Plan Review Details - Permit 08060247
Plan Review Stops For Permit 08060247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-31 Cont ID  
Sent By rmcdouga Date 2008-10-31 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2008-10-31 Time 11:26 Sent To  
Notes
2008-10-31 11:28:02CONTRACTOR SUBMITTED DOOR BUCK FASTENING DETAIL AS
 REQUESTED FOR PROVISO ITEM #2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By rmcdouga Date 2008-10-03 Time 12:29 Rev Time 0.00
Received By rmcdouga Date 2008-10-03 Time 12:29 Sent To  
Notes
2008-10-03 14:26:07BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLION THAT HAVE BEEN REVIEWED BY
 THE DESIGNER OF RECORD. FAC RULE 9B-72.
  
 2) SUBMIT TWO COPIES OF SIGNED AND SEALED DOOR BUCK
 FASTENING DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-09-22 Time 14:54 Rev Time 0.00
Received By rmcdouga Date 2008-07-01 Time 12:10 Sent To  
Notes
2008-07-01 11:40:462004 FBC W/2007 REVISIONS
 ADDITION TO SFD
  
 DENIED BY BUILDING
  
 1)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY (PH.233-5025). THE PLANS MUST BE
 STAMPED AND THE PAID RECEIPT SUBMITTED TO THE CITY
 BUILDING DEPARTMENT.
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. THE FORM LISTS R-5 WALL
 INSULATION AND THE PLANS SPECIFY R-4.5 (A MINIMUM OF
 R-5 IS REQUIRED BY METHOD A). PLEASE CORRECT. THE FORM
 LISTS R-30 CEILING INSULATION AND THE PLANS HAVE R-32.
 PLEASE CORRECT. SEE FBC 13-600.
  
 3) SHOW COMPLIANCE WITH 2004 FBC EXISTING BUILDING
 SECTION 904.2, WHICH REQUIRES SMOKE ALARMS IN THE
 EXISTING BUILDING AS WELL AS THE ADDITION. SEE ALSO
 R313.1.1.
  
 4) THE NEW BATHROOM IS REQUIRED TO HAVE A DOOR WITH A
 29" CLEAR OPENING, MEASURED FROM THE FACE OF THE DOOR
 TO THE OPPOSITE STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 R322.
  
 5) SPECIFY THE WALL THICKNESS OF THE 3" PIPE COLUMN.
 SPECIFY THE WELD TYPE AT THE BASE AND CAP OF THE
 COLUMN. PROVIDE A DETAIL OF THE COLUMN CAP, SHOWING THE
 NUMBER, SIZE, ETC. OF EMBEDS.
  
 6) PROVIDE WINDOW AND DOOR BUCK DETAILS. SEE FBC
 R613.6.1.1.
  
 7) SPECIFY HOW TERMITE PROTECTION WILL BE PROVIDED ON
 THE PLANS AS REQUIRED BY R320.1.
  
 8) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 11) THE ROOF SHEATHING FASTENING SPECIFIED ON SHEET 1
 IS INCORRECT. SEE R803.2.3.1 SHEATHING FASTENINGS. WOOD
 STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO ROOF
 FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON CENTER
 AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY,
 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK
 FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3
 FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE
 WITH FIGURE R803.2.3.1 .
  
 12) THE ROOF FASTENING SCHEDULE ON SHEET 3 DOES NOT
 SPECIFY RING SHANK NAILS. THE ROOF SHEATHING THICKNESS
 SPECIFIED ON SHEET 3 IS DIFFERENT THAN ON SHEET 1.
 PLEASE COORDINATE NOTES. SEE FBC R803.2.3.1 AND FBC
 106.1.1* CITY AMENDMENTS.
  
 13) ON SHEET 2 , A 140 MPH 3 SECOND GUST WIND SPEED
 WITH EXPOSURE B AND C IS SPECIFIED. ON SHEET 3 A 150
 MPH 3 SECOND GUST WIND SPEED AND EXPOSURE C IS
 SPECIFIED. PLEASE COORDINATE THE DESIGN DATUM. SEE R
 301.2.1.
  
 14) THE COMPONENT AND CLADDING PRESSURES FOR EXPOSURE C
 SPECIFIED ON SHEET 2 ARE TOO LOW. SEE TABLE R301.2(2)
 AND TABLE R301.2(3). THE ADJUSTMENT COEFFICIENT FOR
 EXPOSURE C WITH A 15' MRH IS 1.21. PLEASE REVISE OR
 SUBMIT SIGNED AND SEALED CALCULATIONS FOR THE COMPONENT
 AND CLADDING VALUES THAT ARE SPECIFIED ON THE PLANS.
  
 15)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 16) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG
 WINDOWS, MULLIONS AND STORM PANELS THAT ARE TO BE
 REINSTALLED. SPECIFY THE MOUNT TYPE, FASTENERS,
 FASTENER SPACING, EDGE DISTANCE, GLASS SEPARATION, ETC.
 FOR THE STORM PANELS. CIRCLE ALL INFORMATION USED TO
 DETERMINE ADEQUATE INSTALLATION FROM THE STORM PANEL
 PRODUCT APPROVALS.
  
 17) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO
 INSTALL THE GAF MODIFIED ROOF SYSTEM. SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 OF THE ROOFING NOA.
  
 18) PLEASE SUBMIT ONE SET OF OLD PLANS WITH A RESPONSE
 LETTER INDICATING HOW AND WHERE ON THE PLANS THE
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-01 Cont ID  
Sent By btrobaug Date 2008-10-01 Time 12:02 Rev Time 0.00
Received By btrobaug Date 2008-10-01 Time 11:09 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By btrobaug Date 2008-06-16 Time 09:33 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 09:02 Sent To M
Notes
2008-06-16 09:33:01 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE ARE HI HATS ON THE PLAN THAT ARE SO LIGHTLY
 PRINTTED IT IS NOT CLEAR IF THEY ARE TO BE INSTALLED OR
 IF THEY ARE AN ERROR.PLEASE ADDRESSTHIS ISSUE ON THE
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 11:25 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 11:25 Sent To L
Notes
2008-10-22 11:25:49TO "Z" BOX/RESUB--FOR LANDSCAPING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 15:08 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 15:08 Sent To E
Notes
2008-09-30 15:09:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 14:51 Sent To Z
Notes
2008-09-22 14:52:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-01 Cont ID  
Sent By rmcdouga Date 2008-07-01 Time 12:10 Rev Time 0.00
Received By rmcdouga Date 2008-06-10 Time 10:55 Sent To  
Notes
2008-06-10 10:55:42TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2008-10-31 Cont ID  
Sent By rkussner Date 2008-10-31 Time 10:34 Rev Time 0.00
Received By rkussner Date 2008-10-31 Time 10:34 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-10-23 Cont ID  
Sent By rkussner Date 2008-10-23 Time 15:02 Rev Time 0.00
Received By rkussner Date 2008-10-23 Time 15:02 Sent To  
Notes
2008-10-23 15:04:49***LANDSCAPE REVIEW FAILED***
  
 WITH THE EXCEPTION OF THE LANDSCAPE PLAN BEING
 SUBMITTED, NONE OF THE OTHER COMMENTS MADE ON 9/26/08
 HAVE BEEN ADDRESSED.
  
 PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462 IF YOU
 HAVE ANY QUESTIONS.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By rkussner Date 2008-09-26 Time 17:17 Rev Time 0.00
Received By rkussner Date 2008-09-26 Time 17:16 Sent To  
Notes
2008-09-26 17:33:13***LANDSCAPE REVIEW FAILED***
  
 1. BECAUSE THE ADDITION EXCEEDS 50% OF THE IMPROVEMENT
 VALUE, THE ENTIRE SITE MUST BE BROUGHT UP TO CURRENT
 LANDSCAPE STANDARDS. PLEASE SUBMIT A LANDSCAPE PLAN
 BASED UPON ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 2, PLEASE PROVIDE THE REQUIRED LANDSCAPE CALCULATIONS
 SUCH AS TREES REQUIRED AND TREES PROVIDED, SHRUBS
 REQUIRED AND SHRUBS REQUIRED AND SO ON.
  
 3. NOTES SHALL APPEAR ON THE LANDSCAPE PLAN: ALL
 PROHIBITED PLANT SPECIES SHALL BE REMOVED FROM THE
 DEVELOPMENT SITE. ALL LANDSCAPED AREAS SHALL BE
 PROVIDED WITH 100% IRRIGATION COVERAGE. SOD AND
 IRRIGATION IS REQUIRED IN THE RIGHT-OF-WAY BETWEEN THE
 PROPERTY LINE AND THE PAVED ROAD. ALL PLANT MATERIAL
 SHALL BE FLORIDA #1 GRADE OR BETTER.
  
 4, ON THE LANDSCAPE PLAN, PLEASE PROVIDE THE LOCATION
 OF ALL UTILITIES, EASEMENT, OVERHEAD LINES, OVERHANGING
 TREE LIMBS FROM NEIGHBORING PROPERTY AND ANYTHING ELSE
 THAT MAY HAVE AN IMPACT UPON THE LANDSCAPING.
  
 5. IDENTIFY ALL EXISTING AND PROPOSED TREES, SHRUBS AND
 GROUND COVER ON THE LANDCAPE PLAN AND SHOW WHAT ITEMS
 WILL REMAIN, BE REMOVED OR RELOCATED.
  
 6. SUBMIT A TREE ALTERATION PERMIT APPLICATION TO THE
 PLANNING AND ZONING DEPARTMENT IF ANY TREES WILL BE
 REMOVED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME, ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-02 Cont ID  
Sent By tgordon Date 2008-10-02 Time 08:07 Rev Time 0.40
Received By tgordon Date 2008-10-02 Time 08:07 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By tgordon Date 2008-06-16 Time 13:30 Rev Time 0.30
Received By tgordon Date 2008-06-16 Time 13:30 Sent To P
Notes
2008-06-16 13:40:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE FILL IN LINES 11 AND 12 ON THE ENERGY
 CALCULATIONS, PER 2004 FBC 13-607.1.C.1.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) THE COOLING LOAD CALCULATIONS ARE SHOWING THE WRONG
 TOTAL AREA (1632), THIS SHOULD ONLY SHOW THE TOTAL
 SQUARE FEET UNDER AIR. SEE ATTACHED PROPERTY APPRAISER
 PRINT OUT SHOWING EXISTING SQ. FT. UNDER AIR THEN SEE
 THE PLANS AND SCALE THE NEW ADDITION, MY CALCULATION
 CAME UP WITH 1388 SQUARE FEET UNDER AIR. PLEASE CORRECT
 COOLING LOAD CALCULATIONS, PER 13-607.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-02 Cont ID  
Sent By mperson Date 2008-10-02 Time 16:07 Rev Time 0.30
Received By mperson Date 2008-10-02 Time 16:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By mperson Date 2008-06-20 Time 16:04 Rev Time 0.00
Received By mperson Date 2008-06-20 Time 16:04 Sent To B
Notes
2008-06-20 16:09:26PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2ADDITION PLUMBING AND SANITARY RISER:
 PLEASE INDICATE THE FOLLOWING PER FBC- PLUMBING
 SECTIONS.
  
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
  
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-25 Cont ID  
Sent By mcruz Date 2008-09-25 Time 17:15 Rev Time 0.00
Received By mcruz Date 2008-09-25 Time 17:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 14:24 Sent To E
Notes
2008-06-10 14:26:44***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZLDRS.
  
 2)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO ALL ADJACENT PROPERTY LINES (WEST SIDE).
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK