Plan Review Details - Permit 08060698
Plan Review Stops For Permit 08060698
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By mjacobs Date 2008-10-22 Time 13:58 Rev Time 0.00
Received By mjacobs Date 2008-10-22 Time 12:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By mjacobs Date 2008-09-23 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2008-09-23 Time 06:36 Sent To  
Notes
2008-09-23 10:21:13BUILDING PLAN REVIEW
 PERMIT: 08060698
 ADD: 2048 PONCE DE LEON
 CONT: JB KERN CONST.
 TEL: (561)762-4849
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 9-23-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **NOTED** THE PLANS DO NOT MEET THE REQUIREMENTS. RAMPS
 AND LANDINGS WITH DROP-OFFS SHALL HAVE A MINIMUM CURB
 OF 2 INCHES. 11-4.8.7 AND FIG 17. THE CLEAR WIDTH SHALL
 BE 44".
 2) 11-4.8.3 THE MINIMUM CLEAR WIDTH OF A RAMP SHALL BE
 36 INCHES. HOWEVER, RAMPS THAT ARE PART OF A REQUIRED
 MEANS OF EGRESS SHALL BE NOT LESS THAN 44 INCHES WIDE.
  
 **NOTE; 1;48 SLOPES MORE THAT 1;50. THEREFORE, THE 1;48
 DO NOT MEET THE REQUIREMENTS.
 3) 11-4.8.6 THE CROSS SLOPE OF RAMP SURFACES SHALL BE
 NO GREATER THAN 1:50. RAMP SURFACES SHALL COMPLY WITH
 SECTION. 11-4.5.
  
 4) 11-4.17.3 THE SIZE AND ARRANGEMENT OF THE STANDARD
 TOILET STALL SHALL COMPLY WITH FIGURE 30(A). SEE DETAIL
 (C) ON SHEET A-2.
  
 WHAT IS THE SLOPE OF THE RAMP? STATE THE INFORMATION ON
 THE PLANS. SEE 11-4.8.
 5) INDICATE THE DIMENSIONS OF THE SLOPE AND LANDING OF
 THE RAMP ON THE SHEET A-2 DETAIL D-3.
  
 NOTE: WHEN RESUBMITTING, PLEASE MAKE SURE TWO SETS OF
 PLANS ARE BOUND TOGETHER. LOOSE PAGES ARE NOT
 ACCEPTABLE. THANKS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By mjacobs Date 2008-07-22 Time 10:25 Rev Time 0.00
Received By mjacobs Date 2008-07-22 Time 06:10 Sent To PC
Notes
2008-07-22 10:25:36 
 BUILDING PLAN REVIEW
 PERMIT: 08060698
 ADD: 2048 PONCE DE LEON
 CONT: JB KERN CONST.
 TEL: (561)762-4849
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 11-4.8.3 THE MINIMUM CLEAR WIDTH OF A RAMP SHALL BE
 36 INCHES. HOWEVER, RAMPS THAT ARE PART OF A REQUIRED
 MEANS OF EGRESS SHALL BE NOT LESS THAN 44 INCHES WIDE.
  
 3) 11-4.8.6 THE CROSS SLOPE OF RAMP SURFACES SHALL BE
 NO GREATER THAN 1:50. RAMP SURFACES SHALL COMPLY WITH
 SECTION. 11-4.5.
  
 4) 11-4.17.3 THE SIZE AND ARRANGEMENT OF THE STANDARD
 TOILET STALL SHALL COMPLY WITH FIGURE 30(A). SEE DETAIL
 (C) ON SHEET A-2.
  
 5) INDICATE THE DIMENSIONS OF THE SLOPE AND LANDING OF
 THE RAMP ON THE SHEET A-2 DETAIL D-3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By btrobaug Date 2008-10-24 Time 07:31 Rev Time 0.00
Received By btrobaug Date 2008-10-24 Time 07:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-14 Cont ID  
Sent By btrobaug Date 2008-07-14 Time 14:43 Rev Time 0.00
Received By btrobaug Date 2008-07-14 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-29 Cont ID  
Sent By mawillia Date 2008-10-29 Time 12:48 Rev Time 0.00
Received By mawillia Date 2008-10-29 Time 12:16 Sent To  
Notes
2008-10-29 12:18:38*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1 & A-1 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-29 Cont ID  
Sent By mawillia Date 2008-09-29 Time 14:10 Rev Time 0.00
Received By mawillia Date 2008-09-29 Time 13:10 Sent To  
Notes
2008-09-29 13:37:38*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
 1. MINIMUM 2A-10BC RATED FIRE EXTINGUISHER(S) SHALL BE
 MOUNTED. SHOW THE LOCATION OF FIRE EXTINGUISHER(S) ON
 THE APPROPIATE PLAN SHEET.
  
 2. RAMP TO COMPLY WITH NFPA 101, SEC 7.2.5. YOUR
 RESPONSE LETTER INDICATES THAT THE WIDTH OF THE RAMP
 HAS BEEN INCREASED TO 3' - 8" WITH NO OBSTRUCTIONS IN
 THAT WIDTH, HOWEVER PLAN SHEET SHOWS 3' - 6" ITS WIDTH
  
 3. ADDRESS SHALL BE A MINUMUM OF 6" IN HEIGHT, 1" WIDTH
 AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL
 BUILDINGS. COULD NOT LOTATE THIS NOTE ON SHEET SP-1 AS
 PER YOUR RESPONSE LETTER. DISPLAY/SHOW THE NUMERICAL
 ADDRESS ON THE APPROPIATE EXTERIOR ELEVATION OF THE
 STRUCTURE WHICH FRONTS PONCE DE LEON AVENUE
  
 4. LOCKS TO COMPLY WITH NFPA 101, SEC 7.2.1.5. COULD
 NOT LOTATE THIS NOTE ON SHEET A-1 AS PER YOUR RESPONSE
 LETTER
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 15:44 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 15:44 Sent To  
Notes
2008-07-21 15:48:43***DENIED***
  
 1) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHER(S) SHALL BE
 MOUNTED.
  
 2) RAMP TO COMPLY WITH NFPA 101, SEC 7.2.5.
  
 3) ADDRESS IS REQUIRED TO BE MINIMUM OF 6" IN HEIGHT,
 1" WIDTH AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL
 BUILDINGS.
  
 4) LOCKS TO COMPLY WITH NFPA 101, SEC. 7.2.1.5.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 09:24 Sent To Z
Notes
2008-11-13 09:24:28TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-21 Cont ID  
Sent By adarroug Date 2008-10-21 Time 12:03 Rev Time 0.00
Received By adarroug Date 2008-10-21 Time 12:03 Sent To  
Notes
2008-10-21 12:05:17TO "BOB#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 12:01 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 12:01 Sent To  
Notes
2008-09-19 12:03:06TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-22 Time   Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 11:49 Sent To  
Notes
2008-06-25 11:49:17TO "BOB"#16

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-09-26 Cont ID  
Sent By rkussner Date 2008-09-26 Time 18:08 Rev Time 0.00
Received By rkussner Date 2008-09-26 Time 18:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By mperson Date 2008-10-24 Time 14:53 Rev Time 0.45
Received By mperson Date 2008-10-24 Time 14:53 Sent To  
Notes
2008-10-24 14:57:25****************PROVISO****************
 INFORMATION ONLY, REVISION NOT REQUIRED.
 FIXTURES SHALL NOT BE DOUBLE TRAPPED. PLEASE KNOW THAT
 A WATER CLOSET HAS AN INTEGRAL TRAP AND ONE IS NOT
 REQUIRED. PER FBC-2004 PLUMBING SECTION 1002.1 FIXTURE
 TRAPS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By mperson Date 2008-09-23 Time 13:22 Rev Time 0.00
Received By mperson Date 2008-09-23 Time 13:22 Sent To  
Notes
2008-09-23 14:10:28PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 **PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES
 WITH 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. SHEET SP-1 PLUMBING FIXTURE CALCULATIONS: THE
 INDICATED PLUMBING CALCULATIONS ON THIS SHEET ARE
 WRONG. PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES FOR AN OCCUPANCY BROUP B-
 BUSSINESS ARE AS FOLLOWS.
  
 *WATER CLOSETS MALE/FEMALE= 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 *LAVATORIES MALE/FEMALE= 1 PER 40 FOR THE FIRST 50 AND
 1 PER 80 FOR THE REMAINDER EXCEEDING 50.
  
 *DRINKING FOUNTAIN= 1 PER 100.
  
 PLEASE CORRECT THESE CALCULATIONS ON THE RESUBMITTAL.
  
 **RESPONSE NOTED, HOWEVER COMMENT #1 HAS NOT BEEN
 ADDRESSED ON THE RESUBMITTED PLANS.
  
 2. SHEET A-2 DETAIL B, H.C. BATHROOM INT. ELEVATION:
 THE GRAB BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES
 MINIMUM. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE SECTION 11-4.16.4 GRAB BARS.
  
 **RESPONSE NOTED, HOWEVER COMMENT #2 HAS NOT BEEN
 ADDRESSED ON THE RESUBMITTED PLANS.
  
 3. SHEET A-2 DETAIL D-2, DRINKING FOUNTAIN DETAIL. PER
 FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **RESPONSE NOTED, HOWEVER COMMENT #3 HAS NOT BEEN
 ADDRESSED ON THE RESUBMITTED PLANS.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 PLUMBING
 (4)(6)(13): PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS FOR THE PROPOSED NEW H.C.
 BATHROOM AND DRINKING FOUNTAIN.
  
 **RESPONSE NOTED, HOWEVER PER OUR TELEPHONE
 CONVERSATION THE RESUBMITTED PLANS DO NOT SHOW THE
 PARTS OF THE RISER DIAGRAMS THAT ARE VISABLE AND PART
 OF THE NEW WORK ONLY.
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS EXISTING
 AND WHAT IS NEW ON THE RESUBMITTAL.
  
 **RESPONSE NOTED, HOWEVER PER OUR TELEPHONE
 CONVERSATION THE RESUBMITTED PLANS DO NOT SHOW PARTS OF
 THE RISER DIAGRAMS THAT ARE VISABLE AND PART OF THE NEW
 WORK ONLY.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 6. THE RESUBMITTED PLANS APPEAR TO BE THE SAME AS THE
 ORIGNAL SET OF PLANS. ALL CHANGES TO THE PLAN ARE TO BE
 CLOUDED WITH REVISION NUMBERS/DATES PER FBC-2004
 CHAPTER 1, SECTION 106.1.3 QUALITY OF BUILDING PLANS,
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By mperson Date 2008-07-18 Time 09:57 Rev Time 0.00
Received By mperson Date 2008-07-18 Time 09:57 Sent To  
Notes
2008-07-18 10:28:02PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET SP-1 PLUMBING FIXTURE CALCULATIONS: THE
 INDICATED PLUMBING CALCULATIONS ON THIS SHEET ARE
 WRONG. PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES FOR AN OCCUPANCY BROUP B-
 BUSSINESS ARE AS FOLLOWS.
  
 *WATER CLOSETS MALE/FEMALE= 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 *LAVATORIES MALE/FEMALE= 1 PER 40 FOR THE FIRST 50 AND
 1 PER 80 FOR THE REMAINDER EXCEEDING 50.
  
 *DRINKING FOUNTAIN= 1 PER 100.
  
 PLEASE CORRECT THESE CALCULATIONS ON THE RESUBMITTAL.
  
 2. SHEET A-2 DETAIL B, H.C. BATHROOM INT. ELEVATION:
 THE GRAB BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES
 MINIMUM. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE SECTION 11-4.16.4 GRAB BARS.
  
 3. SHEET A-2 DETAIL D-2, DRINKING FOUNTAIN DETAIL. PER
 FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 PLUMBING
 (4)(6)(13): PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS FOR THE PROPOSED NEW H.C.
 BATHROOM AND DRINKING FOUNTAIN.
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS EXISTING
 AND WHAT IS NEW ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-12-01 Cont ID  
Sent By jroach Date 2008-12-01 Time 17:29 Rev Time 0.00
Received By jroach Date 2008-12-01 Time 17:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By jroach Date 2008-11-04 Time 10:17 Rev Time 0.00
Received By jroach Date 2008-11-04 Time 10:16 Sent To  
Notes
2008-11-04 10:24:13***PROVISO***
  
 PRIOR TO THE FIRST INSPECTION, THE FOLLOWING SHALL
 OCCUR:
  
 1) SHEET SP-1 SHALL BE REVISED TO SHOW NO CURB
 INSTALLATION WITHIN THE ALLEY.
  
 2) A SECOND SET OF LANDSCAPE PLANS SHALL BE SUBMITTED
 AND APPROVED FOR RECORD ON THE JOB SITE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-26 Cont ID  
Sent By jroach Date 2008-09-26 Time 16:23 Rev Time 0.00
Received By jroach Date 2008-09-26 Time 16:23 Sent To  
Notes
2008-09-26 16:39:37***FAILED***
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED. ONLY ONE (1) COPY WAS INCLUDED IN
 THE PACKAGE. ADDITIONALLY, THE SURVEY INDICATES THAT IT
 "SHALL NOT BE USED FOR CONSTRUCTION PURPOSES."
  
 2) THE APPLICATION FOR THE TREE ALTERATION PERMIT SHALL
 BE SUBMITTED TO ROBERT KUSSNER, CITY LANDSCAPE PLANNER,
 ON THE 5TH FLOOR OF CITY HALL....NOT BE SUBMITTED AS
 PART OF THE BUILDING PERMIT APPLICATION. ONCE APPROVED
 BY MR. KUSSNER, A COPY OF THE TREE ALTERATION PERMIT
 SHALL BE PROVIDED WITH THE BUILDING PERMIT APPLICATION,
 ALONG WITH TWO (2) COPIES OF THE PROPOSED LANDSCAPE
 PLANS.
  
 3) IT IS UNCLEAR AS TO WHICH IS THE LATEST SET OF
 PLANS. PLEASE ORGANIZE THE SUBMITTAL SUCH THAT THERE
 ARE TWO (2) SETS OF THE LATEST DRAWINGS, AS WELL AS ONE
 (1) SET OF ALL OLD, VOIDED SHEETS.
  
 4) THE SITE PLAN WAS NOT REVISED TO SHOW THE LABELING
 OF EXISTING VS. PROPOSED. SEE COMMENT FROM ORIGINAL
 REVIEW.
  
 5) NO NOTE WAS ADDED TO THE PLANS INDICATING THAT THE
 FENCE WOULD BE BLACK PVC COATED. SEE COMMENT FROM
 ORIGINAL REVIEW.
  
 6) NO CURB DETAIL WAS PROVIDED AND CURBING IS NOT SHOWN
 ON THE SITE PLAN OR LANDSCAPE PLAN. SEE COMMENT FROM
 ORIGINAL REVIEW.
  
 7) NO STIRPING DETAIL WAS PROVIDED. SEE COMMENT FROM
 ORIGINAL REVIEW.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By jroach Date 2008-07-17 Time 14:59 Rev Time 0.00
Received By jroach Date 2008-07-17 Time 14:59 Sent To  
Notes
2008-07-17 15:41:49***FAILED***
  
 1) AS THE PERMIT VALUE EXCEEDS $5,000, THE ENTIRE
 PROPERTY IS REQUIRED TO BE BROUGHT INTO COMLIANCE WITH
 THE CITY'S LANDSCAPE CODE (ARTICLE XIV OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS).A LANDSCAPE
 PLAN SHALL BE PROVIDED SHOWING COMPLIANCE WITH THE
 LANDSCAPE CODE, AND SHALL BE SIGNED/SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT.
  
 2) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE
 PROVIDED.
  
 3) A COMPLETED AND APPROVED EASEMENT CONSENT FORM SHALL
 BE PROVIDED FOR THE INSTALLATION OF THE NEW FENCING.
 THIS FORM SHALL BE APPROVED BY THE CITY'S PUBLIC
 UTILITIES DEPARTMENT (SUBMIT TO 1ST FLOOR OF CITY
 HALL).
  
 4) PLEASE LABEL ITEMS ON THE SITE PLAN AS EXISTING OR
 NEW...SOME ITEMS ARE UNCLEAR.
  
 5) IF CHAIN LINK IS TO BE USED IN THE REAR OF THE
 PROPERTY, IT SHALL BE BLACK PVC COATED AND SHALL BE
 COMBINED WITH THE INSTALLATION OF A HEDGE.
  
 6) PLEASE PROVIDE THE ELEVATION OF THE NEW CONCRETE
 LANDING AT THE REAR OF THE STRUCTURE.
  
 7) "TYPE D" CURBING SHALL BE PROVIDED AROUND ALL NEW
 VEHICULAR AREAS TO PREVENT ENCROACHMENT INTO THE
 LANDSCAPING.
  
 8) A STRIPING DETAIL SHALL BE PROVIDED FOR THE NEW
 PARKING (SEE ATTACHED).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.