Plan Review Details - Permit 08070387
Plan Review Stops For Permit 08070387
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-08 Cont ID  
Sent By shill Date 2008-08-08 Time 15:53 Rev Time 0.00
Received By shill Date 2008-08-08 Time 15:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By shill Date 2008-07-22 Time 16:06 Rev Time 0.00
Received By shill Date 2008-07-22 Time 16:06 Sent To  
Notes
2008-07-22 16:08:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.SEE OPENING 4, SPAN NOT CORRECT.A 77" OPENING,
 WALL MOUNT, WITH 3 1/2" EDGE DISTANCE SHOULD HAVE A
 SPAN OF 84".REVISE.CHECK ALL.
  
 2.CEILING MOUNT 5 IS HIGHLIGHTED, NOT SPECIFIED.IT
 IS NOT REQUIRED TO MARK THE PRODUCT APPROVAL BUT IF YOU
 DO, IT MUST CORRELATE WITH THE INSTALLATION SCHEDULE
 AND THIS JOB.
  
 3.SEE OPENING 1.FLOOR MOUNT 6 REQUIRES CONCRETE
 SUBSTRATE, SEE PRODUCT APPROVAL PAGE 11.
  
 4.#3 IS SPECIFIED FOR MOUNTING TYPE, #1 HIGHLIGHTED.
 #1 REQUIRES CONCRETE SUBSTRATE.CLARIFY.
  
 5.TWO COMPLETE SETS REQUIRED.ONLY ONE INSTALLATION
 SCHEDULE SUBMITTED.THE PERMIT CANNOT BE ISSUED
 WITHOUT TWO COMPLETE SETS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 08:54 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 08:54 Sent To B
Notes
2008-07-30 08:54:39TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By shill Date 2008-07-22 Time 16:08 Rev Time 0.00
Received By shill Date 2008-07-15 Time 08:39 Sent To  
Notes
2008-07-15 08:39:47TO "MISC" BOX#1