2008-07-14 17:08:04 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET C1 IS INDICATING THE WRONG OCCUPANCY AS GROUP |
| B BUSSINESS. THE CORRECT OCCUPANCY GROUP SHOULD BE |
| GROUP A-3 (PLACES OF WORSHIP AND OTHER RELIGIOUS |
| SERVICES. CHURCHES WITHOUT ASSEMBLY HALLS). ALSO THE |
| NUMBER OF OCCUPANTS NEEDS TO BE INDICATED. PER |
| FBC-PLUMBING SECTION 403.1. |
| |
| 2. SHEET C1: PLEASE DECLARE THE CORRECT GOVERNING CODE |
| (FBC-2004 WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED) |
| SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. |
| |
| 3. SHEET C1: PLEASE DECLARE THE LEVEL OF ALTERATION. |
| PER FBC-2004 EXISTING BUILDING CODE. |
| |
| 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY |
| INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR |
| PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER |
| OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3. |
| |
| 5. SHEET A1 PROPOSED FLOOR PLAN: PLEASE CLEARLY |
| IDENTIFY ALL PROPOSED PLUMBING FIXTURES ON THIS SHEET |
| AND PROVIDE A FIXTURE SCHEDULE. SOME PLUMBING FIXTURES |
| ARE NOT IDENTIFIED AND OTHERS ARE IDENTIFIED BY |
| ABBREVIATIONS. IS THE WF. IN THE ENTRY A DRINKING |
| FOUNTAIN? THE LAVATORIES ARE NOT IDENTIFIED AND SOME OF |
| THE WATER CLOSETS HAVE ABB. IDENTIFICATION. PLEASE |
| CLARIFY THIS PER FBC- PLUMBING SECTION 401.1 SCOPE. |
| |
| 6. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: THE |
| GRAB BARS ARE BEING INDICATED IN THE WRONG PLACE. THE |
| 36" GRAB BAR NEEDS TO BE LOCATED BEHIND THE WATER |
| CLOSET AND THE 42" GRAB BAR NEEDS TO BE LOCATED TO THE |
| SIDE. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTION 11-4.16.4. |
| |
| 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER |
| FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| 11-4.17.3. |
| EXCEPTION: NEW CONSTRUCTION. |
| (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL |
| CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF |
| SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO |
| COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH |
| LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| FIXTURE COUNT FOR THE BUILDING. |
| (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN |
| THE CORNER, DIAGONAL TO THE DOOR. |
| |
| 8. SHEET A3 HC LAV. BATH PLAN VIEW DETAIL: PLEASE |
| CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS WITH |
| THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL BE |
| 1'-6" AND THE LAVATORY SHALL BE 1'-5". PER FBC- CHAPTER |
| 11, FLORIDA ACCESSIBILITY CODE SECTION 11-4.16.2 FOR |
| THE WATER CLOSET AND SECTION 11-4.19.3 CLEAR FLOOR |
| SPACE. ALSO PLEASE PROVIDE THE FOLLOWING INFORMATION ON |
| THE ELEVATION DETAILS AND SHEET A1 PROPOSED FLOOR |
| PLAN. |
| |
| **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE |
| FOLLOWING INFORMATION AND CLEAR FLOOR SPACE NEEDS TO BE |
| INDICATED ON SHEET A1) |
| 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5 |
| FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH. |
| |
| **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR |
| SPACE NEEDS TO BE INDICATED ON SHEET A1) |
| 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| 32) |
| 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| |
| 9. SHEET A3 TYPICAL BASE CABINET DETAIL INDICATES A |
| KOHLER STAINLESS STEEL, LYRIC BAR SINK K-3288 W/GOOSE |
| NECK FAUCET K-11930 FOR ELEV. D ONLY. REUSED EXISTING |
| SINK FOR ELEV. C ONLY. THIS DETAIL IS CONFUSING, PLEASE |
| CLEARLY INDICATE THE ROOM NUMBER THIS SINK ANS FAUCET |
| IS BEING INSTALLED IN AND ITS LOCATION ON SHEET A1 |
| FLOOR PLAN. |
| |
| 10. SHEET A3 DRINKING FOUNTAIN DETAIL: PLEASE PROVIDE |
| THE FOLLOWING INFORMATION ON THE ELEVATION DETAIL AND |
| INDICATE THE CLEAR FLOOR SPACE ON SHEET A1 PROPOSED |
| FLOOR PLAN. |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELEVATION DETAIL REQUIRES WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM |
| NOT THE SPOUT) |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN |
| 3" OF THE FRONT OF FOUNTAIN. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103 |
| INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE |
| COMPLIANT TO THE FOLLOWING SECTIONS. |
| |
| **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR |
| SPACE ON SHEET A1 PROPOSED FLOOR PLAN) |
| 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F. |
| 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48" |
| 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F. |
| |
| 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE |
| FOLLOWING REQUIREMENTS FOR BATHROOMS #103, #106, #109, |
| AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTIONS. |
| **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER |
| ROOMS. |
| 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| SPACE |
| 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR |
| SPACE (PER 11-4.2.3) |
| |
| 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT |
| THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL |
| REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING |
| AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING. |
| PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| A} DRINKING FOUNTAIN MISSING FROM RISER DIAGRAM.B} |
| LAVATORY IN MENS BATH #103 BEING INDICATED IN WRONG |
| PLACE. |
| C} LAVATORY IN WOMENS BATH #106 HANDICAP STALL BING |
| INDICATED IN WRONG PLACE. |
| D} LAVATORIES IN MENS BATH #109 AND WOMENS BATH #110 |
| BEING INDICATED IN WRONG PLACE. |
| E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED |
| ON THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER |
| DIAGRAM ON SHEET M1. |
| |
| 14. SHEET M1 SANITARY PLUMBING RISER: THE FOLLOWING |
| FIXTURES REQUIRE VENTS PER THE FOLLOWNG FBC- PLUMBING |
| SECTIONS. |
| A} URINALS IN MENS BATH #103. PER SECTION 901.2.1 |
| VENTING REQUIRED. |
| B} A CIRCUIT VENT SHALL BE LOCATED BETWEEN THETWO MOST |
| UPSTREAM FIXTURE DRAINS. PER SECTION 911.2 VENT |
| CONNECTION. |
| |
| 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS |
| THE PRINTED NAME AND SIGNATURE: |
| NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA |
| BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED |
| NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL |
| SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION |
| *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| *ROLANDS A/C AND REFRIGERATION IS NOT A LICENSED |
| PLUMBING CONTRACTOR AND MAY NOT DESIGN OR SIGN FOR THE |
| SANITARY PLUMBING RISER. PER F.S. 471.003(H). PLEASE |
| REMOVE PLUMBING FROM THE MECHANICAL PLAN AND SUBMIT |
| SEPERATELY. |
| |
| 16. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER |
| RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR |
| BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES, |
| VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH |
| BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR |
| THE WATER HEATER **607.3, AND LOCATION OF THE |
| WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE |
| UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE |
| MAKERS) **604.9. |
| |
| 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE |
| DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING |
| COMPLIANCE. PER FBC- CHAPTER 13, SECTION 13-412 WATER |
| HEATING SYSTEMS TABLE 13-412.1.ABC.3 PERFORMANCE |
| REQUIREMENTS FOR WATER HEATING EQUIPMENT, AND TABLE |
| 13-411.1.ABC.2 MINIMUM PIPE INSULATION. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |