2008-06-16 14:04:12 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE SUBMITTED ISOMETRIC IS NOT INDICATING THE |
| REQUIRED TEE FITTING OR THE CORRESPONDING LENGTH AND |
| PIPE SIZE AFTER THE MP REGULATOR TO THE TEE FITTING FOR |
| THE NEW 150,000 BTU TANKLESS WATER HEATER AND 50,000 |
| BTU GRILL. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| NOTE: PIPE SIZE FROM THE OUTLET SIDE OF THE MP |
| REGULATOR TO THE TEE FITTING SHALL BE 1 INCH. PER |
| FBC-2004 FUEL GAS TABLE 402.4(2). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |