Plan Review Stops For Permit 08060871 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-01 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-06-30 |
Time |
15:18 |
Sent To |
|
|
Notes |
2008-06-30 15:18:37 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2008-07-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-01 |
Time |
08:48 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-07-01 |
Time |
08:48 |
Sent To |
|
|
Notes |
2008-07-01 09:01:09 | *** PROVISO *** | | 1) APARTMENT ONE NEEDS TO COMPLY WITH 2004 FBC/R | | M1602.2 RETURN AIR PROHIBITED SOURCES. | | OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR | | COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING | | LOCATIONS. | | (4) A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, | | GARAGE, MECHANICAL ROOM, FURNACE ROOM OR OTHER DWELLING | | UNIT. | | 2) APARTMENT TWO NEEDS TO PROVIDE FOR RETURN AIR TO THE | | BEDROOM, PER 2004 FBC/R M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
|