Plan Review Details - Permit 08060582
Plan Review Stops For Permit 08060582
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-01 Cont ID  
Sent By jwitmer Date 2008-12-01 Time 15:37 Rev Time 0.55
Received By jwitmer Date 2008-12-01 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 09:55 Rev Time 0.55
Received By jwitmer Date 2008-10-20 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 15:31 Rev Time 1.11
Received By jwitmer Date 2008-07-09 Time 15:31 Sent To  
Notes
2008-07-09 15:36:19BUILDING PLAN REVIEW
 PERMIT: 08060582
 ADD: 10130 NORTHLAKE BLVD
 CONT: POWER SOURCE
 TEL: (919)818-8700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3) PLANS INDICATE ON SHEET E7 THE CONCRETE FOUNDATION
 AND SLAB BUT FAIL TO PROVIDE ATTACHMENT OF THE
 GENERATOR AND BELLY TANK. 1609.1.3 MOMMENT AGAINST
 OVERTURNING, UPLIFT AND SLIPPAGE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By btrobaug Date 2008-11-04 Time 15:17 Rev Time 0.00
Received By btrobaug Date 2008-11-04 Time 13:47 Sent To PC
Notes
2008-11-06 11:02:38 
  
  
  
  
 PROVISO
  
 250.32(B)(2) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE
 BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS
 METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH
 BUILDING OR STRUCTURE INVOLVED, AND (3) GROUND-FAULT
 PROTECTION OF EQUIPMENT HAS NOT BEEN INSTALLED ON THE
 SUPPLY SIDE OF THE FEEDER(S), THE GROUNDED CONDUCTOR
 RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE SHALL
 BE CONNECTED TO THE BUILDING OR STRUCTURE DISCONNECTING
 MEANS AND TO THE GROUNDING ELECTRODE(S) AND SHALL BE
 USED FOR GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES,
 OR FRAMES REQUIRED TO BE GROUNDED OR BONDED.---IF THESE
 CONDITIONS ARE NOT MET, AN EQUIPMENT GROUND MUST BE
 INSTALLED WITH THE FEEDERS, AND THE NEUTRAL ISOLATED
 INTHE EXISTING MAIN SWITCHGEAR.
2008-11-04 15:16:25 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By btrobaug Date 2008-07-17 Time 13:29 Rev Time 0.00
Received By btrobaug Date 2008-07-15 Time 08:26 Sent To  
Notes
2008-07-17 13:29:05 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE MANUFACTURERS SPECIFICATIONS REQUESTED IN THE
 PRIOR REVIEW, COMMENT #3, WERE NOT SUBMITTED, THE
 SCHEMATIC ON SHEET E2 DOES NOT CLEARLY INDICATE
 COMPLIANCE WITH 230.76 OR 225.31, 32. PLEASE SUBMIT
 SAME.
  
 2} SHEET E5 INDICATES A BONDING JUMPER IN THE EXISTING
 SWITCHGEAR IN VIOLATION OF 250.24(A)(5) "LOAD-SIDE
 GROUNDING CONNECTIONS A GROUNDING CONNECTION SHALL NOT
 BE MADE TO ANY GROUNDED CONDUCTOR ON THE LOAD SIDE OF
 THE SERVICE DISCONNECTING MEANS EXCEPT AS OTHERWISE
 PERMITTED IN THIS ARTICLE." THE NEUTRALS AND GROUNDS
 MUST BE SEPARATED IN THE EXISTING SWITCHBOARD AS THE
 APS IS NOW THE FIRST MEANS OF DISCONNECT. ALSO SEE
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS
 AND 250.32(B)(1)----- "ANY INSTALLED GROUNDED CONDUCTOR
 SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING
 CONDUCTOR OR TO THE GROUNDING ELECTRODE(S).
  
 3} THE RESPONSE TO COMMENT #4 FROM THE PEVIOUS REVIEW
 WAS NOT CLEAR, SEE COMMENT #1.
  
 4} VERIFY THAT 250 MCM EQUIPMENT GROUND COMPLIES WITH
 250.122(F)(1). THIS WOULD DEPEND ON THE AMPERAGE RATING
 OF THE OCP. SEE COMMENT #1.
  
 5} THE NOTE "E" SHEET E5, SYSTEM GROUNDING LEGEND AND
 NOTE "9" SHEET E2 REGARDING ARTICLE 250.32(A)(2) AND
 USING THE NEUTRAL AS THE GROUND TO THE BUILDING IS NOT
 ALLOWED. ARTICLE 250.32(B)(2) STATES " GROUNDED
 CONDUCTOR WHERE (1) AN EQUIPMENT GROUNDING CONDUCTOR IS
 NOT RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE,
 (2) THERE ARE NO CONTINUOUS METALLIC PATHS BONDED TO
 THE GROUNDING SYSTEM IN EACH BUILDING OR STRUCTURE
 INVOLVED". CONDITION #2 CANNOT BE MET . SEE E6"SYSTEM
 CONTROL WIRING, AND SHEET E4 INDICATING CONTROL WIRING
 RUNING BETWEEN THE STRUCTURE AND THE BUILDING AN
 EQUIPMENT GROUND PER 250.122 IS REQUIRED, MAKING
 COMMENT #2 A REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-03 Cont ID  
Sent By mawillia Date 2008-11-03 Time 13:15 Rev Time 0.00
Received By mawillia Date 2008-11-03 Time 13:02 Sent To  
Notes
2008-11-03 13:15:40*****APPROVED******
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS E1.1, E4.1, & SD1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By mawillia Date 2008-07-23 Time 15:02 Rev Time 0.00
Received By mawillia Date 2008-07-23 Time 14:37 Sent To  
Notes
2008-07-23 14:58:54*****DENIED******
  
  
 1. THE SCOPE OF WORK SHALL NOT INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE BUILDING(S) OR THE VICINITY
 THEREOF (INCLUDING FIRE LANES) .
  
 2. PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3. STATIONARY GENERATORS USED FOR EMERGENCY OR STANDBY
 POWER SHALL BE INSTALLED , TESTED, AND MAINTAINED TO
 COMPLY WITH NFPA 110.
  
 4. DIESEL FUEL STORAGE SHALL COMPLY WITH NFPA 30.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-07-17 Cont ID  
Sent By tgordon Date 2008-07-17 Time 14:05 Rev Time 0.20
Received By tgordon Date 2008-07-17 Time 14:05 Sent To  
Notes
2008-07-17 14:05:36*** PROVISO ***
 1) FUEL STORAGE TANK MUST BE A MINIMUM OF 5 FEET FROM
 THE BUILDING, PER NFPA 30 4.3.2.1.1.
  
 2) THE GENERATOR MUST BE A MINIMUM OF 5 FEET FROM ANY
 BUILDING OPENINGS, PER NFPA 37 4.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 09:13 Sent To  
Notes
2008-11-14 09:14:12TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 10:08 Sent To  
Notes
2008-10-02 10:10:56TO "COMM" BD#61

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-23 Cont ID  
Sent By mawillia Date 2008-07-23 Time 14:39 Rev Time 0.00
Received By mawillia Date 2008-06-23 Time 09:20 Sent To  
Notes
2008-06-24 16:18:52TO "COMM" BD#60
2008-06-23 09:21:49WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-17 Cont ID  
Sent By tgordon Date 2008-07-17 Time 13:54 Rev Time 0.20
Received By tgordon Date 2008-07-17 Time 13:54 Sent To  
Notes
2008-07-17 14:04:23*** PROVISO ***
 1) FUEL STORAGE TANK MUST BE A MINIMUM OF 5 FEET FROM
 THE BUILDING, PER NFPA 30 4.3.2.1.1.
 2) THE GENERATOR MUST BE A MINIMUM OF 5 FEET FROM ANY
 BUILDING OPENINGS, PER NFPA 37 4.1.4.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-25 Cont ID  
Sent By jroach Date 2008-11-25 Time 18:57 Rev Time 0.00
Received By jroach Date 2008-11-25 Time 18:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-16 Cont ID  
Sent By jroach Date 2008-10-16 Time 17:00 Rev Time 0.00
Received By jroach Date 2008-10-16 Time 17:00 Sent To  
Notes
2008-10-16 19:47:07***FAILED***
  
 1) PLEASE SPECIFY THE TYPE OF LANDSCAPING PROPOSED. THE
 CITY'S LANDSCAPE PLANNER RECOMMENDS THE INSTALLATION OF
 PODOCARPUS. IF IT RESULTS WHERE THIS IS THE ONLY
 OUTSTANDING COMMENT, IT MAY BE INCLUDED AS A PROVISO.
  
 THE FOLLOWING COMMENTS ARE NEWLY-GENERATED AS A RESULT
 OF THE NEW PROPOSED LOCATION OF THE GENERATOR:
  
 1) THE GENERATOR CANNOT BE LOCATED WHERE PROPOSED AS IT
 CONFLICTS WITH EXISTING TREES IN THE LANDSCAPE ISLAND.
 THESE TREES ARE REQUIRED AS PART OF THE SITE PLAN AND
 SHALL NOT BE REMOVED. WHY WAS THE GENERATOR RELOCATED?
 ZONING HAD NO OBJECTION TO THE LOCATION OF THE
 GENERATOR ADJACENT TO THE BUILDING...ALL THE NEEDED TO
 BE DONE WAS SCREEN THE GENERATOR WITH A FENCE/WALL,
 LANDSCAPE AROUND THE WALL, AND PROTECT THE LANDSCAPING
 VIA A CURB. PLEASE CONTACT ME REGARDING THIS ISSUE TO
 TRY AND WORK OUT A LOCATION THAT WILL BE SUFFICIENT FOR
 ALL PARTIES.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By jroach Date 2008-07-14 Time 12:50 Rev Time 0.00
Received By jroach Date 2008-07-09 Time 17:31 Sent To  
Notes
2008-07-14 13:35:14***FAILED***
  
 1) THE DRIVE AISLE ADJACENT TO THE GENERATOR WILL NEED
 TO BECOME ONE-WAY, AS IT WILL ONLY BE 15 FEET IN WIDTH.
 I SUGGEST THAT A "DO NOT ENTER" SIGN BE INSTALLED IN
 THE LANDSCAPE ISLAND TO PREVENT PEOPLE FROM DRIVING
 SOUTH THROUGH THE AISLE (SEE ATTACHED SKETCH FOR
 LOCATION OF SIGN).
  
 2) AS NOTED PREVIOUSLY, ALL MECHANICAL EQUIPMENT WILL
 NEED TO BE SCREENED PURSUANT TO SECTION 94-444(B) OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS):
  
 A) THE PROPOSED PVC FENCE SHALL COMPLETELY ENCLOSE THE
 GENERATOR.
 B) THE FENCE SHALL BE LANDSCAPE WITH SHRUBS/HEDGES
 PLANTED AT 2 FOOT INTERVALS.
 C) THE SHRUBS/HEDGES SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY MEANS OF CURBING.
 D) THE SWITCHGEAR AND TRANSFORMER SHALL ALSO BE
 PROPERLY SCREENED.
  
 QUESTIONS/COMMENTS CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
2008-07-09 17:34:05PLANNING AND ZONING:
  
 CURRENTLY PENDING MINOR AMENDMENT REVIEW FROM THE
 PLANNING AND ZONING DEPT.
  
 ANY QUESTIONS, PLEASE CONTACT JOHN ROACH AT 822-1448.