Plan Review Stops For Permit 08060519 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2009-12-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-12-01 |
Time |
16:43 |
Rev Time |
4.50 |
Received By |
jwitmer |
Date |
2009-12-01 |
Time |
13:17 |
Sent To |
|
|
Notes |
2009-12-01 16:43:39 | BUILDING PLAN REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: WELLINGTON EQUESTRIAN | | TEL: (561)951-6729 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISIONS DATED: | | ARCHITECTURAL: REVISION# 4 NOV. 4/2009 | | STRUCTURAL: REVISION# 3 NOV.2/ 2009 | | | | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | | 1) SHEET A-1 THE FRONT ENTRY STAIRWAY REVISION# 2 HAS | | NOT BEEN UPDATED, THE REVISION SUBMITTED DOES INDICATE | | THE STEEL COLUMN IN THE STAIRWELL BUT THE EGRESS | | CALCULATIONS FOR BOTH THE STAIRS AND FRONT ENTRY | | INDICATE THE PERMIT SET OF EGRESS CALCULATIONS, NOT | | WHAT IS CURRENTLY BUILT. PLEASE REVISE PLANS INDICATING | | THE REVISED SSTAIR AND DOORWAY EGRESS CALCULATION FOR | | THE FRONT STAIR AND ENTRY. PLEASE INCLUDE THE UPDATED 1 | | HR RATED WALL ASSEMBLY WITH THE VERTICAL STEEL BEAMS | | LOCATED | | OUTSIDE OF THE 1 HOUR RATED ASSEMBLY. 1020.1.2 | | PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN | | EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT | | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION | | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT | | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING | | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE | | PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL | | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. | | | | PLEASE NOTE THE FIRST FLOOR ENTRY DOOR IS NOT LOCATED | | ON THE DOOR SCHEDULE LOCATED ON SHEET A-15. | | | | 2) SHEET A-2 THE FRONT ROOFTOP STAIRWAY LOCATED IN THE | | BOTTOM RIGHT CORNER OF THE SHEET INDICATES A NEW 3'-0" | | DOOR THAT LEADS INTO THE MECHANICAL ROOM LOCATED | | BENEATH THE THIRD FLOOR LEVEL. PLEASE REVIEW SECTIONS : | | VERTICAL EXIT ENCLOSURES | | 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE | | OPENING PROTECTIVE???S SHALL BE IN ACCORDANCE WITH THE | | REQUIREMENTS OF SECTION 715. | | | | EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN | | EXIT ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR | | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT | | ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES | | AND FOR EGRESS FROM THE ENCLOSURE. | | | | 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS | | THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR | | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY | | FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING | | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT | | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | SECTION 712. THERE SHALL BE NO PENETRATIONS OR | | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, | | BETWEEN ADJACENT EXIT ENCLOSURES. | | | | 3A) SHEET A-3 INDICATES A NEW DUMBWAITER, NOT NOTED ON | | THIS SHEET BUT S-2, S-3 AND S-29 INDICATE AS SUCH. | | PLEASE PROVIDE THE WALL TYPES TO BE ASSOCIATED WITH THE | | SHAFT CONSTRUCTION A-3 DOES PROVIDE SHAFT AND WALL | | TYPES BUT NO WALL SECTION TAG IS PROVIDED FOR THE | | BUMBWAITER.. 3002.1 HOISTWAY ENCLOSURE PROTECTION. | | ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES | | SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 707. | | 3002.1.1 OPENING PROTECTIVES. OPENINGS IN HOISTWAY | | ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. | | | | 3B) SHEET S-29 THE DUMBWAITER INDICATES HOW THE | | STRUCTURAL MEMBERS WILL BE INSTALLLED ON THE FIRST AND | | SECOND FLOOR BUT NO INFORMATION IS PROVIDED PAST THE | | SECOND FLOOR ROOF LINE. ADDITIONAL INFORMATION | | REQUIRED. | | | | 3C) 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS AND | | DUMBWAITERS PENETRATING MORE THAN THREE STORIES SHALL | | BE PROVIDED WITH A MEANS FOR VENTING SMOKE AND HOT | | GASES TO THE OUTER AIR IN CASE OF FIRE. | | | | 3D) PLEASE ALSO REVIEW SECTION 3006 FOR ELEVATOR | | MACHINE ROOMS SECTION 1-6. | | | | 3E) A-3 THE ORIGINAL ISSUED PLANS DOES INDICATE A THIRD | | FLOOR KITCHEN THE NEW REVISION INDICATES THE REMOVAL OF | | THE KITCHEN AND ADDITIONAL DINING AREA, PLEASE UPDATE | | THE OCCUPANCY LOADS FOR THE THIRD FLOOR AND EGRESS OF | | THE STAIRS, IF THIS FLOOR CONTAINS THE HIGHEST | | CONCENTRATION OF OCCUPANTS. TABLE 1004.1.1& TABLE | | 1005.1. | | | | 4) SHEET A-5 WEST ELEVATION THE OPENING PROTECTIVES, | | FIRE SHUTTERS ARE STILL INDICATED ON PLANS, THERE HAS | | BEEN RECENT DISCUSSION WITH THE CONTRACTOR, DESIGNER | | AND OWNER ABOUT THE ELIMINATION OF THE FIRE SHUTTERS | | AND THE USE OF A HINGED COLLASPABLE WALL SECTION THAT | | WAS SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW UNDER | | ALTERNATE MATERIALS AND METHODS, TO DATE NO FORMAL | | SUBMITTAL HAS BEEN BROUGHT IN TO THE CITY FOR REVIEW. | | 104.11 ALTERNATE MATERIALS, DESIGN OF METHODSOF | | CONSTRUCTION AND EQUIPMENT. | | | | 5) SHEET A-8.1 INDICATES CABANAS TO BE DETERMINED BY | | OWNER, A SEPERATE PERMIT REVIEW AND ASSOCIATED FEES | | WILL BE REQUIRED. NOTE WIND INFORMATION OF HOW CABANAS | | WILL MEET WIND LOADING: WIND DESIGN SEECTION 1609. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2009-06-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-06-11 |
Time |
16:00 |
Rev Time |
1.66 |
Received By |
jwitmer |
Date |
2009-06-11 |
Time |
14:20 |
Sent To |
|
|
Notes |
2009-06-11 15:52:12 | BUILDING PLAN REVIEW- | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: WELLINGTON EQUSTRIAN | | TEL: (561)248-3403 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 6-11-09 | | 5TH REVIEW: | | BUILDING PROVISOS: | | 1)PROVIDE DOCUMENTATION FOR MCKEON RETRACTABLE FIRE | | SHUTTER 1 1/2 HR MODEL FSFD-M | | | | 2) BUILDING PROVISO: | | PROVIDE PRODUCT APPROVALS FOR : | | 2A) LOUVER- WOOD LOUVER @ GAZEBO | | 2B) STANDING SEAM METAL ROOF | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | SURVEY: | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2009-06-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-06-01 |
Time |
10:19 |
Rev Time |
1.10 |
Received By |
jwitmer |
Date |
2009-06-01 |
Time |
09:33 |
Sent To |
|
|
Notes |
2009-06-01 10:37:07 | BUILDING PLAN REVIEW- MAJOR WORKING DRAWING REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: PLAN REVIEW- CON JOHN WEBB | | TEL: (561)312-6247 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 6-01-09 | | 4TH REVIEW: | | | | 1) MISSING 2HR FIRE SHUTTER REQUIRED AS PER TABLE 602/ | | TABLE 704.2 FIRE SHUTTER WILL ALSO NEED REPORTS FOR | | WIND LOADING, PLEASE PROVIDE. SHEET A-5 INDICATES | | FRAMING OF THE OPENINGS, IF THE PRODUCT APPROVALS DOES | | NOT PROVIDE ATTACHMENT OF THE SHUTTER TO THE WALL | | FRAMING THIS ATTACHMENT DETAILS WILL ALSO BE REQUIRED | | FOR PERMIT. ALSO PROVIDE POSITIVE AND NEGATIVE | | PRESSURES FOR THESE OPENINGS. | | | | 2) BUILDING PROVISO: | | 2A) LOUVER- WOOD LOUVER @ GAZEBO | | 2B) STANDING SEAM METAL ROOF | | | | 3) PROVISO: SHEET A-3 VERSES S-6 THE GAZEBOS WEST WALL | | ( KITHEN) DOES NOT SHOW UP ON THE STRUCTURAL PLANS WILL | | NEED REVISION. | | | | 4)PROVISO: RED LINED A-11 DETAIL# 7 STAIR RISER | | INDICATED AS 7" MINIMUM, TYPO 7" MAXIMUM RISER 1009.3. | | | | 5) COMPLIED. | | | | 6)PROVISO: STRUCTURAL SHEET S8 NOR S22 PROVIDE NAILING | | FOR THE T&G 3/4" ROOF SHEATHING. COMPONENTS AND | | CLADDING, ROOF DECK IS ABOVE 50'. | | | | 7-8 ) COMPLIED. | | | | 9) ONCE PERMIT APPLICATION IS MADE RADON FEES FOR 7,650 | | SQ FT TO BE ADDED . | | | | 10) | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 11) THRESHOLD BUILDING: | | | | 11A) COMPLIED: THRESHOLD INSPECTION PLAN FL S. S. | | 553.71(7) | | | | 11B) ONCE CONTRACTOR IS SIGNED ON THE SPECIAL INSPECTOR | | WILL NEED TO BE SIGNED. | | THRESHOLD INSPECTOR: | | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | CODE. CONTACT THE BUILDING OFFICIAL DOUG WISE FOR A | | MEETING FOR THE SPECIAL INSPECTOR PROGRAM AT | | (561)805-6654 FOR FURTHER INFORMATION | | | | 12) CONTRACTOR TO APPLY FOR PERMIT. | | | | NOTE: SPECIAL INSPECTOR FORMS ATTACHED TO BUILDING | | COMMENTS THIS REVIEW. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2009-05-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-05-19 |
Time |
12:42 |
Rev Time |
4.75 |
Received By |
jwitmer |
Date |
2009-05-19 |
Time |
08:00 |
Sent To |
|
|
Notes |
2009-05-19 16:57:40 | BUILDING PLAN REVIEW- MAJOR WORKING DRAWING REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: PLAN REVIEW- CON JOHN WEBB | | TEL: (561)312-6247 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 5-19-09 | | 3RD REVIEW: | | | | 1) MISSING 2HR FIRE SHUTTER REQUIRED AS PER TABLE 602/ | | TABLE 704.2 | | | | 2) BUILDING PROVISO: | | 2A) LOUVER- WOOD LOUVER @ GAZEBO | | 2B) STANDING SEAM METAL ROOF | | | | 3) PROVISO: SHEET A-3 VERSES S-6 THE GAZEBOS WEST WALL | | ( KITHEN) DOES NOT SHOW UP ON THE STRUCTURAL PLANS WILL | | NEED REVISION. | | | | 4) RED LINED A-11 DETAIL# 7 STAIR RISER INDICATED AS 7" | | MINIMUM, TYPO 7" MAXIMUM RISER 1009.3. | | | | 5) SHEET A-12 DETAIL A/B WILL REQUIRE A 2 HR FIRE | | RATING DETAIL, I SPOKE WITH KELLY YATES TODAY HE WILL | | BE BRINGING OVER SHORTLY.PROVISO. | | | | 6) STRUCTURAL SHEETS DO NOT PROVIDE NAILING FOR THE T&G | | 3/4" ROOF SHEATHING. COMPONENTS AND CLADDING, ROOF DECK | | IS ABOVE 50', PROVISO. | | | | 7) SHEET S-22 DESIGNED TO ASCE 7-05 2007 FBC, THIS PLAN | | WILL BE CONSIDERED TO BE DESIGNED UNDER THE 2004 FBC | | WITH 2007 SUPPLEMENTS, NEEDS TO BE UPDATED. | | | | 8) SPOKE WITH ALLEN PRESSURE ZONE 2 CORRECT. | | | | 9) ONCE PERMIT APPLICATION IS MADE RADON FEES FOR 7,030 | | SQ FT TO BE ADDED . | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 11) THRESHOLD BUILDING: | | | | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | THE | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA | | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | WITH THE PERMITTED DOCUMENTS. | | | | THRESHOLD INSPECTOR: | | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | CODE. | | CONTACT THE BUILDING OFFICIAL DOUG WISE FOR A MEETING | | FOR THE SPECIAL INSPECTOR PROGRAM AT (561)805-6654 FOR | | FURTHER INFORMATION | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-10-21 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-10-21 |
Time |
13:29 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-10-20 |
Time |
16:01 |
Sent To |
|
|
Notes |
2008-10-21 13:43:00 | BUILDING PLAN REVIEW- MAJOR WORKING DRAWING REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: PLAN REVIEW- CON JOHN WEBB | | TEL: (561)312-6247 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | PLANS ARE CODE COMPLIANT, UNTIL CONTRACTOR MAKES | | APPLICATION FOR THE STRUCTURAL PERMIT AND: | | | | 1) CGC CONTRACTOR MAKE APPLICATION FOR PERMIT AND PAYS | | FEES FOR THE STRUCTURAL PORTION OFTHE BUILDING | | | | 2) CONTRACTOR PAYS RADON FEES FOR 7650 SQ FT | | | | 3) CONTRACTOR TAKES THE PLANS TO PALM BEACH COUNTY | | BUILDING DEPARTMENT FOR COUNTY IMPACT FEE ASSESSMENT, | | | | 4) CONTRACTOR TO SET MEETING WITH SUPERVISOR KEN CONRAD | | , AND THRESHOLD INSPECTOR FOR MORE INFORMATION PLEASE | | CONTACT MR. CONRAD AT (561)805-6666 FOR TIME, LOCATION | | AND REQUIRED ATTENDANCE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-27 |
Time |
14:24 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2008-08-27 |
Time |
14:24 |
Sent To |
|
|
Notes |
2008-08-27 14:25:25 | BUILDING PLAN REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: PLAN REVIEW CON JOHN WEBB | | TEL: (561)312-6247 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. 2 COPIES OF | | RESPONCE COMMENTS WERE SUBMITTED AND COMMENTS 1 & 2 | | WERE ONLY RESPONDED TOO. | | | | 1B) COMPLIED, 3 SETS OF DOCUMENTS SUBMITTED, THRESHOLD | | BUILDING BECAUSE OF OCCUPANT LOAD. | | | | 1C) INFORMATIONAL | | | | 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME | | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE | | 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.NOTE THIS | | IS AN ADDITION AND THE 2004 EXISTING BUILDING CODE | | CHAPTER 9 WILL NEED TO BE ADDRESSED. SHEET DT-1 | | INDICATES A LEVEL II ALTERATION, THIS MAY BE TRUE FOR | | THE INTERIOR WORK UNDER ANOTHER PERMIT. THIS WORK IS TO | | BE COVERED UNDER 2004 EXISTING BUILDING CODE CHAPTER 9 | | ADDITIONS, PLEASE MAKE CORRECTIONS. | | | | 1F-H) COMPLIED. | | | | 2) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT PROVIDED | | WHAT THE BASE DESIGN IS FOR WIND IN SHEETS A-1- A-4. | | PLANS ARE MISSING THE WIND DESIGN CRITERIA. 1603.1.4 | | WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO | | WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND | | LOADS GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING | | SYSTEM OF THE BUILDING: | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | (KM/HR). | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | DIRECTION SHALL BE INDICATED. | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | PROFESSIONAL. | | | | 3) 2ND REQUEST, THIS BUILDING IS CLASSIFIED AS A | | THRESHOLD BUILDING BECAUSE THE OCCUPANT LOAD IS GREATER | | THAN 500 OCUPANTS. | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | THE | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA | | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | 3A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | 3B) THRESHOLD INSPECTOR: | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | INFORMATION BEFORE | | THE PERMIT MAY BE ISSUED. | | | | 3C) COMPLIED. | | | | 4)SOILS REPORTS COMPLIED. | | | | 5) 2ND REQUEST, THE PLANS INDICATE TWO DIFFERENT | | ENGINEERS IT APPEARS THAT ONE WILL BE A SPECIALTY | | ENGINEER AND THE OTHER THE ENGINEER OF RECORD FOR THE | | PROJECT, OR TO TAKE RESPONSIBILITY FOR THE PROJECT. THE | | DESIGNER OF RECORD WILL NEED TO REVIEW ALL SHOP | | DRAWINGS AND APPLY THEIR SHOP DRAWING STAMP ONCE PLANS | | ARE REVIEWED AND APPROVED. FL 61G1-23.015 (2) THE | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... | | | | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL | | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE | | ENGINEER OF RECORD FOR REVIEW. | | | | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-16 |
Time |
13:48 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2008-07-16 |
Time |
10:56 |
Sent To |
|
|
Notes |
2008-07-16 14:35:10 | BUILDING PLAN REVIEW | | PERMIT: 08060519 | | ADD: 309 CLEMATIS ST | | CONT: PLAN REVIEW CON JOHN WEBB | | TEL: (561)312-6247 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. 2 COPIES OF | | RESPONCE COMMENTS WERE SUBMITTED AND COMMENTS 1 & 2 | | WERE ONLY RESPONDED TOO. | | | | 1B) COMPLIED, 3 SETS OF DOCUMENTS SUBMITTED, THRESHOLD | | BUILDING BECAUSE OF OCCUPANT LOAD. | | | | 1C)INFORMATIONAL | | | | 1D )FL S S 713.13NOTICE OF COMMENCEMENT, TO BE | | FILED WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF | | THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) 2ND REQUEST,PLANS SUBMITTED FOR PERMIT (FIRST | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.NOTE | | THIS IS AN ADDITION AND THE 2004 EXISTING BUILDING CODE | | CHAPTER 9 WILL NEED TO BE ADDRESSED. SHEET DT-1 | | INDICATES A LEVEL II ALTERATION, THIS MAY BE TRUE FOR | | THE INTERIOR WORK UNDER ANOTHER PERMIT. THIS WORK IS TO | | BE COVERED UNDER 2004 EXISTING BUILDING CODE CHAPTER 9 | | ADDITIONS, PLEASE MAKE CORRECTIONS. | | | | 1F-H) COMPLIED. | | | | 2) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT PROVIDED | | WHAT THE BASE DESIGN IS FOR WIND IN SHEETS A-1- A-4. | | PLANS ARE MISSING THE WIND DESIGN CRITERIA. 1603.1.4 | | WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO | | WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND | | LOADS GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING | | SYSTEM OF THE BUILDING: | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | (KM/HR). | | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | DIRECTION SHALL BE INDICATED. | | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | PROFESSIONAL. | | | | 3) 2ND REQUEST,THIS BUILDING IS CLASSIFIED AS A | | THRESHOLD BUILDING BECAUSE THE OCCUPANT LOAD IS GREATER | | THAN 500 OCUPANTS. | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | THE | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA | | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | 3A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | 3B) THRESHOLD INSPECTOR: | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | CODE. CONTACT KEN CONRADMANAGER OF THE SPECIAL | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | INFORMATION BEFORE | | THE PERMIT MAY BE ISSUED. | | | | 3C) COMPLIED. | | | | 4)SOILS REPORTS COMPLIED. | | | | 5) 2ND REQUEST, THE PLANS INDICATE TWO DIFFERENT | | ENGINEERS IT APPEARS THAT ONE WILL BE A SPECIALTY | | ENGINEER AND THE OTHER THE ENGINEER OF RECORD FOR THE | | PROJECT, OR TO TAKE RESPONSIBILITY FOR THE PROJECT. THE | | DESIGNER OF RECORD WILL NEED TO REVIEW ALL SHOP | | DRAWINGS AND APPLY THEIR SHOP DRAWING STAMP ONCE PLANS | | ARE REVIEWED AND APPROVED.FL 61G1-23.015 (2) THE | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... | | | | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL | | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE | | ENGINEER OF RECORD FOR REVIEW. | | | | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2009-12-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-12-02 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-12-02 |
Time |
11:53 |
Sent To |
|
|
Notes |
2009-12-02 15:30:46 | | | | | ELECTRICAL APPROVED WITH EXCEPTION. | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. A REVISION | | IS REQUIRED CORRECTING THE LISTED DEFICIENCIES THIS | | PLAN PRIOR TO INSPECTION, OR A REINSPECTION FEE WILL | | RESULT. | | | | 1} THE SOUTH STAIRWAY SHOWN ON SHEET E-2 DOES NOT MATCH | | SHEET A-2.0.CORRELATE SAME. IF THE DOORS SHOWN ON SHEET | | A-2.0ARE TO BE INSTALLED LOCATE THE EXIT SIGNS FOR | | SAME. | | | | 2} THE FIXTURE COUNT AND TYPES ON THE SCHEDULE DO NOT | | CORRELATE WITH THE THE ONES ON THE FLOOR PLAN SHEETS | | E-2, 4, 5 AND 11. NEW FIXTURES HAVE BEEN ADDED BUT THE | | LIGHTING POWER DENSITIES REMAIN THE SAME AS THE PERMIT | | SET OF PLANS. RECALCULATE THE DENSITIES TO MATCH WITH | | THE PROPOSED FIXTURES. | | | | 3} SHEETS E-9 & 10 PHOTOMETRICS DID NOT CHANGE TO | | REFLECT THE NEW FIXTURE WATTAGES, CORRECT SAME. | | | | 4} TYPE "P-1" FIXTURES ARE NOT LISTED ON THE SCHEDULE. | | | | 5} THE ROOM LABELED "STORAGE" AT THE SERVICE BAR, | | SHEETS E-3, 4, AND 5 , WAS LABELED "BEER" AND PRESUMED | | TO BE A COOLER ON THE PERMIT SET OF PLANS NO COMPRESSOR | | FOR THAT UNIT APPEARS IN THE PANEL SCHEDULES. PLEASE | | CLARIFY.. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2009-11-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-11-23 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-11-23 |
Time |
09:01 |
Sent To |
FIRE |
|
Notes |
2009-11-23 13:13:31 | TO CAPTAIN WILLIAMS./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-09-23 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-09-23 |
Time |
09:53 |
Sent To |
|
|
Notes |
2009-09-23 09:53:40 | | | ** DENIED ** | | | | ** ** REVIEW DONE AT THE REQUEST OF THE BUILDING | | OFFICIAL FOR PREVIOUS REVIEWER. | | | | 1) NOTE: PLANS SUBMITTED DO NOT MATCH. THE REVISED | | SHEET E-2 SUBMITTED IS COMPLETELY DIFFERENT FORM | | PREVIOUS SHEET E-2. IN FACT IT IS FOR A DIFFERENT FLOOR | | ALTOGETHER. THE TITLE BLOCK INDICATES A REVISION DATE | | OF 8/20/08 YET NO REVISIONS WERE MADE TO PLANS | | COORDINATING WITH ANY NEW CHANGES FOR ELECTRICAL. | | PLEASE KNOW THAT EVEN THE PREVIOUS E-3 SHEET HAS A | | DIFFERENT FLOOR LAYOUT FOR POWER ETC. | | THE R2 PANEL SCHEDULE INDICATES PANEL AS *EXISTING* YET | | THE FILE SET OF PLANS INDICATES THIS PANEL AS NEW. | | | | 2) NOTE: PLEASE SUBMIT ACCURATE LOAD CALCULATIONS. LOAD | | CALCULATIONS STATE PER NEC 220.87 FOR EXISTING LOADS. | | HOWEVER HOW CAN THIS BE POSSIBLE WHEN THE NEW PANEL R2 | | WAS ONLY JUST PERMITTED AND NOT YET INSTALLED? HOW | | COULD THERE BE AN 24 MONTH DEMAND FROM FPL WHEN THE | | PERMITTED LOAD/ADDITION OF FLOOR AND ALL OTHER | | ELECTRICAL SYSTEMS ON PREVIOUS SUBMITTED PLANS HAVE NOT | | YET BEEN INSTALLED TO DATE. | | | | *** IT IS TO BE CLEAR THAT THE FILE SET OF PLANS WERE | | NOT REVIEW FOR CODE COMPLIANCE BY THIS REVIEWER. ONLY | | THE SHEET E-2, E-3 AND PANEL SCHEDULES WERE LOOKED AT | | FOR THERE RELEVANT CONTENTS BASED ON THE COORDINATION | | OF REVISED DOCUMENTS SUBMITTED. | | | | ** IT SHOULD ALSO BE CLEAR THAT AS THERE IS INFORMATION | | NOT YET SHOWN, REVISED OR MISSING ON PLANS THERE MAY BE | | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT | | POSSIBLE BE MADE AT THIS TIME. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
Sent By |
dwise |
Date |
2009-05-28 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
dwise |
Date |
2009-07-09 |
Time |
16:23 |
Sent To |
|
|
Notes |
2009-07-09 16:24:51 | PLANS REVIEWED BY BILL TROBAUGH. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2009-11-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-11-20 |
Time |
07:41 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-11-20 |
Time |
07:29 |
Sent To |
|
|
Notes |
2009-11-20 07:41:20 | REVISIONS | | | | 1. ROOF ACCESS DOOR TO INTERSTITIAL SPACE IS NOT | | ALLOWED WHICH IS SHOWN ON PAGE A-2.0. THIS OPENING IS | | TO BE SEALED WITH THE PROPER FIRE RATING OF THE EXIT | | ENCLOSURE FOR WHICH IT IS LOCATED. | | | | 2. A NEW FIRE DEPARTMENT CONENCTION WAS TO HAVE BEEN | | INSTALLED ON THE SOUTH SIDE OF THE BUILDING TO REPLACE | | THE EXISTING SNOOT. THE NEW DOUBLE FIRE DEPARTMENT | | CONNECTION IS TO BE LOCATED WITHIN 150 FEET OF A FIRE | | HYDRANT. THE PLAN SEEM TO SUUEST THAT THE FIRE | | DEPARTMENT CONNECTION WILL BE PLACED ON THE RISER WHICH | | WOULD BE LOCATED ON THE NORTH SIDE OF THE BUILDING. | | PLEASE COORDINATE THE PLACEMENT OF THE NEW FIRE | | DEPARTMENT CONNECTION. KNOX-LOCKING CAPS ARE REQUIRED | | FOR THE NEW FIRE DEPARTMENT CONNECTION. THE EXISTING | | SNOOT NEEDS TO BE REMOVED. | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW KITCHEN | | HOODS, DUCTS, AND FIRE SUPPRESSION SYSTEMS. | | | | 4. ON PAGE E-12 IT APPEARS THAT FIRE ALARM EQUIPMENT | | WILL BE CONNECTED TO THE EXISTING FIRE ALARM CONTROL | | PANEL. ON PAGE E-11 HORN STROBES ARE SHOWN IN THE FIRE | | ALARM LEGEND. DUE TO THE OCCUPANT LOAD OF THE BUILDING | | SPEAKER STROBES WITH A VOICE EVACUATION MESSAGE WILL BE | | REQUIRED. A FIRE ALARM PERMIT IS REQUIRED FOR THE FIRE | | ALARM WORK PLANNED FOR THE THIRD FLOOR. THE ENTIRE | | BUILDING SHALL BE EQUIPPED WITH SPEAKER STROBE DEVICES. | | | | 5. THE FIRE SPRINKLER DRAWINGS MAY NOT BE ILLUSTRATIVE | | TO THE WORK THAT HAS BEEN PERFORMED IN THE FIELD. | | PLEASE COORDINATE DRAWINGS WITH THE WORK AND CORRECT | | DISCREPANCIES. | | | | | | DENIED | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-08-05 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-08-05 |
Time |
14:45 |
Sent To |
|
|
Notes |
2009-08-05 15:21:10 | *****DENIED***** | | | | | | 1. THE REVISED E-2 PLAN SHEET, ELECTRICAL PLAN - | | KITCHEN (PATIO LEVEL), DOES NOT CORRELATE WITH PLAN | | SHEET E-2, 2ND FLOOR LIGHTING PLAN MODIFICATION, OF THE | | CITY'S FILED SET. PLEASE EXPLAIN, AMEND, AND/OR ADJUST | | WITH THE PERMIT SET OF PLANS AS NECESSARY. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-07-10 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-07-10 |
Time |
12:05 |
Sent To |
|
|
Notes |
2009-07-10 13:02:25 | *****APPROVED***** | | | | ALL COMMENTS/PROVISOS FROM THE PREVIOUS FIRE PLAN | | REVIEWS HAVE BEEN ADDRESSED; PLAN SHEETS A-2.0, A-2.1, | | A-3, A-4, A-12, A-15, LS-1, E-2, E-4, E-12, FP-1, FP2, | | AND FP-3 WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-05-26 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-05-26 |
Time |
07:17 |
Sent To |
|
|
Notes |
2009-05-26 07:21:22 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE | | SPRINKLER SYSTEM INSTALLATION. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | INSTALLATION OF FIRE ALARM EQUIPMENT. | | | | 3. ALL WORK SUBJECT TO FEILD VERIFICATION AND | | INSPECTION. | | | | 4. PLEASE COMPLETE NECESSARY PLAN REVISIONS AND MEET | | ATT CONSTRUCTION SERVICES DEPARTMENT REQUIREMENTS. | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
N |
Date |
2008-09-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-07-28 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-07-28 |
Time |
07:12 |
Sent To |
|
|
Notes |
2008-07-28 07:15:38 | PLANS WERE PREVIOUSLY REVIEWED BY THIS DEPARTMENT FOR | | THE PROPOSED ROOF TOP ASSEMBLY AREA AND COMMENTS WERE | | PROVIDED. THE STRUCTURAL PLANS SUBMITTED WERE NOT | | REVIEWED BY THIS DEPARTMENT. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2021-01-13 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2021-01-13 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2021-01-13 |
Time |
09:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-23 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-09-23 |
Time |
16:02 |
Sent To |
|
|
Notes |
2009-09-23 16:10:45 | DENIED | | REFERENCE: | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | REVIEW DONE AT THE REQUEST OF THE BUILDING OFFICIAL FOR | | THE PREVIOUS REVIEWER: | | | | A. SHT P-1 SUBMITTED FOR REVISION DOES NOT INDICATE A | | REVISION NUMBER NOR DOES IT INDICATE WHERE THE REVISION | | IS LOCATED BECAUSE OF THE LACK OF REVISION CLOUDS. THAT | | SAID, THE SANITARY PIPING HAS BEEN DELETED, MANY | | FIXTURES HAVE BEEN DELETED FROM THE PLUMBING FIXTURE | | SCHEDULE SUCH AS THE W/C'S, LAVS, FAUCETS, URINAL, | | FLOOR SINKS, HOSE BIBB & WATER HEATER. PLEASE CLARIFY, | | HAVE THESE FIXTURES BEEN CHANGED, DELETED OR BOTH? | | SECTIONS 106.1.1, 106.2 & 106.1.3. | | | | B. SHT P-2 HAS COMPLETLY DIFFERENT INFORMATION THAN | | WHAT IS ON FILE FOR PUBLIC RECORD. WILL ALL THE | | INFORMATION FOR THE BARS BE DELETED? PLEASE CLARIFY. | | SECTIONS 106.1.1, 106.2 & 106.1.3. | | | | *****FROM PREVIOUS REVIEW PERMIT NUMBER 09020194**** | | | | A. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED: | | | | 1. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT | | OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH | | MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED | | DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR | | SERVICING & REPLACEMENT. | | | | 2. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE | | TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE | | MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM. | | SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION | | 402 PIPE SIZING. | | | | 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES | | GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE | | INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E. | | FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1. | | | | 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE | | GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE | | FORTHCOMING). | | | | 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT | | OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD | | SHUT DOWN SHUT OFF VALVE. | | | | 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF. | | SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL | | NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL | | APPLIANCES COMBINED. SECTION 410.2(1)(2)(3). | | | | 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES | | GAS PIPE SIZE PER TABLE 402.4(2) WHICH IS .5 PSI OR | | LESS, BUT DELIVERY PRESSURE IS INDICATED AT 5 PSI. | | PLEASE CLAIRFY. SECTION 402. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2009-11-05 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-11-05 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-11-05 |
Time |
13:53 |
Sent To |
|
|
Notes |
2009-11-05 13:54:42 | FULL ON REVISION | | C--26 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2009-09-12 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-07-10 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-07-10 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2009-05-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-05-05 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-05-05 |
Time |
14:02 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-10-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-07 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-10-07 |
Time |
10:28 |
Sent To |
|
|
Notes |
2008-10-07 10:32:26 | TO "COMM" BD#9 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-25 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-25 |
Time |
08:13 |
Sent To |
|
|
Notes |
2008-08-25 08:14:05 | TO: COM. BD. #1. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-28 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-06-18 |
Time |
15:49 |
Sent To |
|
|
Notes |
2008-06-18 15:49:29 | TO "COMM" BD#45 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
Sent By |
dwise |
Date |
2009-07-09 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
dwise |
Date |
2009-07-09 |
Time |
16:26 |
Sent To |
|
|
Notes |
2009-07-09 16:27:13 | REC#09070700234 ON FILE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2009-11-06 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-11-06 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-11-06 |
Time |
13:06 |
Sent To |
|
|
Notes |
2009-11-06 13:06:28 | REVISED M-1 DELTA 4, M-2 DELTA 5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2009-07-29 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-07-29 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-07-29 |
Time |
08:20 |
Sent To |
|
|
Notes |
2009-07-29 08:23:18 | PAGE M-1 SUBMITTED FOR ADDITION OF KITCHEN TO ROOFTOP | | CAN NOT BE BROUGHT IN AS A REVISION TO THIS PERMIT AS | | PAGE M-1 ALREADY COVERS A DIFFERENT SCOPE OF WORK UNDER | | THIS PERMIT #. MECHANICAL SCOPE NOT REQUIRED AS PART OF | | THIS REVISION. SUBMIT SEPARATE PLANS AND PERMIT | | APPLICATIONS FOR COMMERCIAL KITCHEN HOOD AND HOOD | | SUPPRESSION SYSTEMS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2009-06-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-06-01 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-06-01 |
Time |
15:06 |
Sent To |
|
|
Notes |
2009-06-05 15:07:43 | REVIEW FOR THIS SCOPE OF WORK PERFORMED UNDER PROJECT | | PERMIT #08070215 | | | | NOTE: EXTENSION AND RELOCATION OF EXISTING KITCHEN | | EXHAUST SHALL BE UNDER SEPARATE PERMIT AND EXCLUDED | | FROM THIS SCOPE OF WORK. | | | | NOTE FOR YOUR INFORMATION: MECHANICAL PLAN SHOWS THE | | KITCHEN EXHAUST FAN AT A MINIMUM HEIGHT OF 40" ABOVE | | THE ROOD SURFACE. ARCHITECTURAL PLANS SHOW THE FAN | | SURROUNDED ON 3 SIDES BY A 42" HIGH PARAPET. IF FAN IS | | TO BE LOCATED IN CLOSE PROXIMITY TO PARAPET (MIN. 2' | | SEPARATION) THE DISCHARGE OPENING OF THE FAN MUST BE | | HIGHER THAN THE PARAPET IN ACCORDANCE WITH FBC-M | | 506.5.5. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2009-11-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-11-30 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-11-30 |
Time |
10:26 |
Sent To |
|
|
Notes |
2009-11-30 10:27:21 | REVISIONS OK -- SHTS P-1, P-2 & P-3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-23 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-09-23 |
Time |
15:54 |
Sent To |
|
|
Notes |
2009-09-23 16:02:39 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | REVIEW DONE AT THE REQUEST OF THE BUILDING OFFICIAL FOR | | THE PREVIOUS REVIEWER: | | | | A. SHT P-1 SUBMITTED FOR REVISION DOES NOT INDICATE A | | REVISION NUMBER NOR DOES IT INDICATE WHERE THE REVISION | | IS LOCATED BECAUSE OF THE LACK OF REVISION CLOUDS. THAT | | SAID, THE SANITARY PIPING HAS BEEN DELETED, MANY | | FIXTURES HAVE BEEN DELETED FROM THE PLUMBING FIXTURE | | SCHEDULE SUCH AS THE W/C'S, LAVS, FAUCETS, URINAL, | | FLOOR SINKS, HOSE BIBB & WATER HEATER. PLEASE CLARIFY, | | HAVE THESE FIXTURES BEEN CHANGED, DELETED OR BOTH? | | SECTIONS 106.1.1, 106.2 & 106.1.3. | | | | B. SHT P-2 HAS COMPLETLY DIFFERENT INFORMATION THAN | | WHAT IS ON FILE FOR PUBLIC RECORD. WILL ALL THE | | INFORMATION FOR THE BARS BE DELETED? PLEASE CLARIFY. | | SECTIONS 106.1.1, 106.2 & 106.1.3. | | | | *****FROM PREVIOUS REVIEW PERMIT NUMBER 09020194**** | | | | 1. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE DISH | | WASHER SHALL DISCHARGE VIA A SEPARATE LINE, (SANITARY). | | ARTICLE III SECTION 90-124(7)(B). | | | | 2. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE | | COMBINATION DRAIN & VENT SYSTEM SHALL BE PROVIDED WITH | | A DRY VENT CONNECTED AT ANY POINT WITHIN THE SYSTEM. | | SECTION 912.2.2. SYSTEM NOT VENTED. | | | | 3. SHT P-2 POTABLE WATER RISER DIAGRAM. A WATER HAMMER | | ARRESTOR IS REQUIRED AT THE DISH WASHER. SECTION 604.9. | | | | 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT | | OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH | | MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED | | DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR | | SERVICING & REPLACEMENT. | | | | 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE | | TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE | | MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM. | | SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION | | 402 PIPE SIZING. | | | | 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES | | GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE | | INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E. | | FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1. | | | | 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE | | GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE | | FORTHCOMING). | | | | 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT | | OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD | | SHUT DOWN SHUT OFF VALVE. | | | | 9. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF. | | SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL | | NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL | | APPLIANCES COMBINED. SECTION 410.2(1)(2)(3). | | | | 10. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES | | GAS PIPE SIZE PER TABLE 402.4(2) WHICH IS .5 PSI OR | | LESS, BUT DELIVERY PRESSURE IS INDICATED AT 5 PSI. | | PLEASE CLAIRFY. SECTION 402. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
Sent By |
dwise |
Date |
2009-07-09 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
dwise |
Date |
2009-07-09 |
Time |
16:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2009-11-24 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2009-11-24 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2009-11-24 |
Time |
08:59 |
Sent To |
|
|
Notes |
2009-11-24 09:04:12 | ZONING APPROVAL FOR CHANGES TO THE ROOF TOP TERRACE. | | APPROVAL FOR ANY LANDSCAPE PROPOSED ON ROOF TOP TERRACE | | NECESSARY ACCORDING TO COMMENT ON PERMIT NUMBER | | 08070215. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-09-09 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-09-09 |
Time |
08:18 |
Sent To |
|
|
Notes |
2008-09-09 08:19:34 | ** MAJOR WORKING DRAWING REVIEW ** | | | | ZONING REVIEW: PASS WITH PROVISO: | | | | ** OVERHANG INTO ROW SUBJECT TO AERIAL EASEMENT | | APPROVAL BY CITY COMMISSION | | | | ** SEE ADDITIONAL COMMENTS PERMIT 08070215 | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-06-26 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-06-26 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-06-26 |
Time |
08:36 |
Sent To |
|
|
Notes |
2008-06-26 08:42:27 | ZONING REVIEW: STRUCTURE ONLY- FAIL | | | | 1) PLEASE PROVIDE COPIES OF PROPERTY SURVEY WITH ALL | | PERMIT SUBMISSIONS. | | | | 2)BUILDING SECTION ON A-3 DOES NOT SEEM TO INDICATED | | OVERHANG ON CLEMATIS STREET SIDE. PLEASE CONFIRM. | | | | 3) CONFIRM MAX STRUCTURE HEIGHT TO EAVE OF CUPOLA IS | | 63'-1". MAX HEIGHT IN THIS DISTRICT TO THE MEAN OF | | SLOPED ROOF IS 68'-0". | | | | 4) ANY BUILDING STRUCTURE WHICH INTRUDES INTO THE ROW | | SHALL REQUIRE AN AIR-RIGHTS EASEMENT AS APPROVED BY THE | | CITY COMMISSION. | | | | MATT FLIS - 822-1445 |
|
|