Plan Review Details - Permit 08070147
Plan Review Stops For Permit 08070147
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By shill Date 2008-07-22 Time 14:21 Rev Time 0.00
Received By shill Date 2008-07-22 Time 14:21 Sent To  
Notes
2008-07-22 14:22:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS481.
  
 2.PROVIDE A STRUCTURAL DETAIL FOR THE SLAB.PREFAB
 SLABS REQUIRE ENGINEERING TO SHOW HOW IT WILL RESIST
 WIND AND GRAVITY LOADS.
  
 3.DECLARE GOVERNING CODE INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 4.DECLARE WIND DESIGN CRITERIA (WIND SPEED AND
 EXPOSURE), FBC R 301.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 12:01 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 11:33 Sent To P
Notes
2008-07-08 12:01:27 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 PROVIDE THE FOLLOWING FOR REVIEW
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE
 THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST
 CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE
 RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR
 DETAILS REGARDING SETBACKS.
  
 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE
 THE FOLLOWING:
  
 A) GENERATOR AND TRANSFER SWITCH MANUFACTURER
 SPECIFICATIONS.
  
  
 B) RISER DIAGRAM SHOWING LOCATIONS OF ALL
 EQUIPMENT ELECTRICALLY.
  
 C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE
 EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE
 STRUCTURES.
  
 D) MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES
  
 G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS
 INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL
 BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND
 TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-07-11 Cont ID  
Sent By mperson Date 2008-07-11 Time 08:03 Rev Time 0.00
Received By mperson Date 2008-07-11 Time 08:03 Sent To B
Notes
2008-07-11 08:44:11GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PERMIT APPLICATION WHERE THE PLUMBING
 CONTRACTOR IS SIGNED ON THE DATE IS INDICATED AS
 9/23/08. THIS DATE IS INCORRECT, PLEASE CORRECT. ALSO
 THE STATE LICENSE OF CERT. OF COMPETENCY FOR THE
 PLUMBING CONTRACTOR IS REQUIRED. PLEASE REFERENCE A
 COPY OF THE PLUMBING CONTRACTORS STATE LICENSE NUMBER
 ATTACHED TO THESE COMMENTS AND CORRECT THE PERMIT
 APPLCATION. PER FLORIDA STATUTES SECTION 713.135(5) AND
 (6) ALSO (W.P.B. AS AMENDED) SECTION 105 PERMITS.
  
 2. TWO COPIES OF REVISED GAS ISOMETRIC RISER DIAGRAM
 PLANS WITH REVISION FEES PAID DESIGNATING THE GENERATOR
 "NEW" REQUIRED. PER FBC- FUEL GAS CODE SECTION 401.1
 SCOPE.
  
 3. TWO COPIES OF A OF A SITE PLAN OR SURVEY CLEARLY
 INDICATING THE LOCATION OF THE GENERATOR, DIMENSIONS
 FROM PROPERTY LINES AND DISTANCES FROM ADJACENT
 STRUCTURES REQUIRED. PER FBC- FUEL GAS CODE SECTION
 401.1 SCOPE.
  
 4. TWO COPIES OF MANUFACTURER'S SPECIFICATIONS OF THE
 GENERATOR CLEARLY INDICATING THE MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, SETBACK RECOMMENDATIONS FROM
 STRUCTURES, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY ARE REQUIRED. PER FBC- FUEL GAS CODE
 SECTION 402.2 MAXIMUM GAS DEMAND, ALSO NFPA 54 AND 58
 STANDARDS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-07-03 Cont ID  
Sent By swurafti Date 2008-07-03 Time 11:24 Rev Time 0.00
Received By swurafti Date 2008-07-03 Time 11:24 Sent To  
Notes
2008-07-03 11:25:07HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 17:40 Sent To  
Notes
2008-07-03 17:40:35TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By tgordon Date 2008-07-08 Time 14:21 Rev Time 0.25
Received By tgordon Date 2008-07-08 Time 14:21 Sent To G
Notes
2008-07-08 14:24:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 GENERATOR.
  
 2) SUBMIT SITE PLAN SHOWING GENERATOR LOCATION AND ANY
 BUILDING OPENINGS WITH IN 10 FEET.
  
 3) PLEASE INDICATE FLUE TYPE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By choops Date 2008-07-08 Time 08:35 Rev Time 0.00
Received By choops Date 2008-07-08 Time 08:35 Sent To E
Notes
2008-07-08 08:45:02***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 NOTE:REQUIRED SETBACKS FOR POR ZONING DISTRICT:
  
 MINIMUM SETBACKS:
 A.FRONT: 25 FEET.
 B.CORNER SIDE (IF APPLICABLE): 15 FEET.
 C.SIDE: TEN FEET.
 D.INTERIOR SIDE: TEN FEET.
 E.REAR: 15 FEET.
  
 3) SCREENING REQUIRED.PURSUANT TO SECTION
 94-444(B) OF THE ZLDRS:
  
 OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY
 USES; STORAGE AND DISPOSAL FACILITIES.OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR
 PROPANE TANKS, AND MECHANICAL EQUIPMENT SHALL NOT BE
 PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - GENRES BOX