Plan Review Details - Permit 08060314
Plan Review Stops For Permit 08060314
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-15 Cont ID  
Sent By jwitmer Date 2008-10-15 Time 16:40 Rev Time 2.22
Received By jwitmer Date 2008-10-15 Time 16:40 Sent To  
Notes
2008-10-15 16:47:01BUILDING PLAN REVIEW
 PERMIT: 08060314
 ADD: 1025 23RD ST
 CONT: MURRAY LOGAN CONSTRUCRION
 TEL: (561)248-1473
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1-2 COMPLIED.
  
 3) 2ND REQUEST, SOILS REPORTS SUPPLYED ARE COLOR COPIES
 NOT ORIGINAL SIGNED AND SEALED REPORTS. PROVIDE SOILS
 REPORT WITH THE MINIMUM SAFE BEAARING VALUE. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6-12) COMPLIED.
  
 13) 2ND REQUEST, SHEET A-7 ANTENNA DETAIL PLEASE SUBMIT
 ENGINEERING FOR COMMUNICATIONS ANTENNA1609.1.1(7). THIS
 DETAIL INDICATES THE ANTENNA BASE TOWER AND ASSEMBLY
 SHALL MEET THE LATEST FL BLDG LOAD REQUIREMENTS,
 CONTRACTOR SHALL SUBMIT SHOP DRAWINGSWITH STRUCTURAL
 ENGINEERS CALCULATIONS TO SUPPORT REQUIREMENTS. THE
 PLANS DO NOT EVEN MENTION WHAT THE WIND ZONE IS OR THE
 EXTENT THIS TOWER CAN BE RAISED?
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By jwitmer Date 2008-07-01 Time 12:11 Rev Time 2.22
Received By jwitmer Date 2008-07-01 Time 12:11 Sent To  
Notes
2008-07-01 13:35:13BUILDING PLAN REVIEW
 PERMIT: 08060314
 ADD: 1025 23RD ST
 CONT: MURRAY LOGAN CONSTRUCRION
 TEL: (561)248-1473
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.SHEET
 S-1 INDICATES JUST AMENDMENTS PLEASE UPDATE PLANS TO
 INCLUDE THE CURRENT 2007 AMENDMENTS.
  
 2) PLEASE PROVIDE THE FOLLOWING INFORMATION TO ALLOW
 FOR A ACCCURATE PLAN REVIEW OF THIS PROJECT. 110.2* W.
 P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED
 FOR RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
  
 3) PROVIDE SOILS REPORT WITH THE MINIMUM SAFE BEAARING
 VALUE. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6) PLANS FAIL TO INDICATE COMPLIANCE WITH 1816.1.
 TERMITE PROTECTION.
  
 7) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 7A) EXTERIOR DOORS
 7B) LOUVERS
 C) ROOF ASSEMBLIES
  
 8) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S- 5 INDICATES 2000 GALLON DEISEL FUEL
 CONVAULT, PLEASE SUBMIT PRODUCT INFORMATION 414.5.5
 SPILL CONTROL, DRAINAGE AND CONTAINMENT.
  
 11) PLANS FAIL TO PROVIDE ANCHORAGE FOR THE GENERATOR ,
 ANCHORAGE AGAINST MOMENT OF OVERTURNING. 1609.1.3.
  
 12) SHEET A-7 THE LIGHT POLE DETAIL INDICATES THE
 DESIGN TO THE SOUTH FLORIDA BUILDING CODE PLEASE
 CORRECT TO THE 2007 FBC AND SUBMIT WIND CALCULATIONS.
  
 13) SHEET A-7 ANTENNA DETAIL PLEASE SUBMIT ENGINEERING
 FOR COMMUNICATIONS ANTENNA1609.1.1(7).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 08:39 Sent To  
Notes
2008-10-10 08:39:28** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4. THE SAME
 COMMENT EXISTS. THE RESPONSE GOES INTO LENGTHY DETAIL
 ABOUT THE FPL TRANSFORMER AND SERVICE ENTRANCE
 CONDUCTORS. THE PREVIOUS COMMENT HAD NOTHING TO DO WITH
 THE FPL TRANSFORMER AS ALL WORK ON THE LINE SIDE AND
 MANY TIMES ON THE LOAD SIDE OF THEIR TRANSFORMER IS NOT
 UNDER THE RESPONSIBILITY OR JURISDICTION. IN FACT THE
 UTILITY WORK IS EXEMPT UNDER FEDERAL LAW. THE COMMENT
 HAD TO DO WITH THE ONLY TRANSFORMER ON RISER WHICH IS
 UNDER THE REVIEW OF THIS OFFICE. PLEASE SEE TRANSFORMER
 FED FROM PDP. THIS SHOWS 4-#6 CONDUCTORS AND THAT IS
 ALL. IS THE 4TH #6 A NEUTRAL WHICH WOULD NOT BE
 INSTALLED OR IS IT AN EQUIPMENT WHICH IS REQUIRED?
 250.20,250.30,250.50,.250.110,250.50 ETC
  
 2) NOTE: PLEASE REMOVE ANY REQUIREMENTS AND NOTES THAT
 LIGHTING DESIGN IS PER PALM BEACH COUNTY LIGHTING CODE.
 PALM BEACH COUNTY LIGHTING CODE/ORDINANCES IS NOT PART
 OF THE CITY OF WEST PALM BEACH.
 THE LIGHTING IS HOWEVER UNDER THE REVIEW OF FBC
 13-415.2.ABC.1.3 FOR MAXIMUM ALLOWANCES PER THE FLORIDA
 ENERGY CODE. PLEASE BE SURE TO CHECK THE FEDERAL
 REQUIREMENTS UNDER THE ASHRAE STANDARDS OF 90.1
 (SECTION 2.3) BEFORE A BUILDING MAY BE EXEMPT. ANY
 REQUIREMENTS OF A FEDERAL LEVEL ARE MORE RESTRICTIVE
 THAN STATE CODES AND APPLY. NO REQUEST WAS MADE FOR
 ENERGY CALCULATIONS FROM ELECTRICAL REVIEW OR OTHER
 REVIEW TRADES FOR THESE SPECIFIC ITEMS. PLEASE EXPLAIN
 WHY THE PACKAGE CONTAINS SECTIONS OF THE FLORIDA ENERGY
 CODE HIGH-LIGHTED AND RESPONSE MENTIONS THIS BUILDING
 IS EXEMPT?
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO GFI SHOWN ON GENERATOR. THE RESPONSE LETTER
 MENTIONS THIS IS FOR GROUND FAULT INDICATION AND TO SEE
 EXPLANATION/REVISED RISER. PLEASE EXPLAIN WHERE THIS
 STANDARD COMES FROM? THE STANDARD OF GFI IS FOR
 PERSONNEL PROTECTION AND EVEN WHEN REQUIRED SYSTEMS
 SUCH AS THOSE IN 240.12, 230.95 THESE ARE GFP WHICH IS
 NOT THE SAME.
 PLEASE REVISE RISER OR SYMBOLS TO ESTABLISH GROUND
 FAULT ALARM OR INDICATION.
 FBC 106.1.1 FOR CLARITY, COORDINATION AND ADDITIONAL
 INFORMATION.
  
 4) NOTE: AS NOTED FOR INFORMATION THIS WILL BE PART OF
 BUILDING REVIEW: THE SUBMITTED WIND LOAD CALCULATIONS
 DO NOT CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FS
 471.025. THIS SAME DESIGNER/ENGINEER HAS HAD THIS SAME
 COMMENT ON NUMEROUS OTHER PROJECTS. THIS OFFICE HAS
 PLACED A CALL TO SAID DESIGNER AND LEFT A MESSAGE TO
 CONTACT THIS OFFICE.
 THESE WILL BE RETAINED AND PLACED WITH OTHER PREVIOUSLY
 RETAINED DOCUMENTS FOR REVIEW FROM THE FLORIDA BOARD OF
 ENGINEERS.
 FAC 61G15-23.002, FS 4713025
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #8. RESPONSE MENTIONS
 DESIGN IS 480V 3-PHASE WITH GROUND AND THERE ARE NO 277
 NEUTRAL LOADS. THIS REVIEWER IS CONFUSED AT THIS
 RESPONSE AS THE PREVIOUS COMMENT DID NOT STATE ANYTHING
 ABOUT A NEUTRAL WHICH IS A *GROUNDED CONDUCTOR*. THE
 PREVIOUS COMMENT STATED *EQUIPMENT * GROUNDING*
 CONDUCTORS MISSING FROM ATS TO GENERATOR, FIRST MEANS
 OF DISCONNECT TO THE ATS AND ATS TO THE PDP. THE
 RESPONSE MENTIONS NO NEUTRALS (GROUNDED CONDUCTORS) YET
 RISER SHOWS THEM????
 250.6, 250.24, 250.110, 250.122 ETC
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-07 Cont ID  
Sent By dpalmer Date 2008-07-07 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2008-07-07 Time 13:52 Sent To  
Notes
2008-07-07 13:53:00** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE VERIFY WHY THE GENERATOR IS SHOWING GFI
 PROTECTION. IT IS UNCLEAR AT THIS TIME WHY THIS TYPE PF
 PERSONNEL PROTECTION IS BEING PROVIDED ON THE GENERATOR
 BREAKER.
 ** CODE SECTIONS SUCH AS 240.13, 230.95 REQUIRED GROUND
 FAULT BUT NOT IN THIS CASE.
  
 2)NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETSFOR THE NEW PROPOSED ATS AND GENERATOR.
 90.7, 110.3, 702.6
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 3) NOTE: PLEASE VERIFY THE NEW MAIN WHICH INDICATES A
 SHUNT TRIP BREAKER ACTUALLY STILL CONTAINS THE MANUAL
 MEANS OF DISCONNECT RATED FOR LOAD SERVED PER 230.76,
 230.79
  
 4) NOTE: PLEASE VERIFY THE NUMBER OF CONDUCTORS ON THE
 LINE SIDE OF THE TRANSFORMER.IT APPEARS TO INDICATE A
 NEUTRAL AND NOT AN EQUIPMENT GROUND.
 PLEASE VERIFY THE CONDUCTORS ON THE LOAD SIDE OF THE
 TRANSFORMER ALSO. WILL THE EQUIPMENT GROUNDING
 CONDUCTOR BE THE SAME SIZE?
 240.21, 310.16, 250.20 ETC
  
 5) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION OF THE
 TRANSFORMER. ALONG WITH THE CONDUCTOR SIZE. 250.20,
 250.50, 250.58, 25.66.
  
 6) NOTE: THE PHOTO-METRICS NOTED ON E-1 STATE
 REQUIREMENTS PER PALM BEACH COUNTY. THIS PROJECT IS
 LOCATED WITH THE CITY OF WEST PALM BEACH. THE LIGHTING
 AS SHOWN IS NOT REQUIRED.
 PLEASE BE SURE TO ADJUST LOCATION.
  
 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS FUEL
 TANKS/PLANS WILL BE REQUIRED TO BE STAMPED BY DERM.
 (DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT.
  
 8) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAIN TO ATS AND ATS TO DISTRIBUTION
 BOARD ARE MISSING.
 250.110, 250.122 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-15 Cont ID  
Sent By mwennerg Date 2008-07-15 Time 15:40 Rev Time 0.00
Received By mwennerg Date 2008-07-15 Time 15:40 Sent To  
Notes
2008-07-15 15:48:44***DENIED***
  
 1) PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR
 PROPOSED 2000 GALLON DIESEL TANK.
  
 2) DERM TO BE CONTACTED FOR APPROVAL OF THE 2000 GALLON
 DIESEL TANK.
  
 3) PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED.
  
  
 5) PLACARDING IN COMPLIANCE WITH NFPA 30 AND NFPA 704
 TO BE PROVIDED ALONG WITH NO SMOKING SIGNS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-10-10 Cont ID  
Sent By tgordon Date 2008-10-10 Time 09:54 Rev Time 0.30
Received By tgordon Date 2008-10-10 Time 09:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-06-11 Cont ID  
Sent By swurafti Date 2008-06-11 Time 11:26 Rev Time 0.00
Received By swurafti Date 2008-06-11 Time 11:26 Sent To  
Notes
2008-06-11 11:26:43HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 09:57 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 09:57 Sent To  
Notes
2008-09-26 10:00:36TO "COMM" BD#26--PLANS ON RACK/LARGE FOLDED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-15 Cont ID  
Sent By mwennerg Date 2008-07-15 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2008-06-11 Time 16:06 Sent To  
Notes
2008-06-11 16:06:45TO "COMM" BD#18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By tgordon Date 2008-10-10 Time 09:54 Rev Time 0.30
Received By tgordon Date 2008-10-10 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By tgordon Date 2008-06-30 Time 11:05 Rev Time 0.45
Received By tgordon Date 2008-06-30 Time 11:05 Sent To  
Notes
2008-06-30 11:46:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS SHOW TWO AIR CONDITIONING SYSTEMS ARE TO BE
 INSTALLED, PLEASE SUBMIT A MECHANICAL (A/C) PLAN
 SHOWING THE EQUIPMENT LOCATION AND EQUIPMENT SCHEDULE,
 PER 2004 FBC 106.3.5.
  
 2) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR THE
 2000 GALLON FUEL STORAGE TANK BEING INSTALLED, PER 2004
 FBC/M 1301.
  
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR THE
 DUTY FAN AND LOUVERS, PER 2004 FBC 1609.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 GENERATOR ROOM LOUVERS, SEE FS 553.842(1) AND FAC RULE
 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By kstevens Date 2008-10-03 Time 17:20 Rev Time 0.00
Received By kstevens Date 2008-10-03 Time 15:59 Sent To  
Notes
2008-10-03 17:26:46PLUMBING PERMIT REQUIRED. SEE BACKFLOW STAMP ON SHT M-1

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-11 Cont ID  
Sent By mperson Date 2008-07-11 Time 10:25 Rev Time 0.00
Received By mperson Date 2008-07-11 Time 10:25 Sent To  
Notes
2008-07-11 10:58:51PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET S-1 AND S-2, ELECTRICAL BUILDING-FLOOR PLANS
 INDICATES 3 ALUMINUM SCUPPERS WITH DOWNSPOUTS AND SHEET
 S-6 INDICATES A SCUPPER AND CONDUCTOR HEAD- FRONT-SIDE
 DETAILS, HOWEVER THERE ARE NO SIZES OF THE SCUPPER,
 CONDUCTOR HEAD OR DOWNSPOUTS BEING INDICATED AS WELL AS
 THE REQUIRED SECONDARY ROOF DRAINAGE AND ROOF
 CALCULATION BEING INDICATED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
  
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTION 1106.
  
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
  
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
  
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 NOTE: THE SCUPPER DETAIL ON SHEET S-6 INDICATES THE
 SCUPPER 3/4" ABOVE THE ROOF. IS IT THE INTENT TO HAVE
 3/4" OF WATER ON THE ROOF AS INDICATED?
  
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 2. THERE ARE NO FLOOR DRAINS OR POTABLE WATER HOSE
 BIBBS BEING INDICATED ON THE PLANS. IS IT THE INTENT
 NOT TO HAVE THESE ITEMS OR IS THIS AN OVERSIGHT?
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-06 Cont ID  
Sent By bpowell Date 2008-10-06 Time 10:55 Rev Time 0.00
Received By bpowell Date 2008-10-06 Time 10:55 Sent To  
Notes
2008-10-06 10:56:391. THE PROVIDED EASEMENT CONSENT FORM MUST BE COMPLETED
 AND APPROVED.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT;
 BOBBY POWELL JR., [email protected], (561) 822-1449

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-24 Cont ID  
Sent By bpowell Date 2008-06-24 Time 10:32 Rev Time 0.00
Received By bpowell Date 2008-06-24 Time 10:32 Sent To  
Notes
2008-06-24 10:36:131. THE APPROACH WILL NEED TO BE CURBED. PER SECTION
 94-443(5) LANDSCAPE AREAS AND PLANT MATERIALS MUST BE
 PROTECTED FROM VEHICULAR ENCROACHMENT.
  
 2. AN EASEMENT CONSENT FORM.
  
 3. FUEL TANK NEEDS TO BE SCREENED.
  
 4. A R.O.W PERMIT NEEDS TO BE IN PLACE FOR THE
 APPROACH.
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY POWELL
 JR., (561) 822-1401, [email protected]