2008-06-26 16:43:03 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| FACFLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| 1.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES FOR |
| BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING |
| ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER |
| AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| ORIGINALS FAC61G15-23.002. |
| |
| 2.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL. |
| |
| 3.PLEASE STATE OPENING SIZE, PANEL SIZE, AND PANEL |
| CONFIGURATION ON THE FLOOR PLAN.A AND F ARE SHOWN; |
| SLIDING GLASS DOORS USE X AND O TO INDICATE OPERABLE |
| AND FIXED PANELS.A AND F ARE NOT STANDARD |
| ABBREVIATIONS. |
| |
| 4.ON THE PRODUCT APPROVAL, CIRCLE GLASS/SIZE |
| OPTION(S).CODE COMPLIANCE CANNOT BE DETERMINED UNTIL |
| DESIGN PRESSURES AND SIZES ARE SPECIFIED, FBC16. |
| |
| 5.APPLICANT IS A BUILDING CONTRACTOR.HOW TALL IS |
| THIS BUILDING?PLEASE CONFIRM THAT THIS IS WITHIN THE |
| SCOPE OF CONTRACTOR'S LICENSE PRIOR TO RESUBMITTAL. |
| PAPA WEBSITE IS NOT AVAILABLE FOR ME TO CONFIRM. |
| |