2008-08-04 12:22:55 | ***ZONING FAILED*** |
| |
| 1.PLEASE PROVIDE ALL RESPONSES IN WRITING. |
| |
| 2.PURSUANT TO SECTION 94-305(C)(1) OF THE ZONING AND |
| LAND DEVELOPMENT REGULATIONS (ZLDRS):MULTIFRONTAGE |
| LOTS. UNLESS OTHERWISE PROVIDED BY THIS CHAPTER, THE |
| REQUIRED FRONT SETBACK SHALL BE REQUIRED FOR ALL LOTS |
| HAVING FRONTAGE ON MORE THAN ONE STREET. |
| |
| NOTE:PER SECTION 94-74(A)(3) OF THE ZLDRS: |
| SINGLE-FAMILY HIGH DENSITY (SF14) RESIDENTIAL |
| DISTRICTS. MINIMUM SETBACK REQUIREMENTS FOR PRINCIPAL |
| BUILDING ARE AS FOLLOWS: |
| |
| A. FRONT: 25 FEET; |
| B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60 |
| FEET WIDE; |
| C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS |
| LESS; |
| D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. |
| |
| 3.FENCE EXCEEDS MAXIMUM HEIGHT ALLOWABLE.PURSUANT |
| TO ZLDRS, SECTION 94-302(B)(1):MAXIMUM HEIGHT. IN |
| RESIDENTIAL DISTRICTS, NO FENCE OR WALL SHALL EXCEED |
| SIX FEET IN HEIGHT WITHIN REQUIRED SIDE AND REAR |
| SETBACKS. FENCES OR WALLS SHALL NOT BE IN EXCESS OF 48 |
| INCHES IN HEIGHT WITHIN THE REQUIRED FRONT SETBACK. |
| HEDGES SHALL NOT EXCEED TEN FEET IN HEIGHT IN ANY |
| REQUIRED SETBACK.NO FENCE, WALL, OR GATE THAT EXCEEDS |
| 4 FEET IN HEIGHT SHALL BE PERMITTED WITHIN THE REQUIRED |
| FRONT SETBACK OF 25 FEET. |
| |
| 4.DESCRIPTION OF SCOPE OF WORK INDICATES A NEW DRIVEWAY |
| ADJACENT TO FLAMINGO DRIVE BUT THE SITE PLAN SHOWS THAT |
| THE DRIVEWAY IS EXISTING.PLEASE CLARIFY ON THE |
| APPLICATION (THE ORIGINAL APPLICATION). |
| |
| 5.INDICATE ON THE SURVEY AND SITE PLAN THE DIMENSIONS |
| OF THENEW DRIVEWAY, IF APPLICABLE, AND THE AREA OF |
| NEW PAVING ALONG AUSTIN LN.THE SITE PLAN SHOWS AN |
| EXISTING CARPORT, HOWEVER, IT IS NOT ON THE SURVEY. |
| PLEASE CLARIFY AND MAKE BOTH THE SITE PLAN AND SURVEY |
| CONSISTENT. |
| |
| 6.REPEAT COMMENT:PURSUANT TO SECTION 94-482 OF THE |
| ZLDRS: REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN |
| FOUR RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE |
| PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED |
| PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE |
| LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT |
| YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN |
| THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, |
| NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION |
| 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO |
| PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. |
| ADD DIMENSIONS FOR BOTH FRONTAGES. |
| |
| |
| NOTE:THE SITE PLAN SHOWS THE PROPOSED GENERATOR WILL |
| BE LOCATED 6'-6" FROM PROPERTY LINE FACING AUSTIN LN. |
| THE 25 FOOT SETBACK REQUIREMENT ALSO APPLIES TO THE |
| GENERATOR EQUIPMENT.AS PER SECTION 94-305(B)(4) OF |
| THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE |
| THAN 4 FEET INTO A REQUIRED SETBACK, THEREFORE, THE |
| GENERATOR SHALL BE LOCATED AT LEAST 21 FEET FROM THE |
| FRONT PROPERTY LINE (IN THIS CASE FROM BOTH FLAMINGO |
| DR. AND AUSTIN LN.). |
| |
| NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY |
| GENERATE ADDITIONAL COMMENTS. |
| |