Plan Review Details - Permit 08070262
Plan Review Stops For Permit 08070262
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 08:47 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 08:47 Sent To Z
Notes
2008-08-13 08:47:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 09:03 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 09:03 Sent To M
Notes
2008-07-22 09:03:39TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-16 Cont ID  
Sent By adarroug Date 2008-07-16 Time 12:15 Rev Time 0.00
Received By adarroug Date 2008-07-16 Time 12:15 Sent To M
Notes
2008-07-16 12:15:43TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-11 Cont ID  
Sent By tgordon Date 2008-07-11 Time 09:34 Rev Time 0.00
Received By tgordon Date 2008-07-10 Time 11:03 Sent To  
Notes
2008-07-10 11:04:01TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By tgordon Date 2008-07-22 Time 15:51 Rev Time 0.30
Received By tgordon Date 2008-07-22 Time 15:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-11 Cont ID  
Sent By tgordon Date 2008-07-11 Time 09:24 Rev Time 0.40
Received By tgordon Date 2008-07-11 Time 09:24 Sent To  
Notes
2008-07-11 09:32:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW THE SIZE OF THE SUPPLY AIR TRUNK LINE ON
 PLAN, PER 2004 FBC 106.3.5.
  
 2) SHOW ON PLANS HOW THE AIR IS RETURNING TO THE AIR
 HANDLER UNIT, IF GRILL SHOW GRILL SIZES, PER 2004 FBC/M
 601.4.
  
 3) SHOW ON PLANS THE OUTDOOR AIR CALCULATIONS AND HOW
 MUCH OUTDOOR AIR IS TO BE PROVIDED, PER 2004 FBC/M
 403.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By mcruz Date 2008-08-21 Time 12:39 Rev Time 0.00
Received By mcruz Date 2008-08-21 Time 12:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By mcruz Date 2008-07-31 Time 11:28 Rev Time 0.00
Received By mcruz Date 2008-07-31 Time 11:28 Sent To M
Notes
2008-07-31 12:00:28***ZONING FAILED PER LMF***
  
 1.INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2.INDICATE THE DIMENSIONS OF THE A/C EQUIPMENT ON THE
 SURVEY.
  
 3.PURSUANT TO SECTION 94-444(B), MECHANICAL SYSTEMS
 SHALL BE SCREENED FROM VIEW BY LANDSCAPING OR BUILT
 ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE BUILDING
 ARCHITECTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved