Plan Review Details - Permit 08070446
Plan Review Stops For Permit 08070446
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-25 Cont ID  
Sent By jgomez Date 2008-07-25 Time 15:54 Rev Time 0.00
Received By jgomez Date 2008-07-25 Time 15:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-25 Cont ID  
Sent By jgomez Date 2008-07-25 Time 13:03 Rev Time 0.00
Received By jgomez Date 2008-07-25 Time 12:56 Sent To  
Notes
2008-07-25 13:14:31RESIDENTIAL SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- A) CLEARLY IDENTIFYSHUTTER MOUNTING CONDITIONS AT
 TOP AT BOTTOM OF EACH OPENING TO VERIFY COMPLIANCE WITH
 THE MINIMUM PANEL SPANS SIZE AS REQUIRED BY TABLE T3 ON
 SHEET 3 OF DRAWING 05-AAS-0001 SUBMITTED.
  
 B) CLEARLY IDENTIFY WHICH CLOSURE IS USED TO CONFORM
 TONOTE #5 OF TABLE T3 OFDRAWING 05-AAS-0001.
  
 C) OPENING #2 DOESN'T COMPLY WITH TABLE T3 OR NOTE #5
 OF TABLE T3.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By jgomez Date 2008-07-17 Time 15:07 Rev Time 0.00
Received By jgomez Date 2008-07-17 Time 15:07 Sent To PC
Notes
2008-07-17 15:46:27RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULE SUBMITTED CALLS FOROPENING
 #2 TO HAVECONNECTION TYPE"C1"ON TOP AND
 CONNECTION TYPE"C4"AT BOTTOM.ACCORDING TOPAGES
 4 AND 5 OFSHUTTERS DRAWING 05-AAS-0001 SUBMITTED
 CONNECTION TYPE"C4' IS NOT ALLOWED FOR CONNECTOR TYPE
 CIRCLED ON THE ANCHORSPACING TABLE. REVISE AS
 REQUIRED.
  
 2- ANCHOR TYPE SPECIFIED ON INSTALLATION SCHEDULE
 DOESN'T MATCHANCHOR TYPE CIRCLED ON THE ANCHOR
 SPACING TABLES ON SHEETS 4 AND 5OF DRAWING
 05-AAS-0001.REVISE AS REQUIRED TO MATCH.
  
 3-PANEL SPAN FOR OPENINGS #S 1,3, 4,7,9, 11 AND
 12 DON'T COMPLY WITHTABLE T3 OF SHEET 3 OF DRAWING
 05-AAS-0001 SUBMITTED.THE MINIMUM ALLOWABLE PANEL
 SIZEMUST BE MET TO COMPLY WITH THIS TABLE. REVISE AS
 REQUIRED.
  
 4- SHUTTER SPAN SIZE SHOWN ON INSTALLATION SCHEDULE
 SUBMITTED CAN'T NOT BE THE SAME SIZE AS THE OPENING.
 PANEL SPAN MUST BE LARGER IN ORDER TO PROVIDE THE
 MINIMUM EDGE DISTANCE.ALSO,STUCCO THICKNESS MUST BE
 CONSIDERED BECAUSE THE EDGE DISTANCE IS FOR THE ACTUAL
 FRAMING MEMBER EXCLUDING THE STUCCO THICKNESS. REVISE
 ASREQUIRED.
  
 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 WAS TOO LOW.PERMIT VALUATION WAS UPDATEDTO $2,553
 AS REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC
 2004.THEREFORE OWES #1.06 FOR UPDATED VALUATION.
  
 6- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13OF FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-07-15 Cont ID  
Sent By ssherman Date 2008-07-15 Time 14:08 Rev Time 0.00
Received By ssherman Date 2008-07-15 Time 14:08 Sent To  
Notes
2008-07-15 14:08:23HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-17 Cont ID  
Sent By jgomez Date 2008-07-17 Time 15:52 Rev Time 0.00
Received By jgomez Date 2008-07-17 Time 15:07 Sent To  
Notes
***NONE***