Plan Review Details - Permit 08060871
Plan Review Stops For Permit 08060871
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-01 Cont ID  
Sent By tgordon Date 2008-07-01 Time 09:20 Rev Time 0.00
Received By tgordon Date 2008-06-30 Time 15:18 Sent To  
Notes
2008-06-30 15:18:37TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-01 Cont ID  
Sent By tgordon Date 2008-07-01 Time 08:48 Rev Time 0.45
Received By tgordon Date 2008-07-01 Time 08:48 Sent To  
Notes
2008-07-01 09:01:09*** PROVISO ***
 1) APARTMENT ONE NEEDS TO COMPLY WITH 2004 FBC/R
 M1602.2 RETURN AIR PROHIBITED SOURCES.
 OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR
 COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING
 LOCATIONS.
 (4) A CLOSET, BATHROOM, TOILET ROOM, KITCHEN,
 GARAGE, MECHANICAL ROOM, FURNACE ROOM OR OTHER DWELLING
 UNIT.
 2) APARTMENT TWO NEEDS TO PROVIDE FOR RETURN AIR TO THE
 BEDROOM, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]