Plan Review Details - Permit 08060901
Plan Review Stops For Permit 08060901
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-08 Cont ID  
Sent By shill Date 2008-09-08 Time 15:08 Rev Time 0.00
Received By shill Date 2008-09-08 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By shill Date 2008-08-11 Time 16:27 Rev Time 0.00
Received By shill Date 2008-08-11 Time 16:27 Sent To  
Notes
2008-08-11 16:28:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PROVIDE TWO IDENTICAL COLLATED SETS FOR PERMIT
 ISSUANCE.ONLY ONE NEW SET WAS SUBMITTED; SECOND SET
 MARKED "OLD".

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-16 Cont ID  
Sent By shill Date 2008-07-16 Time 13:59 Rev Time 0.00
Received By shill Date 2008-07-16 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 15:58 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 15:37 Sent To P
Notes
2008-07-08 15:58:42 
  
  
  
 GENERATOR PERMITS MUST BE APPLIED FOR SEPARATELY AND
 THE FOLLOWING IS REQUIRED
  
 ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS,
 SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF
 ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER
 108.3 WPB AMENDMENTS. INDICATE FUEL TYPE AND KW RATING
 ON THE APPLICATION.
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE
 THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST
 CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE
 RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR
 DETAILS REGARDING SETBACKS.
  
 2} A GAS PERMIT MUST BE APPLIED FOR NATURAL GAS OR LP
 FUELED GENERATORS. SUBMIT INFORMATION COMPLIANT WITH
 THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENT.
  
 3} A FUEL PERMIT IS REQUIRED FOR GASOLINE OR DIESEL.
  
 4} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE
 THE FOLLOWING:
  
 A) GENERATOR AND TRANSFER SWITCH MANUFACTURER
 SPECIFICATIONS.
 1) THE TRANSFER SWITCH MUST BE SIZED FOR THE SELECTED
 LOADS.
  
 B) RISER DIAGRAM SHOWING LOCATIONS OF ALL EQUIPMENT
 ELECTRICALLY.
  
 C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE
 EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE
 STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE
 RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF
 LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO
 110.9 FOR AIC RATING.
  
 D) MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 E) IDENTIFY LOADS TO BE SERVED, PROVIDE A PANEL
 SCHEDULE FOR GENERATOR PANEL.
  
 F) LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A
 LOAD CALCULATION FOR THE LOADS TO BE SERVED IF AN
 AUTOMATIC TRANSFER SWITCH IS BEING INSTALLED.
  
 G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS
 INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL
 BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND
 TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING.
  
 SEE ARTICLES 445 AND 702 FOR ADDITIONAL INFORMATION.
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-07-10 Cont ID  
Sent By mperson Date 2008-07-10 Time 11:32 Rev Time 0.00
Received By mperson Date 2008-07-10 Time 11:32 Sent To B
Notes
2008-07-10 11:46:00CONTRACTOR INFORMATION
 NOTE: THE PERMIT APPLICATION INDICATES ONLY STRUCTURAL
 WORK. A SEPERATE RESIDENTIAL GENERATOR PERMIT WILL BE
 REQUIRED FOR THE NEW GENERATOR. ALSO A GAS PERMIT WILL
 BE REQUIRED IF THE GENERATOR IS NATURAL OR LP GAS
 FUELED . A LICENSED GAS OR PLUMBING CONTRACTOR SHALL
 SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS TO BE COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 10:18 Sent To B
Notes
2008-09-08 10:18:25TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 10:31 Sent To Z
Notes
2008-08-21 10:31:59TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 13:17 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 13:17 Sent To Z
Notes
2008-07-24 13:17:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-16 Time 13:08 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 11:41 Sent To  
Notes
2008-07-01 11:42:31TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By kdfreema Date 2008-09-04 Time 16:46 Rev Time 0.00
Received By kdfreema Date 2008-09-04 Time 16:46 Sent To  
Notes
2008-09-04 16:51:30PROVISO:
  
 POOL DECK SHALL NOT BE EXPANDED BEYOND THE BOUNDARIES
 DEPICTED ON THE SITE PLAN.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-08-28 Cont ID  
Sent By kdfreema Date 2008-08-28 Time 11:10 Rev Time 0.00
Received By kdfreema Date 2008-08-28 Time 11:09 Sent To  
Notes
2008-08-28 11:14:46***FAILED***
  
 1. PLEASE SHOW SCOPE OF WORK ON SITE PLAN. THE SITE
 PLAN SHOWS AN EXISTING CIRCULAR DRIVE ON FLAMINGO, IS
 THE DRIVEWAY REWORK A REPLACEMENT OF THE EXISTING
 SURFACE IN THE SAME CONFIGURATION? WILL THE SIZE OF THE
 DRIVEWAY CHANGE? PLEASE CLARIFY.
  
 2. THERE IS NO SCOPE OF WORK INDICATED FOR THE SWIMMING
 POOL DECK. PLEASE INDICATE IF THE SIZE WILL REMAIN AS
 EXISTS OR IF ITS SIZE WILL INCREASE OR DECREASE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By mcruz Date 2008-08-04 Time 12:19 Rev Time 0.00
Received By mcruz Date 2008-08-04 Time 11:58 Sent To B
Notes
2008-08-04 12:22:55***ZONING FAILED***
  
 1.PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2.PURSUANT TO SECTION 94-305(C)(1) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS):MULTIFRONTAGE
 LOTS. UNLESS OTHERWISE PROVIDED BY THIS CHAPTER, THE
 REQUIRED FRONT SETBACK SHALL BE REQUIRED FOR ALL LOTS
 HAVING FRONTAGE ON MORE THAN ONE STREET.
  
 NOTE:PER SECTION 94-74(A)(3) OF THE ZLDRS:
 SINGLE-FAMILY HIGH DENSITY (SF14) RESIDENTIAL
 DISTRICTS. MINIMUM SETBACK REQUIREMENTS FOR PRINCIPAL
 BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 3.FENCE EXCEEDS MAXIMUM HEIGHT ALLOWABLE.PURSUANT
 TO ZLDRS, SECTION 94-302(B)(1):MAXIMUM HEIGHT. IN
 RESIDENTIAL DISTRICTS, NO FENCE OR WALL SHALL EXCEED
 SIX FEET IN HEIGHT WITHIN REQUIRED SIDE AND REAR
 SETBACKS. FENCES OR WALLS SHALL NOT BE IN EXCESS OF 48
 INCHES IN HEIGHT WITHIN THE REQUIRED FRONT SETBACK.
 HEDGES SHALL NOT EXCEED TEN FEET IN HEIGHT IN ANY
 REQUIRED SETBACK.NO FENCE, WALL, OR GATE THAT EXCEEDS
 4 FEET IN HEIGHT SHALL BE PERMITTED WITHIN THE REQUIRED
 FRONT SETBACK OF 25 FEET.
  
 4.DESCRIPTION OF SCOPE OF WORK INDICATES A NEW DRIVEWAY
 ADJACENT TO FLAMINGO DRIVE BUT THE SITE PLAN SHOWS THAT
 THE DRIVEWAY IS EXISTING.PLEASE CLARIFY ON THE
 APPLICATION (THE ORIGINAL APPLICATION).
  
 5.INDICATE ON THE SURVEY AND SITE PLAN THE DIMENSIONS
 OF THENEW DRIVEWAY, IF APPLICABLE, AND THE AREA OF
 NEW PAVING ALONG AUSTIN LN.THE SITE PLAN SHOWS AN
 EXISTING CARPORT, HOWEVER, IT IS NOT ON THE SURVEY.
 PLEASE CLARIFY AND MAKE BOTH THE SITE PLAN AND SURVEY
 CONSISTENT.
  
 6.REPEAT COMMENT:PURSUANT TO SECTION 94-482 OF THE
 ZLDRS: REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN
 FOUR RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
 ADD DIMENSIONS FOR BOTH FRONTAGES.
  
  
 NOTE:THE SITE PLAN SHOWS THE PROPOSED GENERATOR WILL
 BE LOCATED 6'-6" FROM PROPERTY LINE FACING AUSTIN LN.
 THE 25 FOOT SETBACK REQUIREMENT ALSO APPLIES TO THE
 GENERATOR EQUIPMENT.AS PER SECTION 94-305(B)(4) OF
 THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK, THEREFORE, THE
 GENERATOR SHALL BE LOCATED AT LEAST 21 FEET FROM THE
 FRONT PROPERTY LINE (IN THIS CASE FROM BOTH FLAMINGO
 DR. AND AUSTIN LN.).
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-07 Cont ID  
Sent By choops Date 2008-07-07 Time 09:38 Rev Time 0.00
Received By choops Date 2008-07-07 Time 09:38 Sent To E
Notes
2008-07-07 09:47:27***FAILED***
  
  
 1)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 2)CLARIFY SCOPE OF WORK.PLANS INDICATE A NEW
 GENERATOR...IS THIS GENERATOR INCLUDED UNDER THE SCOPE
 OF WORK FOR THIS PERMIT APPLICATION?IF NOT, REMOVE
 FROM PLANS OR LABEL, "TO BE PERMITTED SEPARATELY."IF
 YES, THE GENERATOR DOES NOT MEET THE MINIMUM REAR
 SETBACK REQUIREMENT.AS PER SECTION 94-305(B)(4) OF
 THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE:SIDE PROPERTY LINE DIMENSIONS DO NOT MATCH
 BETWEEN SURVEY AND SITE PLAN.CLARIFY.
  
 3)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
  
 PLEASE CLARIFY IF PAVERS ARE TO BE UNSEALED/SET IN SAND
 OR SEALED.
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]