Plan Review Details - Permit 08060669
Plan Review Stops For Permit 08060669
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-04 Cont ID  
Sent By mjacobs Date 2008-09-04 Time 14:18 Rev Time 0.00
Received By mjacobs Date 2008-09-04 Time 14:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-20 Cont ID  
Sent By mjacobs Date 2008-08-20 Time 17:10 Rev Time 0.00
Received By mjacobs Date 2008-08-20 Time 16:18 Sent To  
Notes
2008-08-20 17:10:00BUILDING PLAN REVIEW
 PERMIT: 08060669
 ADD: 400 N. FLAGLER DR. #605
 CONT: HAWKES & DANIEL CONSTRUCTION
 TEL: (561)315-2525
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 **NO COMMENT NOT ADDRESSED**
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 NO INFORMATION WAS SUBMITTED FOR THE SOFFITS. ELEVATION
 DETAILS REQUIRED. WHAT IS THE NEW OPENING DIMENSIONS?
 5)PROVIDE ELEVATION DETAILED ARCHITECTURAL DRAWINGS
 TO CLEARLY SHOW THE WORK. WILL BE SOFFIT BE INSTALLED
 THROUGHOUT THE SPACE?SUBMIT THE FRAMING DETAILS FOR
 THE NEW WALLS AND SOFFITS SHOWING THE STRUCTURAL
 ATTACHMENTS AND ALL MATERIALS.
  
 6)OK
 7)OK
 8)OK.
 9)OK
  
 **NO COMMENT NOT ADDRESSED**
 10) 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492. PROVIDE INFORMATION MEETING THIS REQUIREMENT OR
 INDICATE ON THE PLANS THE TYPE OF CORK WHICH WILL BE
 USED UNDER THE TILES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By mjacobs Date 2008-07-14 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2008-07-14 Time 10:23 Sent To PC
Notes
2008-07-14 12:21:55BUILDING PLAN REVIEW
 PERMIT: 08060669
 ADD: 400 N. FLAGLER DR. #605
 CONT: HAWKES & DANIEL CONSTRUCTION
 TEL: (561)315-2525
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)PROVIDE DETAILED ARCHITECTURAL DRAWINGS TO CLEARLY
 SHOW THE WORK. WILL BE SOFFIT BE INSTALLED THROUGHOUT
 THE SPACE?SUBMIT THE FRAMING DETAILS FOR THE NEW
 WALLS AND SOFFITS SHOWING THE STRUCTURAL ATTACHMENTS
 AND ALL MATERIALS.
  
 6)THE DRAWINGS SHALL BE SIGN AND DATED BY THE PERSON
 TAKING RESPONSIBILITY. IF THE DESIGN PROFESSIONAL IS
 AND ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE
 LAWS OF THIS STATE, HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWING
 SPECIFICATION AND ACCOMPANYING DATA AS REQUIRED BY
 FLORIDA STATUTES 471 AND 481. FBC 106.1.
  
 7)106.1.3 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
 8)INDICATE THE OCCUPANCY OF THE BUILDING PER CHAPTER
 3 AND THE TYPE OF BUILDING PER CHAPTER 6 AND TABLE
 601.
  
 9)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 ELECTRIC, INTERIOR FINISH, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COST, OVERHEAD AND PROFIT EXCLUDING
 LAND.
  
 10) 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492. PROVIDE INFORMATION MEETING THIS REQUIREMENT OR
 INDICATE ON THE PLANS THE TYPE OF CORK WHICH WILL BE
 USED UNDER THE TILES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-29 Cont ID  
Sent By btrobaug Date 2008-08-29 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2008-08-29 Time 12:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 11:24 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 10:51 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By btrobaug Date 2008-06-26 Time 10:59 Rev Time 0.00
Received By btrobaug Date 2008-06-26 Time 10:54 Sent To  
Notes
2008-06-26 10:59:34 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} THE DESCRIPTION ON THE APPLICATION INDICATES
 ELECTRICAL WORK BEING DONE, BUT NO ELECTRICAL PLANS
 WERE SUBMITTED FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-04 Cont ID  
Sent By mwennerg Date 2008-09-04 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2008-09-04 Time 14:26 Sent To  
Notes
2008-09-04 14:26:50STAMPED NEW SHEET A-1. (2)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-18 Cont ID  
Sent By mawillia Date 2008-08-18 Time 12:32 Rev Time 0.00
Received By mawillia Date 2008-08-18 Time 12:23 Sent To  
Notes
2008-08-18 12:30:40*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;SINGLE PLAN SHEET A-1 STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By mwennerg Date 2008-07-09 Time 14:00 Rev Time 0.00
Received By mwennerg Date 2008-07-09 Time 14:00 Sent To  
Notes
2008-07-09 14:05:00***DENIED***
  
 1) WORK TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) SEE ELECTRICAL COMMENT #1 REGARDING REQUIREMENTS FOR
 DRAWINGS.
  
 3) CLEARLY IDENTIFY THE SCOPE OF WORK. THIS IS
 DIFFICULT TO DETERMINE ON THESE DRAWINGS.
  
 4) NEW SOFFITS SHALL NOT OBSTRUCT OR INTERFERE WITH THE
 EXISTING FIRE PROTECTION SYSTEM IF APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 08:45 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 08:45 Sent To E
Notes
2008-08-26 08:48:20TO "ELECT" BILL T.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 13:46 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 13:46 Sent To  
Notes
2008-08-15 16:04:18TO "BOB"#5
2008-08-08 13:46:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-14 Time   Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 11:51 Sent To  
Notes
2008-06-25 11:54:43TO "BOB"#17

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By choops Date 2008-06-26 Time 14:37 Rev Time 0.00
Received By choops Date 2008-06-26 Time 14:37 Sent To  
Notes
2008-06-26 14:37:45*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved