Plan Review Details - Permit 08070195
Plan Review Stops For Permit 08070195
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-05-20 Cont ID  
Sent By shill Date 2009-05-19 Time 10:45 Rev Time 0.00
Received By shill Date 2009-05-20 Time 13:29 Sent To  
Notes
2009-05-19 10:55:21PENDING VALUATION
  
 ***PROVISO***
  
 REVISE PLAN TO ADDRESS FBC2110.4.1 (GLASS BLOCK)
  
 REVISE PLAN TO CLARIFY WOOD OR METAL FOR PARTITION
 WALLS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-05-19 Cont ID  
Sent By shill Date 2009-05-19 Time 10:08 Rev Time 0.00
Received By shill Date 2009-05-19 Time 10:08 Sent To  
Notes
2009-05-19 10:11:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEETS D1, A2, A3 ARE NOT IN THE RESUBMITTED SET.
 SEE FBC*106, MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. BASED ON PREVIOUS COMMENTS, THE
 EXISTING FLOOR PLAN AND ELEVATIONS WERE CONTAINED IN
 THESE SHEETS. PLEASE PROVIDE THE MISSING PLAN SHEETS.
  
 2. SEE PREVIOUS LISTS, ITEMS 7 AND 12. A4, "GLASS BLK
 DETAIL" STATES "NON BEARING" BUT NO INFORMATION SHOWN
 AS TO HOW GRAVITY LOADS WILL BE PREVENTED FROM BEARING
 ON THE GLASS BLOCK, FBC2110.4.1. PLEASE EXPLAIN HOW
 THIS IS NON BEARING WHEN THE DETAIL SHOWS CONCRETE
 BLOCK ON TOP OF GLASS BLOCK.
  
 3. THERE IS A DETAIL ON SHEET A4 MARKED A-A3 LABELED
 "TYPICAL 4" PARTITION." THIS SPECIFIES WOOD, SHEET A1
 SPECIFIES METAL PARTITION WALLS. FBC*106, DETAILS
 SHOULD INCLUDE ENOUGH CONSISTENT INFORMATION TO
 DETERMINE SCOPE OF WORK.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-30 Cont ID  
Sent By btrobaug Date 2009-03-18 Time 17:22 Rev Time 0.00
Received By mjacobs Date 2008-12-30 Time 13:07 Sent To  
Notes
2008-12-30 13:07:46 
  
 BUILDING PLAN REVIEW
 PERMIT: 08070195
 ADD: 2000 6 AE ISAACS AVE
 CONT: NEWBOLD CONST.
 TEL: (561)842-0033
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS0
  
 12-29-08
 REVIEW: 2ND
 ACTION: DENIED
  
 **NOTE: SHEET D1 WHICH SHOWED THE EXISTING FLOOR PLAN
 AND ALL AREAS TO BE DEMOED WAS NOT RESUBMITTED ALONG
 WITH SHEET A2. AN EXISTING AND A PROPOSED PLAN ARE
 REQUIRED TO SHOW ALL CHANGES TO THE LAYOUT OF THE
 EXISTING BUILDING.**
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
 3) OK
 4) OK
 5) OK
  
 6) SHEET A1 SHOWS TWO NEW WINDOW OPENINGS AT THE NORTH
 ELEVATION, HOWEVER SHEET A2 SHOWS THREE WINDOWS. WILL
 THERE BE THREE OR TWO WINDOWS. THE SOUTH ELEVATION ON
 SHEET D1- A1 AND A2 HAVE CONFLICTING INFORMATION AS TO
 HOW MANY WINDOWS WILL BE CHANGED OUT. WHAT TYPES OF
 WINDOWS ARE INSTALLED AT THIS LOCATION? REMEMBER AN
 EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE
 ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR
 ENERGY EFFICIENT THAN ITS EXISTING CONDITION. FBC
 (EXISTING) 501.2.
  
 **NO RESPONSE NOT ADDRESSED**
 7) 106.3.3* PRODUCT APPROVALS- 2004THOSE PRODUCTS THAT
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR THE NEW GLASS BLOCK. SHEET A4 GLASS BLOCK
 DETAIL FAILS TO STATE THE TYPE OF GLASS UNIT, THE SIZE,
 THE LATERAL AND VERTICAL SUPPORT. THE HEADER ABOVE THE
 GLASS UNITS SHOWS A BLOCK WALL. GLASS UNIT MASONRY
 PANELS SHALL BE ISOLATED SO THAT IN-PLANE LOADS ARE NOT
 IMPARTED ON THE UNITS FBC 2110.4.1. THE DETAIL SHALL
 STATE THE VERTICAL AND LATERAL SUPPORTS FBC 2110.4.3.
 PLEASE SEE SECTION 2110.7 FOR INFORMATION REGARDING THE
 REINFORCEMENT OF THE GLASS UNITS. FOR ADDITIONAL
 INFORMATION SEE SECTION FBC 2110. IF THE GLASS BLOCK
 UNITS ARE NOT IMPACT RESISTANT, IMPACT PROTECTION SHALL
 BE PROVIDED FBC 1609.1.4. PROVIDE PRODUCT APPROVAL FOR
 THE HURRICANE PROTECTION (SHUTTERS).
  
 8) OK
  
 **NO RESPONSE NOT ADDRESSED**
 9) SHEET A1, THE WALL LEGEND INDICATES THAT A PORTION
 OF THE EXISTING STRUCTURE WILL BE CONSTRUCTED WITH 4
 INCH WOOD STUDS; IF THAT IS THE CASE INDICATE THE
 EXTERIOR WALL COVERINGS WITH A COMPLETE ELEVATION WALL
 DETAIL SHOWING ALL MATERIALS. THE WALL LEGEND HAS NO
 SYMBOL FOR THE NEW CONSTRUCTED WALLS. IF SOME WALLS ARE
 DIFFERENT IN SIZE LIKE THE ONE SEPARATING THE BATHROOMS
 AT THE DRESSING ROOMS; INDICATE THE SIZE OF THE WALL
 AND THE MATERIALS TO BE USED ON THE WALL DETAIL SHEET
 A3. ADDITIONAL INFORMATION IS REQUIRED 106.1.2
  
 **SEE THE CODE SECTIONS MENTION BELOW AND SHOW
 COMPLIANCE**
 10) THE ACCESSIBLE BATHROOMS NEED TO BE IN COMPLIANCE
 WITH SECTION FBC 11-4.16 / 11-4.17 / 11-4.18 AND
 11-4.19. THE GRAB RAILS FOR THE BATHROOM SHOWN ON THE
 FLOOR PLAN DO NOT MATCH THE ONE ON THE DETAIL SHEET.
 SEE NOTES ON PLANS AND MAKE THE REQUIRED CHANGES.
  
 **NOTED; HOWEVER, THE NEW DETAIL ON SHEET A1 FOR THE
 STAIRS FAIL TO CLEARLY SHOW THE RISE AND TREAD DEPTH OF
 THE STAIRS...
 11) SHEET D1 INDICATES THE ALTERATION TO THE EXISTING
 EXTERIOR STAIRS AT THE SOUTH ELEVATION; HOWEVER, NO
 CONSTRUCTION DETAIL IS PROVIDED SHOWING THE SIZE OF THE
 TREADS AND RISERS. THE STAIRS SHALL BE IN COMPLIANCE
 WITH FBC 1009 AND 11-4.9. SHEET A3 SOUTH ELEVATION
 HANDRAIL SHALL BE IN CONFORMANCE WITH FBC 1012.3, SUCH
 THAT A 4 INCH DIAMETER SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES. SHOW THE DIMENSION
 BETWEEN THE LANDING AND THE BOTTOM OF THE RAIL.
  
 **NO RESPONSE NOT ADDRESSED**
 12) THE DRAWINGS NEED TO SHOW THE HEAD AND SILL DETAIL
 FOR THE NEW OPENINGS. PROVIDE THE FRONT ELEVATION
 DETAIL FOR THE NEW OPENINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By mjacobs Date 2008-08-14 Time 12:03 Rev Time 0.00
Received By mjacobs Date 2008-08-11 Time 10:29 Sent To PC
Notes
2008-08-12 10:57:39 
 BUILDING PLAN REVIEW
 PERMIT: 08070195
 ADD: 2000 6 AE ISAACS AVE
 CONT: NEWBOLD CONST.
 TEL: (561)842-0033
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) SHEET C1. THE OCCUPANCY USE OF THE BUILDING
 INDICATED ON THE DRAWINGS IS BUSINESS, HOWEVER,
 ACCORDING TO THE USED INDICATED ON THE DRAWINGS THE
 OCCUPANCY OF THE BUILDING WILL FALL UNDER THE CATEGORY
 OF A-3. SEE FBC 303.
  
 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6) SHEET A1 SHOWS TWO NEW WINDOW OPENINGS AT THE NORTH
 ELEVATION, HOWEVER SHEET A2 SHOWS THREE WINDOWS. WILL
 THERE BE THREE OR TWO WINDOWS. THE SOUTH ELEVATION ON
 SHEET D1- A1 AND A2 HAVE CONFLICTING INFORMATION AS TO
 HOW MANY WINDOWS WILL BE CHANGED OUT. WHAT TYPES OF
 WINDOWS ARE INSTALLED AT THIS LOCATION? REMEMBER AN
 EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE
 ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR
 ENERGY EFFICIENT THAN ITS EXISTING CONDITION. FBC
 (EXISTING) 501.2.
  
 7) 106.3.3* PRODUCT APPROVALS- 2004THOSE PRODUCTS THAT
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR THE NEW GLASS BLOCK.
  
 8) IS THE BUILDING TRULY A 4 STORY BUILDING AS STATED
 SHEET C1? INDICATE THE OCCUPANT LOAD OF THE BUILDING ON
 THE PLANS PER FBC 1004 AND TABLE 1004.1.2.
  
 9) SHEET A1, THE WALL LEGEND INDICATES THAT A PORTION
 OF THE EXISTING STRUCTURE WILL BE CONSTRUCTED WITH 4?
 WOOD STUDS; IF THAT IS THE CASE INDICATE THE EXTERIOR
 WALL COVERINGS WITH A COMPLETE ELEVATION WALL DETAIL
 SHOWING ALL MATERIALS. THE WALL LEGEND HAS NO SYMBOL
 FOR THE NEW CONSTRUCTED WALLS. IF SOME WALLS ARE
 DIFFERENT IN SIZE LIKE THE ONE SEPARATING THE BATHROOMS
 AT THE DRESSING ROOMS; INDICATE THE SIZE OF THE WALL
 AND THE MATERIALS TO BE USED ON THE WALL DETAIL SHEET
 A3. ADDITIONAL INFORMATION IS REQUIRED 106.1.2
  
 10) THE ACCESSIBLE BATHROOMS NEEDS TO BE IN COMPLIANCE
 WITH SECTION FBC 11-4.16 ? 11-4.17 ? 11-4.18 AND
 11-4.19. THE GRAB RAILS FOR THE BATHROOM SHOWN ON THE
 FLOOR PLAN DO NOT MATCH THE ONE ON THE DETAIL SHEET.
 SEE NOTES ON PLANS AND MAKE THE REQUIRED CHANGES.
  
 11) SHEET D1 INDICATES THE ALTERATION TO THE EXISTING
 EXTERIOR STAIRS AT THE SOUTH ELEVATION; HOWEVER, NO
 CONSTRUCTION DETAIL IS PROVIDED SHOWING THE SIZE OF THE
 TREADS AND RISERS. THE STAIRS SHALL BE IN COMPLIANCE
 WITH FBC 1009 AND 11-4.9.
  
 12) THE DRAWINGS NEED TO SHOW THE HEAD AND SILL DETAIL
 FOR THE NEW OPENINGS. PROVIDE THE FRONT ELEVATION
 DETAIL FOR THE NEW OPENINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-08 Cont ID  
Sent By btrobaug Date 2009-05-08 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2009-05-08 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-08 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 09:21 Rev Time 0.00
Received By btrobaug Date 2009-01-07 Time 13:34 Sent To  
Notes
2009-01-07 15:32:17 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE AIR HANDLING UNITS ON SHEET E1 ARE CALCULATE
 WITH 10KW HEAT STRIPS. SHEET M1 INDICATES THE UNITS ARE
 15KW. CORRELATE SAME. THE CHANGE MUST BE REFLECTED IN
 THE LOAD CALCULATIONS.
  
 2} LIST THE VOLTAGE OF THE SERVICE ON THE RISER
 DIAGRAM. 215.5 NOTE: 240 VOLTS IS LISTED IN THE LOAD
 CALCULATION
  
 3} THE CHAIR LIFT IS CIRCUITED ON 15,16 AT THE DEVICE.
 THOSE CIRCUITS ARE LISTED AS A/C #2 (AS ARE 18, 19, 20)
 IN THE PANEL SCHEDULE.CORRELATE THE CIRCUITING. 408.4
 NEC.
  
 4} THE CHAIR LIFT IS NOT IN THE LOAD CALCULATIONS.
 220.14(A) SPECIFIC APPLIANCES OR LOADS AN OUTLET FOR A
 SPECIFIC APPLIANCE OR OTHER LOAD NOT COVERED IN
 220.14(B) THROUGH (L) SHALL BE CALCULATED BASED ON THE
 AMPERE RATING OF THE APPLIANCE OR LOAD SERVED.
  
 5} ONE WATER HEATER IS LABELED 12,13 AT THE RECEPTACLE
 NOT IN THE SCHEDULE. THE OTHER HEATER IS NOT LABELED.
 408.4
  
 6} CIRCUITS 3, 5, 6, 7, 8 ARE LABELED "RECEPTACLES BUT
 ARE LIGHTING CIRCUITS. CIRCUIT 10 IS LABELED LIGHTING
 AND IS A RECEPTACLE CIRCUIT. CORRECT THE PANEL
 SCHEDULE. 408.4 NEC.
  
 COMMENTS FROM THE PREVIOUS REVIEW WITH COMMENT NUMBER
 FROM SAME.***INDICATES FURTHER EXPLANATION OF PREVIOUS
 COMMENT
  
 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.***THE WALL UNITS ARE NOT CONNECTED TO
 THE LOCAL CIRCUIT PER 700.12(F)(4).
  
 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.*** NO SIGNATURE ON THE PLANS.
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A)
 (3) IF APPLICABLE.*** ONLY ONE AHU IS ON THE PLAN..
 .
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By btrobaug Date 2008-07-21 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2008-07-21 Time 14:41 Sent To  
Notes
2008-07-21 15:31:49 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE IS AN ELECTRICAL SHEET SUBMITTED BUT THE SCOPE
 OF WORK IS NOT CLEAR. INDICATE WHAT WORK IS EXISTING
 (IF ANY) AND WHAT IS TO BE INSTALLED UNDER THIS PERMIT.
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1 FBC,
 PERFORMANCE CALCULATION PROCEDURES. SEE 13-415.2B OR
 13-415.2.C.1 DENSITIES.SUBMIT A LEGEND OF FIXTURE TYPES
 AND WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS
  
 3} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR
 THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE
 BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY
 DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED.
 SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL
 REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS.
  
 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES.106.3.5 FBC.
  
 5} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 9} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.UNDER 471.003 FS THE CONTRACTOR OF RECORD MAY
 DRAW THE DESIGN IF HE IS THE INSTALLER
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A)
 (3) IF APPLIOCABLE..
 .
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-13 Cont ID  
Sent By mwennerg Date 2009-05-13 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2009-05-13 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-01-09 Cont ID  
Sent By mwennerg Date 2009-01-09 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2009-01-09 Time 11:16 Sent To  
Notes
2009-01-09 11:23:53***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING:
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 7) THE EXIT AND EMRGENCY LIGHT LOCATIONS ARE SHOWN IN
 DIFFERENT LOCATIONS ON SHEET LS AND SHEET E1. PLEASE
 CORRELATE INFORMATION TO REFLECT THE ACTUAL LOCATIONS.
  
 AN OCCUPANT LOAD SIGN IS REQUIRED IF NOT EXISTING.
 PLEASE CONTACT THE BUREAU OF FIRE PREVENTION AT (561)
 804-4724 FOR ASSISTANCE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By mwennerg Date 2008-07-18 Time 15:38 Rev Time 0.00
Received By mwennerg Date 2008-07-18 Time 15:38 Sent To  
Notes
2008-07-18 15:42:01***DENIED***
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 3) RATED DOOR TO BE PROVIDED WITH UL LISTED CLOSERS.
 PLEASE ADD TO DOOR SCHEDULE.
  
 4) NOTE ON LS SHEET REFERENCES FIRE EXTINGUISHERS.
 PLEASE SHOW LOCATIONS ON DRAWINGS.
  
 5) PLEASE CLARIFY OCCUPANCY CLASSIFICATION FOR
 BUILDING. PLEASE NOTE THAT MEANS OF EGRESS SHALL COMPLY
 WITH NFPA 101, CHAPTER 7 AND REQUIREMENTS FOR ASSEMBLY
 OCCUPANCIES NOT CHAPTER 38.
  
 6) STAIRS AND RAMPS TO COMPLY WITH NFPA 101, CHAPTER 7.
 SEE SEC. 7.2.5 FOR RAMPS AND 7.2.2 FOR STAIRS.
  
 7) SHOW NEW AND EXISTING ILLUMINATED EXITS SIGN AND
 EMERGENCY LIGHTING FACILITY LOCATIONS.
  
 8) PLEASE INDICATE OCCUPANT LOAD FOR BUILDING USING
 NFPA 101, TABLE 7.3.1.2 FOR CALCULATIONS.
  
 9) IS BUILDING PROTECTED BY FIRE PROTECTION SYSTEMS, IE
 FIRE SPRINKLER AND OR FIRE ALARM?
  
 10) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING IN TERMS OF CLASS A,B OR C.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN RECVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 16:45 Sent To M
Notes
2009-08-07 16:45:26TO RR DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-06 Cont ID  
Sent By shill Date 2009-05-06 Time 11:57 Rev Time 0.00
Received By shill Date 2009-05-06 Time 11:57 Sent To  
Notes
2009-05-06 11:57:26BOB BOARD #18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 10:36 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 10:36 Sent To  
Notes
2008-12-24 10:36:36TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-14 Time   Rev Time  
Received By adarroug Date 2008-07-09 Time 10:59 Sent To  
Notes
2008-07-09 11:03:29TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-08-13 Cont ID  
Sent By rregueir Date 2009-08-13 Time 10:00 Rev Time 0.00
Received By rregueir Date 2009-08-13 Time 09:54 Sent To PC
Notes
2009-08-13 09:54:49REVISED M1 AND M2 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-14 Cont ID  
Sent By rregueir Date 2009-05-14 Time 10:20 Rev Time 0.00
Received By rregueir Date 2009-05-14 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 17:51 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 17:32 Sent To PC
Notes
2009-01-10 17:51:53REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE EQUIPMENT SCHEDULE ON THE PLANS INDICATES THE
 SYSTEMS ARE "13 SEER." THIS IS NOT POSSIBLE AS SYSTEMS
 OF THIS SIZE ARE NOT GIVEN A "SEER" RATING. THE
 DOCUMENTATION PROVIDED FOR THE SELECTED EQUIPMENT
 INDICATES THAT THE EFFICIENCY RATING IS 9.1 EER.
 HOWEVER, PLANS INDICATE 7.5 TON SYSTEMS WHILE THE
 MANUFACTURER'S DATA IS FOR A 10 TON SYSTEM. PLEASE
 COORDINATE EQUIPMENT SCHEDULE, EFFICIENCY RATING AND
 THE DOCUMENTATION PROVIDED TO DEMONSTRATE CODE
 COMPLIANCE.
  
 2. ELECTRICAL PLANS INDICATE THAT THE A/C UNITS ARE
 EXISTING WHILE MECHANICAL DOCUMENTATION INDICATES THAT
 AC UNITS ARE NEW. ALSO, ELECTRICAL PLAN SHOWS ONE AHU
 AND ONE CU IN DIFFERENT LOCATIONS THAN THE MECHANICAL
 PLANS. PLEASE COORDINATE ELECTRICAL PLANS AND
 MECHANICAL PLANS IN ACCORDANCE WITH FBCB 106.1.1.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION AND OCCUPANT LOADS AS
 INDICATED IN FBCM TABLE 403.3. SHOW THE TOTAL REQUIRED
 CFM FOR EACH SYSTEM. ALSO, PROVIDE SHUTOFF DAMPER
 CONTROLS FOR THE OUTSIDE AIR DUCTS IN ACCORDANCE WITH
 FBCB 13-409.1.ABC.3.2.
  
 4. THE TWO RESTROOMS ON THE NORTH END OF THE SPACE ARE
 SHOWN WITH 50 CFM EXHAUST FANS. THE MINIMUM REQUIRED
 EXHAUST FOR THESE ROOMS IS 50 CFM PER WATER CLOSET OR
 URINAL IN ACCORDANCE WITH FBCM TABLE 403.3. THAT MEANS
 A MINIMUM OF 150 CFM IS REQUIRED FOR EACH RESTROOM.
  
 5. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
 PROVIDE DETAIL WITH WIND LOAD CALCULATIONS FOR THE
 OUTDOOR INSTALLATION OF NEW CONDENSING UNITS SHOWING
 HOW THESE UNITS ARE TO BE INSTALLED TO RESIST
 ANTICIPATED WIND PRESSURES.
  
 6. EACH OF THE PROPOSED AC SYSTEMS IS DESIGNED TO
 PROVIDE IN EXCESS OF 2000 CFM. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM IN THE SUPPLY AIR DUCT IN
 ACCORDANCE WITH FBCM 606.2.1.
  
 7. ACCORDING TO PAGE C1 THIS BUILDING IS DESIGNED AND
 INTENDED FOR AN OCCUPANCY OF 195 PERSONS. THIS MEANS
 THE AIR CONDITIONING SYSTEM MUST BE DESIGNED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH FLORIDA
 STATUTE 471.003(2)(H)(C). THIS PROJECT DOES NOT QUALIFY
 FOR THE EXCEPTION ALLOWING THE CONTRACTOR TO ACT AS THE
 DESIGNER. PLEASE PROVIDE PLANS DESIGNED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH THIS STATUTE
 AND FBCB 105.3.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-10 Cont ID  
Sent By tgordon Date 2008-07-10 Time 08:40 Rev Time 0.45
Received By tgordon Date 2008-07-10 Time 08:40 Sent To  
Notes
2008-07-10 09:22:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MEN BATH #103 AND WOMEN BATH #106 REQUIRE
 EXHAUST FANS, PER 2004 FBC/M 402.3.1 AND TABLE 403.3.
 PLEASE CORRECT. (SHOW ON MECHANICAL PLAN WITH CFM'S.)
  
 2) PLEASE SHOW ON MECHANICAL PLANS ALL THE SUPPLY AND
 RETURN AIR DUCT SIZES, PER 2004 FBC 106.3.5 (IF
 EXISTING PLEASE LABEL AS EXISTING).
  
 3) SHOW ON MECHANICAL PLAN HOW THE AIR IN THE MAIN HALL
 IS RETURNING TO THE AIR HANDLER UNITS, PER 2004 FBC/M
 601.4.
  
 4) IF THE AIR HANDLER UNITS ARE EXISTING PLEASE LABEL
 AS EXISTING, IF NEW PROVIDE REQUIRED INFORMATION WITH
 EQUIPMENT SCHEDULE, AND SHOW THE LOCATION OF THE
 CONDENSER UNITS, PER 2004 FBC 106.3.5.
  
 5) SHOW THE BATHROOM EXHAUST FANS (WITH CFM'S) FOR MEN
 BATH #109 AND WOMEN BATH #110 ON THE MECHANICAL PLAN,
 PER 2004 FBC/M 402.3.1 AND TABLE 403.3.
  
 6) MECHANICAL PLAN M1 HAS A PLUMBING RISER DIAGRAM ON
 IT, ROLAND'S A/C IS NOT A LICENSED PLUMBING CONTRACTOR
 AND MAY NOT DESIGN PLUMBING RISERS. SEE F.S 471.003
 (H). PLEASE REMOVE FROM MECHANICAL PLAN.
  
 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTORS LICENSE NUMBER ON THEM, SEE W.P.B. AMEND.
 106.1.3.
  
 *** BE ADVISED THE MECHANICAL CONTRACTOR WILL NEED TO
 SIGN ON FOR THE MECHANICAL PERMIT BEFOR THE MECHANICAL
 PLANS PASS REVIEW AS HE IS THE DESIGNER, SEE FS 471.003
 (H).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-05-12 Cont ID  
Sent By kstevens Date 2009-05-12 Time 14:38 Rev Time 0.00
Received By kstevens Date 2009-05-12 Time 14:38 Sent To  
Notes
2009-05-12 14:48:49PASSED/PROVISO:
  
 SHT A1 - THE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL FROM THE DOOR. REVISIONS REQUIRED. --
 THE MEASUREMENT FROM THE FLOOR TO THE SPOUT OF THE
 DRINKING FOUNTAIN IS 36" MAXIMUM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 07:19 Rev Time 0.00
Received By kstevens Date 2009-01-08 Time 14:25 Sent To  
Notes
2009-01-09 09:39:43PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 ***FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY
 INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR
 PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. OK
 6. OK
  
 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER FBC-
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.17.3.
 (1) THE STANDARD RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAT 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 (SEE FIGURE 30(A) AND FIGURE 30(E) AND TO
 COMPLY WITH SECTION 11-4,19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 8. SHEET A3 (NOW A4) HC LAV. BATH PLAN VIEW DETAIL:
 PLEASE CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS
 WITH THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL
 BE 1'6" AND THE LAVATORY SHALL BE 1'5". PER FBC-
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.16.2 FOR THE WATER CLOSET AND SECTION 11-4.19.3
 CLEAR FLOOR SPACE. ALSO PLEASE PROVIDE THE FOLOWING
 INFORMATION ON THE ELEVATION DETAILS AND SHEET A1
 PROPOSED FLOOR PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE
 FOLLOWING INFORMATION AND CLEAR FLOOR SPACES NEEDS TO
 BE INDICATED ON SHEET A1).
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5
 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR
 SAPCE TO BE INDICATED ON SHEET A1).
 11-4.19.3 CLEAR FLOOR SPACE. 30" X 48" SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32).
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 ****NO RESPONSE, CLEAR FLOOR SPACE FOR THE W/C'S AND
 THE LAVS AS WELL AS THE LAV FAUCET REQUIREMENTS WERE
 NOT ADDRESSED.
  
 9. SHEET A3 (NOW A4) TYPICAL BASE CABINET DETAIL
 INDICATES A KOHLER STAINLESS STEEL, LYRIC BAR SINK
 K-3288 W/GOOSENECK FAUCET K-11930 FOR ELEV. D ONLY.
 REUSED EXISTING SINK FOR ELEV. C ONLY. THIS DETAIL IS
 CONFUSING, PLEASE CLEARLY INDICATE THE ROOM NUMBER THIS
 SINK AND FAUCET IS BEING INSTALLED IN AND ITS LOCATION
 ON SHEET A1 FLOOR PLAN.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 10. SHEET A3 (NOW A4) DRINKING FOUNTAIN DETAIL: PLEASE
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 ELEVATION DETAIL AND INDICATE THE CLEAR FLOOR SPACE ON
 SHEET A1 PROPOSED FLOOR PLAN.
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRES THE FOLLOWING INFORMATION):
 11-4.15.2 SPOUT HIEGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM
 NOT THE SPOUT).
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" CLEAR
 FLOOR SPACE.
 ****RESPONSE NOTED, BUT THE SPOUT HEIGHT AND THE CLEAR
 FLOOR SPACE HAVE NOT BEEN ADDRESSED. (NOTE: CLEAR FLOOR
 SPACE SHALL BE FORWARD APPROACH).
  
 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103
 INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE
 COMPLIANT TO THE FOLLOWING SECTIONS:
  
 **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR
 SPACE ON SHT A1 PROPOSED FLOOR PLAN)
 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F.
 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48"
 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE
 FOLOWING REQUIREMENTS FOR TOILET ROOMS #103, #106, #109
 AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE.
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" UNOBSTRUCTED
 CLEAR FLOOR SPACE (PER 11-4.2.3).
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT
 THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING
 AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING.
 PER FBC- PLUMBING SECTION 701.1 SCOPE.
 E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED ON
 THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER
 DIAGRAM ON SHEET M1
 ****NO RESPONSE, COMMENT SECTION E} NOT ADDRESSED.
 (RISER NOW INDICATED ON SHEET P1).
  
 14. OK
  
 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS
 THE PRINTED NAME AND SIGNATURE: (OF THE PERSON
 DESIGNING THE RISER DIAGRAM)
 NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND THE DATE TO SAID DRAWINGS. PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 16. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATIONS OF THE WATER SUPPLY LINE
 WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION
 CONTROL FOR THE WATER HEATER **607.3, AND THE LOCATION
 OF THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING
 VALVES ARE UTILIZED. (EXAMPLES=WASH MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING
 INSULATION COMPLIANCE. PER FBC- CHAPTER 13, SECTION
 13-412 WATER HEATING SYSTEMS TABLE 13-142.1.ABC.3
 PERFORMANCE REQUIREMENTS FOR WATER HEATING EQUIPMENT,
 AND TABLE 13-411.1.ABC.2 MINIMUM PIPE INSULATION.
  
 ***********NEW COMMENT***********
  
 1B. SHT C-1 REQUIRED PLUMBING FIXTURES. PER TABLE 403.1
 A-3 ASSEMBLY SHOWS THE REQUIRED W/C COUNT TO BE 1 PER
 150 FOR MALE AND 1 PER 75 FOR FEMALE WHICH COMES OUT TO
 1 FOR THE MALE AND 2 FOR THE FEMALE. (TOTAL OCCUPANCY
 195 DIVIDED BY 2 EQUALS 97.5 ROUNDED UP TO 98 MALE & 98
 FEMALE). PLEASE CORRECT REQUIRED PLUMBING FIXTURE
 COUNT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 09:21 Rev Time 0.00
Received By mperson Date 2008-07-15 Time 08:07 Sent To  
Notes
2008-07-14 17:08:04PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET C1 IS INDICATING THE WRONG OCCUPANCY AS GROUP
 B BUSSINESS. THE CORRECT OCCUPANCY GROUP SHOULD BE
 GROUP A-3 (PLACES OF WORSHIP AND OTHER RELIGIOUS
 SERVICES. CHURCHES WITHOUT ASSEMBLY HALLS). ALSO THE
 NUMBER OF OCCUPANTS NEEDS TO BE INDICATED. PER
 FBC-PLUMBING SECTION 403.1.
  
 2. SHEET C1: PLEASE DECLARE THE CORRECT GOVERNING CODE
 (FBC-2004 WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED)
 SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 3. SHEET C1: PLEASE DECLARE THE LEVEL OF ALTERATION.
 PER FBC-2004 EXISTING BUILDING CODE.
  
 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY
 INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR
 PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3.
  
 5. SHEET A1 PROPOSED FLOOR PLAN: PLEASE CLEARLY
 IDENTIFY ALL PROPOSED PLUMBING FIXTURES ON THIS SHEET
 AND PROVIDE A FIXTURE SCHEDULE. SOME PLUMBING FIXTURES
 ARE NOT IDENTIFIED AND OTHERS ARE IDENTIFIED BY
 ABBREVIATIONS. IS THE WF. IN THE ENTRY A DRINKING
 FOUNTAIN? THE LAVATORIES ARE NOT IDENTIFIED AND SOME OF
 THE WATER CLOSETS HAVE ABB. IDENTIFICATION. PLEASE
 CLARIFY THIS PER FBC- PLUMBING SECTION 401.1 SCOPE.
  
 6. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: THE
 GRAB BARS ARE BEING INDICATED IN THE WRONG PLACE. THE
 36" GRAB BAR NEEDS TO BE LOCATED BEHIND THE WATER
 CLOSET AND THE 42" GRAB BAR NEEDS TO BE LOCATED TO THE
 SIDE. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION 11-4.16.4.
  
 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER
 FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.17.3.
 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 8. SHEET A3 HC LAV. BATH PLAN VIEW DETAIL: PLEASE
 CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS WITH
 THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL BE
 1'-6" AND THE LAVATORY SHALL BE 1'-5". PER FBC- CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTION 11-4.16.2 FOR
 THE WATER CLOSET AND SECTION 11-4.19.3 CLEAR FLOOR
 SPACE. ALSO PLEASE PROVIDE THE FOLLOWING INFORMATION ON
 THE ELEVATION DETAILS AND SHEET A1 PROPOSED FLOOR
 PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE
 FOLLOWING INFORMATION AND CLEAR FLOOR SPACE NEEDS TO BE
 INDICATED ON SHEET A1)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5
 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR
 SPACE NEEDS TO BE INDICATED ON SHEET A1)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 9. SHEET A3 TYPICAL BASE CABINET DETAIL INDICATES A
 KOHLER STAINLESS STEEL, LYRIC BAR SINK K-3288 W/GOOSE
 NECK FAUCET K-11930 FOR ELEV. D ONLY. REUSED EXISTING
 SINK FOR ELEV. C ONLY. THIS DETAIL IS CONFUSING, PLEASE
 CLEARLY INDICATE THE ROOM NUMBER THIS SINK ANS FAUCET
 IS BEING INSTALLED IN AND ITS LOCATION ON SHEET A1
 FLOOR PLAN.
  
 10. SHEET A3 DRINKING FOUNTAIN DETAIL: PLEASE PROVIDE
 THE FOLLOWING INFORMATION ON THE ELEVATION DETAIL AND
 INDICATE THE CLEAR FLOOR SPACE ON SHEET A1 PROPOSED
 FLOOR PLAN.
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRES WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM
 NOT THE SPOUT)
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103
 INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE
 COMPLIANT TO THE FOLLOWING SECTIONS.
  
 **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR
 SPACE ON SHEET A1 PROPOSED FLOOR PLAN)
 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F.
 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48"
 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F.
  
 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE
 FOLLOWING REQUIREMENTS FOR BATHROOMS #103, #106, #109,
 AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT
 THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING
 AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING.
 PER FBC- PLUMBING SECTION 701.1 SCOPE.
 A} DRINKING FOUNTAIN MISSING FROM RISER DIAGRAM.B}
 LAVATORY IN MENS BATH #103 BEING INDICATED IN WRONG
 PLACE.
 C} LAVATORY IN WOMENS BATH #106 HANDICAP STALL BING
 INDICATED IN WRONG PLACE.
 D} LAVATORIES IN MENS BATH #109 AND WOMENS BATH #110
 BEING INDICATED IN WRONG PLACE.
 E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED
 ON THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER
 DIAGRAM ON SHEET M1.
  
 14. SHEET M1 SANITARY PLUMBING RISER: THE FOLLOWING
 FIXTURES REQUIRE VENTS PER THE FOLLOWNG FBC- PLUMBING
 SECTIONS.
 A} URINALS IN MENS BATH #103. PER SECTION 901.2.1
 VENTING REQUIRED.
 B} A CIRCUIT VENT SHALL BE LOCATED BETWEEN THETWO MOST
 UPSTREAM FIXTURE DRAINS. PER SECTION 911.2 VENT
 CONNECTION.
  
 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS
 THE PRINTED NAME AND SIGNATURE:
 NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 *ROLANDS A/C AND REFRIGERATION IS NOT A LICENSED
 PLUMBING CONTRACTOR AND MAY NOT DESIGN OR SIGN FOR THE
 SANITARY PLUMBING RISER. PER F.S. 471.003(H). PLEASE
 REMOVE PLUMBING FROM THE MECHANICAL PLAN AND SUBMIT
 SEPERATELY.
  
 16. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
  
 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING
 COMPLIANCE. PER FBC- CHAPTER 13, SECTION 13-412 WATER
 HEATING SYSTEMS TABLE 13-412.1.ABC.3 PERFORMANCE
 REQUIREMENTS FOR WATER HEATING EQUIPMENT, AND TABLE
 13-411.1.ABC.2 MINIMUM PIPE INSULATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved