Plan Review Details - Permit 08060488
Plan Review Stops For Permit 08060488
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-07 Cont ID  
Sent By rmcdouga Date 2008-08-07 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-08-07 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By rmcdouga Date 2008-07-30 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2008-07-30 Time 07:14 Sent To  
Notes
2008-07-30 08:11:462004 FBC W/2007 REVISIONS
 INSTALL SIGN ON HIGH RISE
  
 DENIED BY BUILDING
  
 1) THE SIGN IS LOCATED ON A HIGH RISE BUILDING WITH A
 MEAN ROOF HEIGHT ABOVE 60 FEET. THE COMPONENT AND
 CLADDING WINDLOADS ARE REQUIRED TO BE CALCULATED USING
 ASCE7-02 OR WIND TUNNEL TESTING. SEE FBC 1609.1.1 THE
 SIMPLIFIED WINDLOAD METHOD CAN NOT BE USED FOR
 BUILDINGS WITH A MEAN ROOF HEIGHT OF 60 FEET AND THE
 BUILDING HAS A MEAN ROOF HEIGHT OF 217 FEET. REPEAT
 COMMENT.
  
 2) THE FBC TABLE NUMBERS REFERENCED ON THE ENGINEERING
 WERE CHANGED IN THE REVISIONS TO THE 2004 FBC. PLEASE
 NOTE.
  
 3)THE NEW DRAWINGS ARE REQUIRED TO HAVE THE CITY
 PLACE STAMP OF APPROVAL.
  
 4) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By rmcdouga Date 2008-07-09 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2008-07-09 Time 08:58 Sent To  
Notes
2008-07-09 08:58:462004 FBC W/2007 REVISIONS
 INSTALL SIGN ON HIGH RISE
  
 DENIED BY BUILDING
  
 1) THE SIGN IS LOCATED ON A HIGH RISE BUILDING WITH A
 MEAN ROOF HEIGHT ABOVE 60 FEET. THE COMPONENT AND
 CLADDING WINDLOADS ARE REQUIRED TO BE CALCULATED USING
 ASCE7-02 OR WIND TUNNEL TESTING. SEE FBC 1609.1.1
  
 2) THE FBC TABLE NUMBERS REFERENCED ON THE ENGINEERING
 WERE CHANGED IN THE REVISIONS TO THE 2004 FBC. PLEASE
 NOTE.
  
 3) THE DESIGN CRITERIA IN THE TITLE BLOCK OF THE
 DRAWINGS INCORRECTLY SPECIFY THE 2004 FBG. PLEASE
 CHANGE TO FBC.
  
 4) PLEASE COORDINATE THE SIZE OF THE LETTERING ON THE
 FRONT AND SIDE VIEW DRAWINGS. FBC 106.1.1* CITY
 AMENDMENTS AND ZONING COMMENTS.
  
 5) THE VALUE FOR THE WORK IS TOO LOW. FBC 108.3* CITY
 AMENDMENTS STATES THAT FOR PERMITTING PURPOSES
 VALUATION OF WORK INCLUDES DESIGN, ENGINEERING, LABOR,
 MATERIALS, ELECTRICAL, OVERHEAD AND PROFIT. THE VALUE
 OF THE WORK BASED ON MARSHALL AND SWIFT HAS BEEN
 DETERMINED AS $13,540.00. PLEASE PAY ADDITIONAL FEES.
 NOTE:A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 10:12 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 10:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-23 Cont ID  
Sent By btrobaug Date 2008-06-23 Time 10:22 Rev Time 0.00
Received By btrobaug Date 2008-06-23 Time 10:22 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 09:11 Sent To E
Notes
2008-07-28 09:11:40TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 10:49 Sent To Z
Notes
2008-07-23 10:49:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-09 Cont ID  
Sent By rmcdouga Date 2008-07-09 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2008-06-18 Time 09:38 Sent To  
Notes
2008-06-18 09:39:28TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-07-25 Cont ID  
Sent By eschneid Date 2008-07-25 Time 16:01 Rev Time 0.00
Received By eschneid Date 2008-07-25 Time 16:01 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By eschneid Date 2008-06-19 Time 09:13 Rev Time 0.00
Received By eschneid Date 2008-06-19 Time 09:13 Sent To E
Notes
2008-06-19 09:41:23FAILED
  
 1) THE SIGN BACKING'S DIMENSIONS ON THE FRONT VIEW IS
 LARGER THAN THE DIMENSIONS OF THE SIGN BACKING APPROVED
 IN THE CITYPLACE MASTER SIGN PLAN - THE SIGN BACKING IS
 APPROVED AS ONLY 7 FEET NOT 7'2" TALL AS SHOWN ON
 PERMIT.
  
 2)ON THE FRONT VIEW THE DIMENSION LINE FOR THE
 OVERALL HEIGHT DOES NOT CORRESPOND TO THE EDGE OF THE
 SIGN BACKING.
  
 3) THE OVERALL HEIGHT OF THE CHANNEL LETTERS IS SHOWN
 AS 67" ON THE FRONT VIEW AND 70" ON THE SIDE VIEW.
 THESE SHALL BE THE SAME.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  