE: PLEASE INDICATE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE SEE THE APPLIED SCOPE OF WORK ON PERMIT
 APPLICATION STATES REPLACE WINDOWS AND STUCCO HOWEVER
 BASED ON PLANS THE SCOPE OF WORK IS SUBSTANTIALLY MORE.
 PLEASE KNOW THE PERMIT APPLICATION VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC PER
 FBC108.3 THIS IS FOR ALL TRADES.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-09-08 Cont ID  
Sent By mawillia Date 2009-09-08 Time 11:19 Rev Time 0.00
Received By mawillia Date 2009-09-08 Time 11:01 Sent To E
Notes
2009-09-08 11:18:52*****REVISIONS, APPROVED*****
  
 REVISED PLAN SHEETS A2.1 (8/14/09) AND ME4 (8/12/2009)
 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-04-15 Cont ID  
Sent By mawillia Date 2009-04-15 Time 13:37 Rev Time 0.00
Received By mawillia Date 2009-04-15 Time 12:55 Sent To  
Notes
2009-04-15 13:37:12*****REVISION #7, DATED 3/05/2009, APPROVED*****
  
 REVISED PLAN SHEETS A2.1 AND ME1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-18 Cont ID  
Sent By mawillia Date 2008-11-18 Time 12:32 Rev Time 0.00
Received By mawillia Date 2008-11-18 Time 12:21 Sent To  
Notes
2008-11-18 12:32:04*****APPROVED*****
  
 PLAN SHEETS A1.1, A1.2, A2.1, FP-1 THRU FP-4, ME1 &
 ME2, AND ME6 WERE PREVIOUSLY STAMPED, INITIALED, AND
 DATED ON 10/29/2008; PLAN SHEET A2.1 WAS RESTAMPED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-29 Cont ID  
Sent By mawillia Date 2008-10-29 Time 17:08 Rev Time 0.00
Received By mawillia Date 2008-10-29 Time 15:52 Sent To  
Notes
2008-10-29 17:08:08*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A1.1, A1.2, A2.1, FP-1 THRU
 FP-4, ME1 & ME2, AND ME6 WERE STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-22 Cont ID  
Sent By mawillia Date 2008-09-22 Time 16:00 Rev Time 0.00
Received By mawillia Date 2008-09-22 Time 15:02 Sent To  
Notes
2008-09-22 15:33:47*****DENIED*****
  
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02. THE SCOPE OF WORK SHALL NOT HINDER OR OBSTRUCT
 ACCESS TO / EGRESS FROM THE BUILDING AND/OR OTHER
 BUILDINGS IN THE VICINITY INCLUDING STREETS, ROADS,
 ALLEYS, FIRE LANES.
  
 03. THE LOCATION OF THE NUMERICAL ADDRESS AS SHOWN ON
 DRAWING A2.1 APPEARS TO BE TO HIGH TO BE READILY
 VISIBLE FOR VISITORS AND/OR APPROACHING VEHICLES.
 PLEASE BE ADVISED THAT ADDRESSES SHALL BE CLEARLY
 VISIBLE FROM THE STREET. IN ADDITION, NUMBERS SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 04. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05. PLEASE EXPLAIN WHY THERE IS NO SPRINKLER LAYOUT FOR
 THE 1ST FLOOR (FP-1) AND 2ND FLOOR (FP-2), BUT ARE
 HOWEVER SHOWN ON THE 3RD FLOOR (FP-3) AND THE 4TH FLOOR
 (FP-4)/
  
 06. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY
 FIRE SPRINKLER INSTALLATION OR REMODEL.
  
 07. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C (IF
 INCLUDED IN THIS SCOPE OF WORK).
  
 08. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OR CLASS II (IF INCLUDED IN THIS SCOPE OF WORK).
  
 09. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR ANY
 FIRE ALARM SYSTEM INSTALLATION OR REMODEL.
  
 10. NFPA 72 - 2002 EDITION SHALL BE REFERENCED AS THE
 FIRE ALARM STANDARD.
  
 11. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER LOCAL CODES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-10-27 Cont ID  
Sent By lmartine Date 2009-10-26 Time 11:40 Rev Time 0.00
Received By lmartine Date 2009-10-26 Time 11:40 Sent To  
Notes
2009-10-27 11:41:31******************* EXPEDITED *******************
 GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-08-31 Cont ID  
Sent By lmartine Date 2009-08-31 Time 15:29 Rev Time 0.00
Received By lmartine Date 2009-08-31 Time 15:29 Sent To  
Notes
2009-08-31 15:39:27*********EXPEDITED****************GAVE TO JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-07-21 Cont ID  
Sent By lmartine Date 2009-07-21 Time 13:28 Rev Time 0.00
Received By lmartine Date 2009-07-21 Time 13:28 Sent To  
Notes
2009-07-21 13:30:02*EXPIDITED* ENGINEERING FOR A/C ROOF STAND, GAVE TO JIM
 WITMER
 LM

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-07-16 Cont ID  
Sent By rmcdouga Date 2009-07-16 Time 12:04 Rev Time 0.00
Received By rmcdouga Date 2009-07-16 Time 12:04 Sent To  
Notes
2009-07-16 12:05:58ELECTRICAL REVISION SENT TO DPALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 14:02 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 13:35 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 13:35 Sent To  
Notes
2009-03-27 13:36:17TO IN-BOX "C1"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 10:45 Sent To B
Notes
2008-12-09 10:45:50TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 15:12 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 15:12 Sent To  
Notes
2008-11-06 15:12:31TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-07 Cont ID  
Sent By adarroug Date 2008-10-07 Time 16:02 Rev Time 0.00
Received By adarroug Date 2008-10-07 Time 16:02 Sent To  
Notes
2008-10-07 16:04:51TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 13:44 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 13:44 Sent To  
Notes
2008-08-25 13:45:00TO 'COMM' BD #63.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-12 Time 13:40 Rev Time 0.00
Received By tgordon Date 2008-07-17 Time 13:47 Sent To  
Notes
2008-07-17 13:49:207/17/08--PLANS CHANGED FROM "MISC" TO "COMM-REMODEL".
 TO "COMM" BD#31

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 16:18 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 16:18 Sent To PC
Notes
2009-07-28 16:18:57REVISED ME-5, ME-8 DELTA 5

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 09:24 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 09:24 Sent To  
Notes
2009-04-02 09:24:53REVISED ME-1, ME-5 AND NEW SHEET ME-8

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-10 Cont ID  
Sent By tgordon Date 2008-10-10 Time 13:41 Rev Time 1.00
Received By tgordon Date 2008-10-10 Time 13:41 Sent To  
Notes
2008-10-10 13:42:33MECHANICAL PLAN ME5 SHOWS INSTALLING TWO NEW CHILLED
 WATER PUMPS FOR THE EXISTING 100 TON CHILLER AND
 INSTALLING NEW BALANCING & BUTTERFLY VALVES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-02 Cont ID  
Sent By tgordon Date 2008-09-02 Time 15:24 Rev Time 0.45
Received By tgordon Date 2008-09-02 Time 15:24 Sent To  
Notes
2008-09-02 15:25:06MECHANICAL PLAN ME5 SHOWS INSTALLING TWO NEW CHILLED
 WATER PUMPS FOR THE EXISTING 100 TON CHILLER AND
 INSTALLING NEW BALANCING & BUTTERFLY VALVES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-24 Cont ID  
Sent By tgordon Date 2008-07-24 Time 13:42 Rev Time 0.40
Received By tgordon Date 2008-07-24 Time 13:42 Sent To  
Notes
2008-07-24 13:48:43MECHANICAL PLAN ME5 SHOWS INSTALLING TWO NEW CHILLED
 WATER PUMPS FOR THE EXISTING 100 TON CHILLER AND
 INSTALLING NEW BALANCING & BUTTERFLY VALVES.

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 10:29 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 10:29 Sent To  
Notes
2008-08-04 10:32:21NOTE: THERE IS NO PROPOSED PLUMBING WORK BEING
 INDICATED ON THE PLANS AND THERE IS NO PLUMBING PERMIT
 THAT HAS BEEN APPLIED FOR. *MRPERSON

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By mflis Date 2008-10-14 Time 13:35 Rev Time 0.00
Received By mflis Date 2008-10-14 Time 13:35 Sent To  
Notes
2008-10-14 13:40:13ZONING REVIEW: PASSED
  
 ** WINDOWS SHALL BE NON-REFLECTIVE, LIGHT TINTED GLASS
 ** SIGNAGE NOT INCLUDED, AND SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT
  
 ANA MARIA APONTE - 822-1439

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-29 Cont ID  
Sent By aaponte Date 2008-07-29 Time 15:39 Rev Time 0.00
Received By aaponte Date 2008-07-29 Time 15:38 Sent To  
Notes
2008-07-29 15:39:28SIGNAGE AND AWNINGS NOT INCLUDED WITH THIS PERMIT


Account Summary | Usage Policy | Privacy Policy