Plan Review Details - Permit 08070213
Plan Review Stops For Permit 08070213
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-10 Time 08:28 Rev Time 0.00
Received By btrobaug Date 2008-07-10 Time 08:24 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 10:33 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 09:00 Sent To I
Notes
2008-07-08 10:32:46 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE ARE NINE BAYS WITH PANELS SHOWN ON THE FLOOR
 PLAN, ONLY EIGHT PANELS SHOWN ON THE RISER DIAGRAM. SEE
 240.24(B). PLEASE CORRELATE SAME.
  
 2} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. THERE ARE TWO OVERHEAD SERVICES SHOWN
 WHICH IS IN VIOLATION OF THIS ARTICLE.SEE 230.40
 EXCEPTION #2 AND INDICATE IF THAT EXCEPTION APPLIES.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.NOTE #2 IN THE ELECTRICAL SPECIFICATIONS
 REFERENCING THE LATEST EDITION OF THE NEC, WHICH IS
 2008, IS INCORRECT.THE 2005 NEC WAS ADOPTED BY THE
 FLORIDA LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE
 APPLICATION FOR THIS PROJECT WAS AFTER THAT DATE AND
 THE PLANS ARE SUBJECT TO THAT CODE. PLEASE CHANGE ALL
 NOTES TO REFLECT THIS CHANGE.
  
 4} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 5} THE FLOOR PLAN LOCATES THE EXISTING ELECTRICAL
 SERVICE, INDICATE IF THE NEW SERVICE IS TO BE INSTALLED
 IN THE SAME LOCATION.
  
 6} THE SCOPE OF WORK ON THE APPLICATION INDICATES NEW
 PANELS IN BAY'S 2 AND 6. PANELS "B" AND "F" WHICH SERVE
 THOSE BAYS ARE MARKED "EX SERVICE" ON THE PLAN, PLEASE
 CLARIFY.
  
 7} ALL THE PANELS ON THE FLOOR PLAN ARE MARKED PANEL
 "A", CORRELATE WITH THE RISER DIAGRAM.
  
 8} VERIFY THAT THE 3/0 FEEDERS SHOWN FOR 150 AMP LOADS
 ARE CORRECT, ALSO VERIFY THE #2 EQUIPMENT GROUND IS
 INTENDED TO BE RAN TO PANEL "F", ALTHOUGH NOT A
 VIOLATION IF IT IS REQUIRED BY THE ENGINEER ON THE PLAN
 IT MUST BE INSTALLED IN THE FIELD OR A REVISION IS
 REQUIRED IF CHANGED AT A LATER DATE. SEE 250.66 FOR
 REQUIRED SIZE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-10 Time 08:24 Rev Time 0.00
Received By btrobaug Date 2008-07-10 Time 08:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 10:33 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 09:00 Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved