Plan Review Details - Permit 08070272
Plan Review Stops For Permit 08070272
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By jgomez Date 2008-07-23 Time 16:59 Rev Time 0.00
Received By jgomez Date 2008-07-23 Time 16:59 Sent To PC
Notes
2008-07-24 11:35:27RESIDENTIAL(R3)ADDITION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-A) PROPERTY IS LOCATED ON FLOOD ZONE A5WITH BASE
 FLOOD ELEVATION OF 7'. IF EXISTING HOUSE AND
 PROPOSED ADDITION FINISH FLOOR ELEVATION IS LESS THAN
 7'-6", THEN THE HOUSE NEEDS TO BE RAISED AS REQUIRED BY
 CITY ORDINANCESEC. 94-546(A) AND (B).PROVIDE
 SURVEY OR ANY OTHERDOCUMENT SHOWING EXISTING FINISH
 FLOOR ELEVATION TO VERIFY COMPLIANCE WITH THIS CODE
 ORDINANCE.
  
 B) PROPOSED PLANS NEED TO SHOW THE PROPOSED FINISH
 FLOOR ELEVATION TO SHOW COMPLIANCE WITH THIS CITY
 ORDINANCE.
  
 2- SHEET #1:
 A) SPECIFYATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: COORDINATELOADS WITH TRUSS ENGINEER. SEE
 TRUSS PACKAGE.EG: PROJECT NOTES CALL FOR 30PSF ROOF
 LIVE LOAD. COORDINATE AND REVISE AS REQUIRED.
  
 B) ENTRY PORCH FOUNDATION PLAN: SPECIFY HOW MUCH
 EMBEDMENT IS REQUIRED FOR ANCHOR BOLTSAT BASE OF
 STEEL COLUMN. SEC.106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH UPLIFT LOADS SEC. R301 2004
 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE LEVEL ALTERATION TYPE SHOWN ON PROJECT
 NOTES. SEECHAPTER 3 OF THE EXISTING BUILDING CODE
 2004TO VIEW SCOPE OF WORK AND REVISE AS REQUIRED.
  
 3- SHEET #2:
 A) PROVIDE ATTIC ACCESSFOR NEW ADDITION AS
 REQUIRED BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) SPECIFY SIZE OF NEW ATTIC ACCESSWITH DROP
 LADDER TO VERIFY COMPLIANCE WITH SEC. R807.
  
 4- SHEET#3, TYPICAL WALL SECTION:
 A)REVISE ROOF SHEATHING FASTENING OPTION FOR ROOF
 ZONE #3 AS REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) CLEARLY SPECIFY ROOF TILE FASTENING AS REQUIRED
 BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. ***NOTE:
 COORDINATE WITH PRODUCT APPROVAL SUBMITTED. SEE SHEET
 12 OF NOA 07-1129.04 SUBMITTED AND REVISE INFORMATION
 ON WALL SECTION AS REQUIRED.
  
 D) INDICATE LINE OF GRADE TO VERIFY COMPLIANCE WITH
 FOOTING MINIMUM DEPTH SEC. R403.1.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SHEET #4: SPECIFY SIZE OF STEEL CORNER BUCKET FOR
 STEEL COLUMNS.
  
 6- OWES #5.90 FOR RADON FEES.
  
 7- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 *** NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK
 UP.
  
 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BYSEC.
 13-101.2 FBC 2004.
 NOTE: MAKE SURE CORRECT REVISED FORM IS USED TO AVOID
 DELAYS OR CONFLICTS.
  
 9- SOIL TEST REPORT SUBMITTED:
 A) NEEDS TO HAVE ENGINEER'S ORIGINAL SIGNATURE (NO
 COPY) AS REQUIRED BY SEC. 61G15-23.002 (1) OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 B) NEEDS TO HAVE THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002(2). FLORIDA ADMINISTRATIVE CODE.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) WINDOW MULLIONS.AND CLEARLY MARKSPECIFIC
 MULLION SIZE AND FASTENERS TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES OF SEC.
 R301.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE WHERE CONNECTOR IS LOCATED. NO NEED TO
 SUBMIT COMPLETE PRODUCT APPROVAL REPORT.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCTAPPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 NOTE: SEPARATE LETTER SUBMITTED BY THE ENGINEER IS
 INCOMPLETE. IT'SNO LISTING ALL PRODUCT APPROVALS AND
 IS NOT LISTING THE SPECIFIC FLORIDAPRODUCT APPROVAL
 OR NOANUMBER REVIEWED.
  
 12- TRUSS PACKAGE:
 A) INDEX SHEET DOESN'TCOMPLY WITH THE REQUIREMENTS
 OF SEC. 61G15-31.003.THE NAME OF THE ENGINEER OF
 RECORD IS NOT SHOWN AND ALL INDIVIDUAL TRUSSES NEED TO
 HAVE THE TRUSS ENGINEER NAME AND INFORMATION. REVISE AS
 REQUIRED.
  
 B) TRUSS PACKAGE NEEDS TO BE REVIEWED BY THE
 ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 C) PROVIDE ONLY 2 COMPLETE COPIES WITH ORIGINAL SEAL
 AND SIGNATURE.(FOUR COPIES WHERE SUBMITTED AND TWO OF
 THOSE HAD NO ORIGINAL SIGNATURE).
  
  
 ***NOTE: PLEASE RESUBMIT PAGES WITH PALM BEACH COUNTY
 IMPACT FEES STAMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-11 Cont ID  
Sent By btrobaug Date 2008-07-11 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2008-07-11 Time 13:34 Sent To Z
Notes
2008-07-11 14:17:18 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. ONLY ONE SET IS SIGNED AND SEALED.
  
 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED.***LOCATE ON THE
 PLAN.
  
 3} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLANIF
 APPLICABLE.NOTE: MAY BE COMBINATION SMOKE/CARBON
 MONOXIDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 14:08 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 14:08 Sent To E
Notes
2008-07-18 14:08:26TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-23 Cont ID  
Sent By jgomez Date 2008-07-23 Time 16:59 Rev Time 0.00
Received By jgomez Date 2008-07-10 Time 08:27 Sent To  
Notes
2008-07-10 08:30:15TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-18 Cont ID  
Sent By tgordon Date 2008-07-18 Time 16:19 Rev Time 0.30
Received By tgordon Date 2008-07-18 Time 16:19 Sent To B
Notes
2008-07-18 16:20:28NO MECHANICAL WORK TO BE DONE. NO MECHANICAL PLANS
 SUBMITTED, AND NO MECHANICAL PERMIT NUMBER APPLIED FOR
 AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-16 Cont ID  
Sent By kdfreema Date 2008-07-16 Time 13:24 Rev Time 0.00
Received By kdfreema Date 2008-07-16 Time 13:24 Sent To  
Notes
***NONE***