Plan Review Details - Permit 08070016
Plan Review Stops For Permit 08070016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-05 Cont ID  
Sent By rmcdouga Date 2008-08-05 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2008-08-05 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-22 Cont ID  
Sent By rmcdouga Date 2008-07-22 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2008-07-22 Time 09:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 14:59 Rev Time 0.00
Received By btrobaug Date 2008-08-04 Time 14:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 13:37 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 13:17 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 16:26 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 16:26 Sent To B
Notes
2008-08-04 16:27:54NOTE: SEE PLUMBING PROVISO, B}.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-07-09 Cont ID  
Sent By mperson Date 2008-07-09 Time 09:26 Rev Time 0.00
Received By mperson Date 2008-07-09 Time 09:26 Sent To B
Notes
2008-07-09 09:28:16NOTE: REFERENCE PLBG. COMMENT #6.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 11:36 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 11:36 Sent To Z
Notes
2008-07-23 11:37:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-22 Time 11:36 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 16:07 Sent To  
Notes
2008-07-01 16:07:24TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 16:17 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 16:17 Sent To G
Notes
2008-08-04 16:26:25****************PROVISO****************
 A} PER FLORIDA STATUTES 489.105 (3)(M), THE POTABLE
 WATER TIE IN AND MAKE UP WATER FOR THE BACKFLOW
 PREVENTER TO THE AUTO FILL LINE SHALL BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR (SEPERATE PERMIT
 REQUIRED).
 B} TWO COPIES OF MANUFACTURER'S SPECIFICATION SHEETS
 FOR THE 400,000 BTU GAS POOL HEATER ARE REQUIRED FOR
 APPROVAL CLEARLY INDICATING THE MAKE, MODEL NUMBER, BTU
 LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (LISTING EXAMPES ARE=
 AGA, CSA, UL).
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By mperson Date 2008-07-09 Time 16:31 Rev Time 0.00
Received By mperson Date 2008-07-09 Time 09:04 Sent To G
Notes
2008-07-08 16:58:10PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SP-1 IS INCORRECTLY INDICATES (4) NEW STUB OUT FOR
 POOL CLEANER. THERE SHOULD ONLY BE (1) INDICATED FOR
 THIS. PER FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6
 ENGINEERING DESIGN.
  
 2. SP-1 IS INCORRECTLY INDICATING AN ARROW TO THE 9"
 MAIN DRAINS AND VENT PIPING WITH THE FOLLOWING "ADD (2)
 JANDYDECK JETS W/1-1/2" SUPPLY LINES AND VALVES". THIS
 IS CONFUSING, PLEASE CLARIFY THIS AREA ON THE RESUB.
 PER FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6
 ENGINEERING DESIGN.
  
 3. SP-2 LEGEND PER THE EQUIPMENT LAYOUT HAS
 INCORRECTLY IDENTIFIED #1 AS A "3" POOL MAIN DRAIN
 LINE". #1 SHOULD BE THE 1-1/2" RAIN ARCH SUPPLY. ALSO
 #2 IS INCORRECTLY IDENTIFIED AS "2" RAIN ARCH SUPPLY
 LINES". #2 SHOULD BE THE 3" POOL MAIN DRAIN LINE.
 PLEASE CORRELATE AND CORRECT THESE ITEMS. PER
 FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6 ENGINEERING
 DESIGN.
  
 4. SP-2 POOL/SPA SPECIFICTIONS INDICATES A SALT
 GENERATOR AND A JANDY RS-8 SYSTEM THAT ARE NOT
 INDICATED ON THE EQUIPMENT LAYOUT. PLEASE CLEARLY
 INDICATE THE LOCATION OF THESE ITEMS ON THE RESUBMITTED
 EQUIPMENT LAYOUT. PER FBC-RESIDENTIAL CHAPTER 41,
 SECTION R4101.6 ENGINEERING DESIGN.
  
 5. SP-2 LEGEND #9. CAN'T FIND THIS ITEM ON SHEET SP-1.
 PLEASE CLARIFY WHERE THIS ITEM IS ON THE RESUBMITTAL.
 PER FBC-RESIDENTIAL CHAPTER 41, SECTION 4101.6
 ENGINEERING DESIGN.
  
 6. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (PLEASE SUBMIT TWO COPIES OF
 MANUFACTURE SHEETS OR IF THE POOL HEATER IS EXISTING
 CLEARLY INDICATE THIS ON THE PLANS)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 12:29 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 12:28 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-07 Cont ID  
Sent By choops Date 2008-07-07 Time 12:57 Rev Time 0.00
Received By choops Date 2008-07-07 Time 12:57 Sent To E
Notes
2008-07-07 12:59:50***APPROVED***
  
 PROVISOS:
 1)PATIO/PAVED AREA PROVIDED SURROUNDING THE POOL,
 SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT NOT
 ONTO ADJACENT PROPERTIES.
 2)SPA SHALL MAINTAIN A MINIMUM SETBACK OF 5' FROM
 WATER'S EDGE TO SIDE AND REAR PROPERTY LINES.